What is Long Transmission Line?

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China


What is Long Transmission Line?

Definition of Long Transmission Line

A long transmission line is defined as a transmission line longer than 250 km (150 miles), which needs a different modeling approach.

608826d6bbd922e09ba1119f2645705c.jpeg

A long transmission line is defined as a transmission line with a length greater than 250 km (150 miles). Unlike short transmission lines and medium transmission lines, long transmission lines need detailed modeling of their distributed parameters along the entire length. This makes calculating the ABCD parameters of transmission line more complex but allows us to find the voltage and current at any point on the line.

In a long transmission line the line constants are uniformly distributed over the entire length of line. This is because the effective circuit length is much higher than what it was for the former models (long and medium line) and hence we can no longer make the following approximations:

Ignoring the shunt admittance of the network, like in a small transmission line model.Considering the circuit impedance and admittance to be lumped and concentrated at a point as was the case for the medium line model.

Instead, we must consider the circuit impedance and admittance as distributed over the entire length. This makes the calculations more rigorous. For accurate modeling of these parameters, we use the circuit diagram of the long transmission line.

bc92416d4e3f867f27265ab70c48edd6.jpeg

 


Here a line of length l > 250km is supplied with a sending end voltage and current of VS and IS respectively, whereas the VR and IR are the values of voltage and current obtained from the receiving end. Lets us now consider an element of infinitely small length Δx at a distance x from the receiving end as shown in the figure where.

V = value of voltage just before entering the element Δx.

I = value of current just before entering the element Δx.

V+ΔV = voltage leaving the element Δx.

I+ΔI = current leaving the element Δx.

ΔV = voltage drop across element Δx.

zΔx = series impedance of element Δx

yΔx = shunt admittance of element Δx

Where, Z = z l and Y = y l are the values of total impedance and admittance of the long transmission line.

Therefore, the voltage drop across the infinitely small element Δx is given by

Now to determine the current ΔI, we apply KCL to node A.

Since the term ΔV yΔx is the product of 2 infinitely small values, we can ignore it for the sake of easier calculation.

Therefore, we can write

a4a00349758d819ce18b2ae7e64a8730.jpeg

Now derivating both sides of eq (1) w.r.t x,

Now substituting from equation (2)

The solution of the above second order differential equation is given by.

Derivating equation (4) w.r.to x.

Now comparing equation (1) with equation (5)

8a5521aba7918f13bc1dc8932b3aba95.jpeg


 

Now to go further let us define the characteristic impedance Zc and propagation constant δ of a long transmission line as

Then the voltage and current equation can be expressed in terms of characteristic impedance and propagation constant at

Now at x=0, V= VR and I= Ir. Substituting these conditions to equation (7) and (8) respectively.

98a203d221e03efcab8c7f886415a8af.jpeg

Solving equation (9) and (10),We get values of A1 and A2 as,


c594a1ba76f79bb1a6bcba021804de86.jpeg

Now applying another extreme condition at x = l, we have V = VS and I = IS.Now to determine VS and IS we substitute x by l and put the values of A1 andA2 in equation (7) and (8) we get

81cc39b0a1f4e8660328fe12c3592a79.jpeg

By trigonometric and exponential operators we know

Therefore, equation (11) and (12) can be re-written as

Thus compared with the general circuit parameters equation, we get the ABCD parameters of a long transmission line as,

a044409c56548215ef1aa86d05c25753.jpeg


Give a tip and encourage the author!
Recommended
 Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes of Fire and Explosion in Oil Circuit Breakers When the oil level in an oil circuit breaker is too low, the oil layer covering the contacts becomes too thin. Under the effect of the electric arc, the oil decomposes and releases flammable gases. These gases accumulate in the space beneath the top cover, mixing with air to form an explosive mixture, which can ignite or explode under high temperature. If the oil level inside the tank is too high, the released gases have limited space to expan
Felix Spark
11/06/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
Why Monitoring Accuracy Matters in Power Quality Systems
Why Monitoring Accuracy Matters in Power Quality Systems
The Critical Role of Monitoring Accuracy in Power Quality Online DevicesThe measurement accuracy of online power quality monitoring devices is the core of the power system’s “perception capability,” directly determining the safety, economy, stability, and reliability of power supply to users. Inadequate accuracy leads to misjudgment, incorrect control, and flawed decision-making—potentially causing equipment damage, economic losses, or even grid failures. Conversely, high accuracy enables precis
Oliver Watts
10/30/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.