• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Analysis of Earth Fault Protection in Low-Voltage Distribution Systems for Data Centers

Leon
Leon
Field: Fault Diagnosis
China

Low-voltage power distribution lines are widely used across various industries, and the distribution environments are complex and diverse. These lines are accessed not only by professionals but also frequently by non-specialists, significantly increasing the risk of faults. Improper design or installation can easily lead to electric shock (particularly indirect contact), damage to wiring, or even electrical fires.

The grounding system is a critical component of low-voltage distribution networks—a technically complex and safety-critical engineering element. The type of grounding system is closely linked to the effectiveness of grounding fault protection.

Currently, the low-voltage distribution systems in data centers across China primarily adopt the TN-S grounding configuration. These systems involve numerous low-voltage distribution devices and extensive cabling, representing substantial capital investment. Any fault, if not promptly addressed, could result in severe personnel injuries and significant property damage, hence demanding extremely high reliability from the distribution system.

To provide a more comprehensive and systematic explanation of grounding fault protection in low-voltage distribution systems, the following section presents a comparative analysis of various grounding configurations and their corresponding fault protection methods.

General Requirements for Earth Fault Protection

  • The earth fault protection system shall be designed to effectively prevent indirect electric shock to personnel, as well as accidents such as electrical fires and damage to wiring.
  • Exposed conductive parts of electrical equipment shall be reliably connected to the protective conductor (PE conductor) in accordance with the specific conditions of the system. Externally accessible conductive parts that may be simultaneously touched shall be connected to the same grounding system to ensure potential equalization.
  • Where the earth fault protection of an electrical installation cannot meet the requirement for automatic disconnection of the fault circuit within the specified time, supplementary equipotential bonding shall be implemented within the local area to reduce touch voltage and enhance safety.

Earth Fault Protection in TN Systems

In TN systems, the operating characteristics of earth fault protection for distribution circuits shall satisfy the following condition:

Zs × Ia ≤ Uo

Where:

  • Zs — Total impedance of the earth fault loop (Ω);
  • Ia — Current required to cause the protective device to automatically disconnect the fault circuit within the specified time (A);
  • Uo — Nominal voltage between phase and earth (V).

As illustrated in the figure below, when a ground fault occurs on phase L3, the fault current (Id) flows through the L3 phase conductor, the metallic enclosure of the equipment, and the PE protective conductor, forming a closed loop. Zs represents the total impedance of the phase-to-protective conductor loop, and Uo is 220V.

Disconnection Time Requirements for Earth Fault Protection in TN Systems

For TN system distribution circuits with a nominal phase-to-earth voltage of 220V, the time required for earth fault protection to disconnect the fault circuit shall comply with the following requirements:

  • For distribution circuits or final circuits supplying fixed electrical equipment, the disconnection time should not exceed 5 seconds;
  • For circuits supplying hand-held or mobile equipment, or socket-outlet circuits, the disconnection time shall not exceed 0.4 seconds.

Selection of Earth Fault Protection Methods in TN Systems:

a. When the above disconnection time requirements can be met, overcurrent protection may be used to also serve as earth fault protection;
b. When overcurrent protection cannot meet the requirements, but zero-sequence current protection can, zero-sequence current protection shall be used. The protection setting value should be greater than the maximum unbalanced current under normal operating conditions;
c. When neither of the above methods can satisfy the requirements, residual current operated protection (RCD, or "leakage current protection") shall be employed.

Earth Fault Protection in TT Systems

The operating characteristic of earth fault protection in TT system distribution circuits shall satisfy the following condition:

RA × Ia ≤ 50 V

Where:

  • RA — The sum of the earth electrode resistance of exposed conductive parts and the neutral (N) conductor earth resistance (Ω);
  • Ia — The current required to ensure the protective device reliably disconnects the fault circuit (A).

As shown in the figure below, when a ground fault occurs on phase L3, the fault current (Id) flows through the L3 conductor, the metallic enclosure of the equipment, the equipment's grounding electrode resistance, the earth, and back to the source via the neutral point grounding resistance, forming the fault loop. The value of 50 V represents the safety limit for touch voltage, ensuring that the voltage to which a person may be exposed during a fault does not pose a danger.

Selection of Earth Fault Protection for TT Systems:

  • When overcurrent protective devices are used, the current Ia shall be the value that ensures disconnection of the fault circuit within 5 seconds;
  • When instantaneous-trip overcurrent protective devices are used, Ia shall be the minimum current required to ensure instantaneous operation;
  • When residual current operated protective devices (RCDs, or "leakage current protection") are used, Ia shall be taken as their rated residual operating current In.

Earth Fault Protection in IT Systems

Under normal operation, the leakage current in each phase of an IT system consists of capacitive current to earth—denoted as Iac, Ibc, Ica—and the vector sum of these three-phase earth capacitance currents is zero. Therefore, the neutral point voltage can be considered as 0V.

When the first earth fault occurs, the voltage-to-earth on the healthy (non-faulted) phases increases by a factor of √3. This indicates that IT systems impose higher insulation level requirements on electrical equipment compared to TN and TT systems. However, since the current during the first earth fault is very small (primarily capacitive current), the system can continue to operate. Nevertheless, an insulation monitoring device must be installed to provide an alarm upon detection of the first fault, enabling operation and maintenance personnel to locate and rectify the fault promptly.

  • When exposed conductive parts are individually earthed, the disconnection of the fault circuit during a second fault on a different phase shall comply with the earth fault protection requirements of the TT system;
  • When exposed conductive parts are connected to a common earthing system, the disconnection of the fault circuit during a second fault on a different phase shall comply with the earth fault protection requirements of the TN system;
  • The IT system should not have a neutral conductor (N line) derived.

In summary, different power supply earthing systems exhibit distinct earth fault characteristics. Only by fully understanding the fault behavior of each system can an appropriate and compatible earth fault protection scheme be designed, ensuring safe and reliable operation of power supply and utilization systems.

Give a tip and encourage the author!
Recommended
How to Identify Internal Faults in a Transformer?
How to Identify Internal Faults in a Transformer?
Measure DC resistance: Use a bridge to measure the DC resistance of each high- and low-voltage winding. Check whether the resistance values among phases are balanced and consistent with the manufacturer’s original data. If phase resistance cannot be measured directly, line resistance may be measured instead. The DC resistance values can indicate whether the windings are intact, whether there are short circuits or open circuits, and whether the contact resistance of the tap changer is normal. If
Felix Spark
11/04/2025
What Are the Top 10 Taboos and Precautions in the Installation of Distribution Boards and Cabinets?
What Are the Top 10 Taboos and Precautions in the Installation of Distribution Boards and Cabinets?
There are many taboos and problematic practices in the installation of distribution boards and cabinets that must be noted. Especially in certain areas, improper operations during installation may lead to serious consequences. For cases where the precautions were not followed, some corrective measures are also provided here to remedy previous mistakes. Let’s follow along and take a look at common installation taboos from manufacturers regarding distribution boxes and cabinets!1. Taboo: Lighting
James
11/04/2025
What Are the Factors Influencing the Impact of Lightning on 10kV Distribution Lines?
What Are the Factors Influencing the Impact of Lightning on 10kV Distribution Lines?
1. Induced Lightning OvervoltageInduced lightning overvoltage refers to the transient overvoltage generated on overhead distribution lines due to nearby lightning discharges, even when the line is not directly struck. When a lightning flash occurs in the vicinity, it induces a large amount of charge on the conductors—opposite in polarity to the charge in the thundercloud.Statistical data shows that lightning-related faults caused by induced overvoltages account for approximately 90% of total fau
Echo
11/03/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.