• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


7 Common VCB Failures and How to Fix Them

Felix Spark
Felix Spark
Field: Failure and maintenance
China

Fault Analysis and Troubleshooting of High-Voltage Vacuum Circuit Breakers

Introduction: Advantages and Evolution

High-voltage vacuum circuit breakers (VCBs) offer significant advantages over traditional oil or SF₆-based breakers, including:

  • Oil-free and environmentally friendly design

  • High dielectric strength in vacuum

  • Excellent arc-quenching capability

  • Long electrical and mechanical life

  • Compact size, light weight

  • Suitable for frequent operation

  • Fire-resistant and low maintenance

These benefits have made VCBs the preferred choice in medium- and high-voltage power systems, widely adopted by utilities, engineers, and maintenance teams.

However, early domestic models in China faced challenges such as inconsistent quality, high current chopping overvoltage, and occasional vacuum leakage. A turning point came at the 1992 Tianjin Vacuum Switch Application Promotion Conference, after which Chinese manufacturing technology rapidly advanced to match international standards.

Despite their high reliability, vacuum circuit breakers may still experience operational faults. This article analyzes seven common failure modes, identifies root causes, and provides practical troubleshooting solutions to ensure safe and stable operation.

Common Abnormal Operating Conditions

image.png

Root Cause Analysis and Diagnostic Methods

1. Failure to Close or Open

  • Symptom: Solenoid operates, latch releases, but mechanism does not drive contact motion.

  • Cause: Excessive clearance or wear in mechanical linkages—particularly at the universal joint connecting the main lever arm.

  • Diagnosis: Confirm secondary control circuit integrity first. If electrical signals are normal, inspect mechanical transmission components for looseness or deformation.

2. Unintended Tripping (False Tripping)

  • Symptom: Breaker trips unexpectedly during normal service.

  • Cause: Short circuit in auxiliary switch contacts due to moisture ingress.

  • Root Cause: Rainwater enters the mechanism box, flows down the output crank arm, and causes insulation failure between auxiliary switch contacts, energizing the trip coil unintentionally.

3. Storage Motor Runs Continuously After Spring Charging

  • Control Logic:

    • Closing → auxiliary switch closes → motor starts.

    • Spring fully charged → limit switch opens (normally closed contact) → motor stops.

  • Failure Cause: The limit switch lever fails to actuate, leaving the normally closed contact closed and the motor circuit energized.

  • Diagnosis: Check mechanical linkage between the spring mechanism and limit switch for misalignment or jamming.

4. Increased DC Contact Resistance

  • Impact: Elevated resistance → increased temperature rise → risk of thermal runaway and contact welding.

  • Cause:

    • Contact erosion due to repeated interruptions.

    • Reduced contact spring pressure.

    • Changes in contact gap and overtravel.

  • Measurement: Use DC voltage drop method with test current ≥100A per IEC/GB standards.

  • Acceptance Criterion: Resistance must be within ±20% of initial value and below manufacturer’s limit.

5. Excessive Closing Bounce Time

  • Standard: Closing bounce should be ≤2ms.

  • Consequences: Prolonged bounce causes arcing, contact burning, and potential welding.

  • Causes:

    • Weakened contact spring force.

    • Wear in pins, levers, and hinge joints.

    • Misalignment in drive mechanism.

6. Discharge from CT Surface to Support Bracket

  • Location: Middle chamber, where the current transformer (CT) is mounted.

  • Cause: Loss of semiconductor coating on CT surface due to scraping during assembly (especially around mounting bolts).

  • Effect: Localized electric field distortion → surface discharge to grounded bracket.

  • Risk: Partial discharge → insulation degradation → eventual flashover.

7. Vacuum Interrupter Fails to Open

  • Critical Risk: Inability to interrupt fault current → system instability or equipment damage.

  • Primary Cause: Loss of vacuum integrity.

    • Low vacuum → ionization inside chamber → reduced dielectric strength.

    • Charged particles prevent arc extinction.

  • Detection: Use vacuum degree tester (high-frequency withstand voltage method) or observe abnormal glow during operation.

Troubleshooting and Corrective Actions

1. Failure to Close or Open

  • Solution:

    • Inspect all mechanical linkages for wear, deformation, or excessive clearance.

    • Replace worn universal joints, pins, and levers with high-hardness, precision-machined components.

    • Ensure proper lubrication and alignment.

2. Unintended Tripping

  • Solution:

    • Seal all entry points in the mechanism box (cable entries, shaft seals).

    • Install silicone protective sleeves on the output crank linkage.

    • Activate heating and moisture-removal devices to prevent condensation.

    • Use auxiliary switches with higher IP protection rating (e.g., IP55).

3. Storage Motor Runs Continuously

  • Solution:

    • Adjust the position and travel of the limit switch.

    • Ensure the actuating lever fully opens the normally closed contact when the spring is fully charged.

    • Verify switch operation under load conditions.

4. Increased DC Contact Resistance

  • Solution:

    • Measure and adjust contact gap and overtravel.

    • Re-torque connections and clean contact surfaces if accessible.

    • If resistance remains high after adjustment, replace the vacuum interrupter.

    • Record baseline resistance values during commissioning for trend analysis.

5. Excessive Closing Bounce

  • Solution:

    • Slightly increase initial contact spring pressure (within design limits).

    • Replace worn pins and levers (clearance > 0.3mm).

    • Optimize drive mechanism geometry: shift linkage slightly toward the dead center position in the closed state to reduce impact velocity and bounce.

6. CT Surface Discharge

  • Solution:

    • Clean the CT surface thoroughly.

    • Reapply a uniform layer of semiconductor paint around the entire circumference, especially near mounting points.

    • Allow proper curing time before re-energizing.

    • Conduct partial discharge test post-repair to verify effectiveness.

7. Vacuum Interrupter Fails to Open

  • Solution:

    • Use a circuit breaker analyzer to measure:

    • Make fine adjustments until all parameters meet specifications.

    • Opening/closing speed

    • Three-phase synchronization

    • Closing bounce time

    • Adjust overtravel via the insulating pull rod’s threaded connection.

    • Adjust contact gap by modifying the length of the moving conductive rod.

    • Ensure the new unit passes factory vacuum integrity test.

    • Install vertically; align the moving rod with the drive mechanism.

    • Avoid torsional stress during installation.

    • Confirm vacuum level using a vacuum tester.

    • Replace the faulty interrupter:

    • Post-installation adjustments:

    • Perform comprehensive testing:

Give a tip and encourage the author!
Recommended
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
 Analysis of Substation Busbar Discharge Faults and Their Solutions
Analysis of Substation Busbar Discharge Faults and Their Solutions
1. Methods for Detecting Busbar Discharge1.1 Insulation Resistance TestThe insulation resistance test is a simple and commonly used method in electrical insulation testing. It is highly sensitive to through-type insulation defects, overall moisture absorption, and surface contamination—conditions that typically result in significantly reduced resistance values. However, it is less effective in detecting localized aging or partial discharge faults.Depending on the equipment’s insulation class and
Edwiin
10/31/2025
Handling Substation Blackout: Step-by-Step Guide
Handling Substation Blackout: Step-by-Step Guide
1. Purpose of Handling Total Substation BlackoutA total blackout at a 220 kV or higher substation may lead to widespread power outages, significant economic losses, and instability in the power grid, potentially causing system separation. This procedure aims to prevent voltage loss in main grid substations rated 220 kV and above.2. General Principles for Handling Total Substation Blackout Establish contact with dispatch as soon as possible. Restore station service power promptly. Quickly restore
Felix Spark
10/31/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.