• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What is GIS (Gas-Insulated Switchgear)? Features, Types, and Applications

Garca
Garca
Field: Design & Maintenance
Congo

What is GIS Equipment?

GIS is the English abbreviation for Gas Insulated Switchgear, which is fully translated into Chinese as Gas-Insulated Metal-Enclosed Switchgear. It typically uses sulfur hexafluoride (SF6) gas as the insulating and arc-quenching medium. GIS integrates, through optimized design, the main primary equipment in a substation—excluding the transformer—such as circuit breakers (CB), disconnectors (DS), earthing switches (ES/FES), busbars (BUS), current transformers (CT), voltage transformers (VT), surge arresters (LA), cable terminations, and incoming/outgoing line bushings—into a single sealed metallic enclosure, forming an integrated unit.

Currently, the voltage rating range of GIS equipment is extensive, spanning from 72.5 kV to 1200 kV.

Characteristics of GIS Equipment

SF6 gas possesses excellent dielectric strength, arc-quenching capability, and chemical stability. As a result, GIS equipment features compact size, minimal footprint, high operational reliability, long maintenance intervals, and strong electromagnetic interference resistance. Additionally, due to its fully enclosed structure, internal components are protected from external environmental factors (such as dust, moisture, and salt fog), ensuring stable operation, low electromagnetic noise, and reduced maintenance workload.

However, the dielectric performance of SF6 gas is highly sensitive to electric field uniformity. Internal defects such as conductor burrs, metallic particles, or assembly flaws can easily lead to partial discharge or even insulation breakdown. Furthermore, the sealed structure of GIS makes internal fault diagnosis and maintenance complex, with limited diagnostic tools. Poor sealing may also result in water ingress or gas leakage, compromising equipment safety.

Types of Electrical Contacts in GIS Conduction Circuits

The conduction circuit in GIS consists of multiple components and can be classified into three types based on contact method:

  • Fixed Contact: Electrical connections secured by bolts or other fasteners, with no relative movement during operation, such as the connection between a busbar and a basin-type insulator.

  • Separable Contact: Electrical contacts that can be opened or closed during operation, such as the contacts in circuit breakers and disconnectors.

  • Sliding or Rolling Contact: Contacts that allow relative sliding or rolling between contact surfaces but cannot be separated, such as intermediate contacts in switchgear.

Introduction to HGIS

In addition to GIS, there is another type called HGIS (Hybrid Gas-Insulated Switchgear), a hybrid gas-insulated switchgear. HGIS does not include components such as busbars, busbar voltage transformers, or busbar surge arresters, resulting in a simpler structure. It is suitable for harsh environments or locations with space constraints and offers greater flexibility in layout.

Classification of GIS Equipment

  • By Installation Location: Indoor and outdoor types.

  • By Structure: Single-phase single-enclosure and three-phase common-enclosure. Generally, busbars at voltage levels of 110 kV and below can adopt the three-phase common-enclosure design, while voltage levels of 220 kV and above typically use the single-phase single-enclosure design to reduce the risk of phase-to-phase faults.

Basic Operating Principles

  • Under normal conditions, GIS circuit breakers and disconnectors are primarily operated remotely. The "Remote/Local" selector switch should be set to the "Remote" position.

  • Earthing switches can only be operated locally. During operation, the "Disconnector/Earthing Switch" selector switch must be switched to the "Local" position.

  • All operations must follow programmed procedures. The "Interlock Release Switch" on the control cabinet must remain in the "Interlock" position. The unlocking key, along with the microcomputer anti-misoperation unlocking key, must be sealed and managed strictly according to regulations.

Basic Operational Requirements

  • For indoor SF6 equipment rooms frequently accessed by personnel, ventilation should be performed at least once per shift for no less than 15 minutes, with air exchange volume exceeding 3–5 times the room volume. Air exhaust outlets should be located at the lower part of the room. For areas not frequently entered, ventilation for 15 minutes is required before entry.

  • During operation, the induced voltage on accessible parts of the GIS enclosure and structure should not exceed 36 V under normal conditions.

  • Temperature Rise Limits:

    • Easily accessible parts: no more than 30 K;

    • Parts easily touched but not contacted during operation: no more than 40 K;

    • Rarely accessible individual parts: no more than 65 K.

  • SF6 switchgear should be inspected at least once daily. For unattended substations, inspections should be conducted according to established procedures. Inspections should focus on visual checks for abnormalities such as unusual sounds, leaks, or abnormal indications, with records maintained accordingly.

Give a tip and encourage the author!
Recommended
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Solid insulation assistance combined with dry air insulation is a development direction for 24 kV ring main units. By balancing insulation performance and compactness, the use of solid auxiliary insulation allows passing insulation tests without significantly increasing phase-to-phase or phase-to-ground dimensions. Encapsulation of the pole can address the insulation of the vacuum interrupter and its connected conductors.For the 24 kV outgoing busbar, with the phase spacing maintained at 110 mm,
Dyson
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
What Is THD? How It Affects Power Quality & Equipment
What Is THD? How It Affects Power Quality & Equipment
In the field of electrical engineering, the stability and reliability of power systems are of paramount importance. With the advancement of power electronics technology, the widespread use of nonlinear loads has led to an increasingly serious problem of harmonic distortion in power systems.Definition of THDTotal Harmonic Distortion (THD) is defined as the ratio of the root mean square (RMS) value of all harmonic components to the RMS value of the fundamental component in a periodic signal. It is
Encyclopedia
11/01/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.