Cooling Tower Material and Main Components

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

What Are The Cooling Tower Material And Main Components

Variety of materials are used for constructing Cooling Tower structures. Materials like fiber glass are used for constructing package cooling towers. However for field erected cooling towers material like steel, fiber glass, redwood and concrete and be used depending upon the project location and client preference.
Plus and minuses of each cooling tower material is given below:
Wood:
Redwood as a material in cooling tower was used in 70’s and 80’s for small capacity cooling towers. Now a days because of its diminishing existance wood is not used in
cooling towers.

colling tower
Following are the drawbacks when wood is used as a material:

  • Durability: Wood is considered as less durable during operation and also having less life compared to other materials.

  • Drift Losses: are more i.e over 1%.

  • Signification: Problem of wood eating is more and requires pH adjustment.

  • Area Requirement: is more thus having a larger foot prints compared to others.

  • Algae: serious problem of algae formation.

  • Heavy structure: Wood structure are more heavier than the other cooling tower materials thus increases the civil cost.

Galvanized Steel:
It is the most common construction material for cooling towers. G-235 hot-dipped-galvanized steel is suitable from corrosion resistance point of view and also having good structural strength.
Stainless Steel:
Further development and improvement in the cooling tower material leads to stainless steel, which is superior to G-235.
Stainless steel 304 cooling tower material is used and recommended for
cooling towers installed in the highly corrosive environment.
Concrete Towers:
Concrete cooling towers are usually very large towers.
concrete towers
Salient features of concrete towers are:

  • Long Life: life of the towers are over 38-40 years.

  • Erection Time: these are field erected towers and requires more time in completion.

  • Expensive towers: these towers are very expensive which is fairly compensated by its long life.

Fibre Reinforced Plastics (FRP) Towers:
Application of FRP towers are growing very fast and more and more process plants are replacing their old wooden cooling towers with FRP.
fibre reinforced plastics (frp) towers
Salient features of FRP cooling towers are:

  • Light in weight

  • Having good defiant against chemical water, thus operation of it is possible in wide pH range.

  • FRP towers are fire resistant, thus need not require fire protection system.

  • These towers requires less erection time and also having cost advantage with respect to others cooling towers.

Components of Cooling Tower

Life of a well maintained cooling towers ranges between 20 to 25 years approximately. There are two type of important components in a cooling:
Replaceable Components like

  • Air moving component (draft fans)

  • Packing materials (Fills)

  • Hot water distribution system

  • Louvers

  • Drift eliminators

Non Replaceable Components/Permanent Structure like

  • Cold Water Basin

Description of the major components of cooling tower and their functions are given below:

Packing Materials Coling Tower

Is vital component of a cooling towers, as it enhances the cooling effective of the cooling tower by providing Spalsh Fills and Film fills.
Splash Fills:
Towers having horizontal and vertical staggered patterns to splash the hot water falling down from the top of the tower distribution deck. Splash causing the hot water to get divided in fine water droplets and increases its surface area of water between air and water.
splash fills
Film Fills :
These are plastic corrugated sheets that are joined together to give a honeycombed appearance. Material used for film fill are PVC, Polypropylene.
film fills

Cooling Tower Hot Water Distribution System

It is for distributing hot circulating water inside the cooling towers to cool the hot process water. It includes distributing basin, headers, distributing arms, spray nozzles, flow regulating valves.

Cooling Tower Cold Water Basin

Cold water basin at the bottom of the tower is designed to collect the cooled water and supply the same to the suction of circulating water pumps.
Capacity of the basin should be to hold the 3 times of circulating water flow rate in gpm.

Cooling Tower Fan

cooling tower fan
Fans are used in induced draft cooling towers. Commonly used blade material are FRP, Aluminum and hot-dipped-galvanized steel.

Louvers

Function of louver in cross flow cooling tower are

  • To equally distribute the air flow to the fills.

  • It helps in retaining the water inside the tower.

function of louver in cross flow cooling tower
Louvers are not required in counter flow cooling tower.

Drift Eliminators

Function of it is to remove the water droplet entrained in the hot air going out of the cooling towers. It reduces the drift to less than 0.0005% of the circulating water. It is made up of PVC.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Solid insulation assistance combined with dry air insulation is a development direction for 24 kV ring main units. By balancing insulation performance and compactness, the use of solid auxiliary insulation allows passing insulation tests without significantly increasing phase-to-phase or phase-to-ground dimensions. Encapsulation of the pole can address the insulation of the vacuum interrupter and its connected conductors.For the 24 kV outgoing busbar, with the phase spacing maintained at 110 mm,
Dyson
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
What Is THD? How It Affects Power Quality & Equipment
What Is THD? How It Affects Power Quality & Equipment
In the field of electrical engineering, the stability and reliability of power systems are of paramount importance. With the advancement of power electronics technology, the widespread use of nonlinear loads has led to an increasingly serious problem of harmonic distortion in power systems.Definition of THDTotal Harmonic Distortion (THD) is defined as the ratio of the root mean square (RMS) value of all harmonic components to the RMS value of the fundamental component in a periodic signal. It is
Encyclopedia
11/01/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.