The main parts of an air insulated primary medium voltage switchgear and their application

Edwiin
Edwiin
Field: Power switch
China

Medium voltage switchgear plays a crucial role in the energy distribution process within alternating current (AC) systems, facilitating the flow of power from generation through transmission to end-users. This essential equipment is governed by specific standards that define its specifications, terminology, ratings, design criteria, construction practices, and testing protocols. For the European region, these guidelines are detailed in the following International Electrotechnical Commission (IEC) standards:

  • IEC 62271-1: Establishes common specifications for high-voltage switchgear and controlgear.

  • IEC 62271-200: Focuses on AC metal-enclosed switchgear and controlgear designed for rated voltages exceeding 1 kV up to and including 52 kV.

  • IEC 62271-300: Addresses gas-insulated metal-enclosed switchgear intended for rated voltages above 52 kV.

While IEC standards are globally recognized, countries such as the United States, China, and Russia may adhere to their own national standards. According to Section 3.5 of IEC 62271-1, all components of switchgear and controlgear are specified, enabling the assembly of comprehensive switchgear systems with functionalities tailored for medium voltage networks. These functions include:

  • Efficiently distributing energy from higher-level transmission systems down to consumption points.

  • Facilitating the switching of electrical currents.

  • Conducting measurements critical for protection mechanisms, operational indicators, and billing processes.

  • Safeguarding loads and equipment against faults.

  • Implementing control, blocking, and interlocking features according to network operation needs.

  • Enabling communication between switchgear and SCADA or DCS systems for enhanced monitoring and control.

  • Ensuring the safety of personnel working within substations.

A variety of designs compliant with IEC standards are available, produced by numerous manufacturers. The IEC standard distinguishes between air-insulated and gas-insulated technologies, with design complexity varying based on the system's position within the distribution network and the sophistication required for protection and control schemes. Higher-rated switchgear typically necessitates more complex protection and control measures.

The typical architecture of primary air-insulated medium voltage switchgear (AIS) is organized into four fundamental compartments, reflecting a structured approach to achieving efficient, safe, and reliable operation within medium voltage applications. This configuration ensures optimal performance while adhering to stringent safety and operational standards.

Medium Voltage Switchgear Basic Structure Compartment

The primary structure, denoted as section B in Figures 1, 2, and 3, comprises metal sheets that provide shape, dimensions, stiffness, and robustness to the switchgear. This structure also incorporates copper components that are crucial for energy transmission and for interconnecting all compartments and apparatus within the switchgear.

This construction offers several key benefits:

  • Metal-Based Segregation: The structure ensures separation between compartments according to IEC 62271-200 standards, which define different levels of accessibility. This segregation enhances safety and operational efficiency.

  • Arc Withstand Capability: Alongside the metal-based segregation, the design includes arc-proof doors that provide additional protection against internal arcing events, ensuring the switchgear's ability to withstand arcs without compromising safety or functionality.

In summary, the primary structure not only gives the switchgear its physical form and strength but also integrates essential copper parts for electrical connectivity. Furthermore, it provides critical compartmentalization and arc resistance, adhering to stringent safety standards and enhancing overall system reliability. This meticulous design ensures that each component within the switchgear operates securely and efficiently, contributing to a safer and more dependable electrical distribution network.

Medium Voltage Switchgear Circuit Breaker Compartment

The circuit breaker compartment, identified as section C in Figures 1, 2, and 3, houses medium voltage (MV) switching apparatus. This compartment can be equipped with various types of switching devices, including load break switches, contactors, circuit breakers, and others. The fundamental role of these switching devices is to reliably and safely open and close steady-state currents and voltages, as well as fault currents and voltages. In most primary air-insulated MV panels, circuit breakers are the preferred choice. Today, vacuum interrupting technology dominates for medium voltage applications due to its reliability and efficiency.

Medium Voltage Switchgear Cable Compartment

The cable compartment, marked as section D in Figures 1, 2, and 3, not only accommodates cable terminations but also includes sensing devices. These devices are primarily used for measuring phase currents, phase voltages, residual current, and residual voltage. The predominant technology employed for measurement purposes is the instrument transformer (IT), which operates on the established inductive principle for both current and voltage measurements. This setup ensures accurate and dependable monitoring within the switchgear system, contributing to enhanced operational safety and performance.

Through this structured approach, each component within the medium voltage switchgear plays a critical role in ensuring the safe, efficient, and reliable distribution of electrical power.

 

Give a tip and encourage the author!
Topics:
Recommended
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
Based on years of field statistics on switchgear accidents, combined with analysis focusing on the circuit breaker itself, the main causes have been identified as: failure of operation mechanism; insulation faults; poor breaking and closing performance; and poor conductivity.1.Failure of Operation MechanismFailure of operation mechanism manifests as delayed operation or unintended operation. Since the most basic and important function of a high-voltage circuit breaker is to operate correctly and
Felix Spark
11/04/2025
Compact Air-Insulated RMUs for Retrofit & New Substations
Compact Air-Insulated RMUs for Retrofit & New Substations
Air-insulated ring main units (RMUs) are defined in contrast to compact gas-insulated RMUs. Early air-insulated RMUs used vacuum or puffer-type load switches from VEI, as well as gas-generating load switches. Later, with the widespread adoption of the SM6 series, it became the mainstream solution for air-insulated RMUs. Similar to other air-insulated RMUs, the key difference lies in replacing the load switch with an SF6-encapsulated type—where the three-position switch for load and grounding is
Echo
11/03/2025
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Expected service life of 30–40 years, front access, compact design equivalent to SF6-GIS, no SF6 gas handling – climate-friendly, 100% dry air insulation. The Nu1 switchgear is metal-enclosed, gas-insulated, featuring a withdrawable circuit breaker design, and has been type-tested according to relevant standards, approved by the internationally recognized STL laboratory.Compliance Standards Switchgear: IEC 62271-1 High-voltage switchgear and controlgear – Part 1: Common specifications for altern
Edwiin
11/03/2025
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Solid insulation assistance combined with dry air insulation is a development direction for 24 kV ring main units. By balancing insulation performance and compactness, the use of solid auxiliary insulation allows passing insulation tests without significantly increasing phase-to-phase or phase-to-ground dimensions. Encapsulation of the pole can address the insulation of the vacuum interrupter and its connected conductors.For the 24 kV outgoing busbar, with the phase spacing maintained at 110 mm,
Dyson
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.