• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Operation and Fault Handling of High and Low Voltage Power Distribution Systems

Felix Spark
Felix Spark
Field: Failure and maintenance
China

Basic Composition and Function of Circuit Breaker Failure Protection

Circuit breaker failure protection refers to a protective scheme that operates when the relay protection of a faulty electrical device issues a trip command but the circuit breaker fails to operate. It uses the protection trip signal from the faulty equipment and the current measurement from the failed breaker to determine breaker failure. The protection can then isolate other relevant breakers within the same substation in a short time delay, minimizing the outage area, ensuring overall grid stability, preventing severe damage to generators, transformers, and other faulted components, and avoiding catastrophic grid collapse.

Breaker failure constitutes a dual fault—combining a power system fault with a breaker malfunction. While slightly relaxed performance criteria may be acceptable, the fundamental principle remains: the fault must ultimately be cleared. In modern high-voltage and extra-high-voltage power grids, breaker failure protection is widely adopted as a near-backup protection method.

Composition and Function of Failure Protection

Breaker failure protection consists of a voltage blocking element, a start-up circuit (formed by protection operation and current discrimination), a time-delay element, and a trip output circuit.

The start-up circuit is critical for the correct and reliable operation of the entire protection system. It must be secure and employ dual criteria to prevent false initiation due to single-condition judgment, stuck protection contacts, accidental contact, or unintended energization. The start-up circuit includes two elements forming an "AND" logic:

  • Start Element: Typically uses the breaker’s own automatic trip output circuit. This can be the instantaneous-reset contact of the trip relay itself or a parallel auxiliary intermediate relay with instantaneous return. A contact that has operated but not reset indicates breaker failure.

  • Discrimination Element: Identifies in various ways whether the fault still persists. Existing operational equipment commonly uses “current presence” methods—phase current (for lines) or zero-sequence current (for transformers). If current remains in the circuit after protection operation, it confirms the fault has not been cleared.

The time-delay element serves as an intermediate stage in breaker failure protection. To prevent maloperation caused by a single time-element failure, the time element must form an "AND" logic with the start-up circuit before activating the trip output relay.

The voltage blocking for failure protection generally consists of bus low-voltage, negative-sequence voltage, and zero-sequence voltage relays. When failure protection shares the trip output circuit with bus differential protection, they also share the same voltage blocking elements.

Give a tip and encourage the author!
Recommended
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Solid insulation assistance combined with dry air insulation is a development direction for 24 kV ring main units. By balancing insulation performance and compactness, the use of solid auxiliary insulation allows passing insulation tests without significantly increasing phase-to-phase or phase-to-ground dimensions. Encapsulation of the pole can address the insulation of the vacuum interrupter and its connected conductors.For the 24 kV outgoing busbar, with the phase spacing maintained at 110 mm,
Dyson
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
What Is THD? How It Affects Power Quality & Equipment
What Is THD? How It Affects Power Quality & Equipment
In the field of electrical engineering, the stability and reliability of power systems are of paramount importance. With the advancement of power electronics technology, the widespread use of nonlinear loads has led to an increasingly serious problem of harmonic distortion in power systems.Definition of THDTotal Harmonic Distortion (THD) is defined as the ratio of the root mean square (RMS) value of all harmonic components to the RMS value of the fundamental component in a periodic signal. It is
Encyclopedia
11/01/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.