Comprehensive Analysis of Common Accessories of Dry-Type Transformers: From Enclosures to Copper Bars, Master Key Configurations in One Article

Rockwell
Rockwell
Field: Manufacturing
China

Enclosures

Enclosures can be categorized into indoor and outdoor types.

For indoor applications, considering heat dissipation and maintenance needs, it is generally recommended not to install an enclosure if there is sufficient installation space. However, if required by the user, enclosures with multiple observation holes can be provided. Enclosures can also be painted in colors preferred by the user.

The protection level of enclosures is typically IP20 or IP23:

  • IP20 prevents the ingress of solid foreign objects larger than 12 mm and protects against accidental impacts.

  • In addition to the functions of IP20, IP23 can prevent water droplets from entering within a 60-degree vertical angle, making it suitable for outdoor installation.

Enclosure materials include ordinary steel plates, injection-molded plastics, stainless steel plates, aluminum alloy composite plates, etc.

Enclosures.jpg

Temperature Controllers

All transformers are equipped with overheating protection devices. These devices detect and control the transformer temperature via PT thermistors built into the low-voltage windings, and output digital signals through an RS232/485 communication interface. The device provides the following functions:

  • During transformer operation, the temperature values of the three-phase windings are displayed on the circuit.

  • Displays the temperature value of the hottest-phase winding.

  • Over-temperature alarm and over-temperature shutdown.

  • Audible and visual alarms, and fan activation.

Temperature Controllers.jpg

Air-Cooling Devices

  • The cooling methods for dry-type transformers can be divided into natural air cooling (AN) and forced air cooling (AF).

  • Under natural air cooling (AN), the transformer can continuously supply 100% of its rated capacity under normal operating conditions.

  • Under forced air cooling (AF), a 50% capacity increase can be achieved under normal operating conditions, making it suitable for various emergency overloads or intermittent overload operations. Continuous overload operation using forced air cooling (AF) is generally not recommended, as it leads to greater increases in load losses and impedance resistance.

Air-Cooling Devices.jpg

Copper Bars

  • Generally, the cable inlet/outlet methods are classified into top inlet/outlet, bottom inlet/outlet, and side inlet/outlet.

  • For transformers with a rated power ≤ 200 kVA, the conventional outlet method is still used; side outlets are connected by the user via cables.

  • When the rated power is ≥ 1600 kVA:

  • Double-row feeders with a spacing of 10 (for 1600–2000 kVA) or 12 (for 2500 kVA) are used for phases A, B, and C.

  • Since the neutral line is located at the top of the transformer, if the neutral line needs to be led out from the bottom of the switchgear, it is recommended that the transformer’s neutral line still enters the switchgear from the top.

Give a tip and encourage the author!
Recommended
What causes a transformer to be noisier under no-load conditions?
What causes a transformer to be noisier under no-load conditions?
When a transformer is operating under no-load conditions, it often produces louder noise than under full load. The primary reason is that, with no load on the secondary winding, the primary voltage tends to be slightly higher than nominal. For example, while the rated voltage is typically 10 kV, the actual no-load voltage may reach around 10.5 kV.This elevated voltage increases the magnetic flux density (B) in the core. According to the formula:B = 45 × Et / S(where Et is the designed volts-per-
Noah
11/05/2025
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
When installing an arc suppression coil, it is important to identify the conditions under which the coil should be taken out of service. The arc suppression coil should be disconnected under the following circumstances: When a transformer is being de-energized, the neutral-point disconnector must be opened first before performing any switching operations on the transformer. The energizing sequence is the reverse: the neutral-point disconnector should be closed only after the transformer is energ
Echo
11/05/2025
What fire prevention measures are available for power transformer failures?
What fire prevention measures are available for power transformer failures?
Failures in power transformers are commonly caused by severe overload operation, short circuits due to winding insulation degradation, aging of transformer oil, excessive contact resistance at connections or tap changers, failure of high- or low-voltage fuses to operate during external short circuits, core damage, internal arcing in oil, and lightning strikes.Since transformers are filled with insulating oil, fires can have severe consequences—ranging from oil spraying and ignition to, in extrem
Noah
11/05/2025
What are the common faults encountered during the operation of power transformer longitudinal differential protection?
What are the common faults encountered during the operation of power transformer longitudinal differential protection?
Transformer Longitudinal Differential Protection: Common Issues and SolutionsTransformer longitudinal differential protection is the most complex among all component differential protections. Misoperations occasionally occur during operation. According to 1997 statistics from the North China Power Grid for transformers rated 220 kV and above, there were 18 incorrect operations in total, of which 5 were due to longitudinal differential protection—accounting for approximately one-third. Causes of