• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Transformer Component Lifespan | -Optimize Maintenance Schedules

Noah
Noah
Field: Design & Maintenance
Australia

The vulnerable components of a transformer and their replacement cycles must be determined comprehensively based on factors such as transformer type, operating environment, load conditions, and manufacturing processes.

Common Vulnerable Components in Oil-Immersed Transformers

Oil-immersed transformers rely on insulating oil for heat dissipation and insulation. Their core components include the core, windings, insulation system, cooling system, and accessories. Vulnerable parts are primarily concentrated in the cooling system, insulation materials, seals, and auxiliary devices.

1. Cooling System Components

  • Submersible Oil Pumps: Drive the circulation of insulating oil for cooling. Long-term high load or frequent start-stop cycles can cause bearing wear and motor aging.
    Replacement Cycle: Approximately 5–8 years under normal operation; may be shortened to 3–5 years under high operating temperatures or frequent overloads.

  • Cooling Fans: Assist in heat dissipation. Motor bearings and fan blades are prone to failure due to dust accumulation or aging.
    Replacement Cycle: 3–6 years.

  • Radiators/Heat Dissipation Fins: Pipes in natural or forced oil circulation radiators may become clogged with oil sludge or develop leaks due to corrosion.
    Replacement Cycle: No replacement needed if no leakage is evident; partial replacement may be required every 5–10 years if severe corrosion occurs.

2. Insulation Materials

  • Insulating Oil: Performs insulation and cooling functions. Performance degrades over time due to oxidation and intrusion of moisture or impurities.
    Replacement Cycle: Test every 3–5 years under normal operation; filtration or replacement is required if parameters exceed limits; immediate replacement is necessary for severe degradation.

  • Insulating Paper/Pressboard: Insulation between windings and core, primarily fails due to thermal or electrical aging.
    Replacement Cycle: Design life is typically 20–30 years; may be prematurely retired by 5–10 years if operated at prolonged high temperatures.

3. Seals

  • Gaskets/Sealing Rings: Sealing components at tank, valve, and bushing locations. Prone to aging and cracking due to prolonged oil pressure and temperature fluctuations, leading to oil leaks.
    Replacement Cycle: Inspect every 2–3 years if no leakage is evident; replace immediately upon detecting seepage.

4. On-Load Tap Changer (OLTC)

  • Core components include the diverter switch, selector switch, and electric drive mechanism. Frequent switching causes contact wear and oil degradation.
    Replacement Cycle:

    • Contacts: Mechanical life is approximately 1–2 million operations;

    • Insulating Oil: Test every 1–2 years; replace if degraded;

    • Entire Unit: Replace if switching exceeds design limits or if jamming or abnormal discharge occurs.

5. Other Accessories

  • Pressure Relief Valve: Protects against internal overpressure. The diaphragm may fail due to aging or frequent activation.
    Replacement Cycle: Inspect every 5–8 years; replace diaphragm if aged.

  • Gas Relay (Buchholz Relay): Detects internal faults. May fail due to oil sludge blockage or contact oxidation over time.
    Replacement Cycle: Calibrate or replace every 3–5 years.

Common Vulnerable Components in Dry-Type Transformers

Dry-type transformers lack insulating oil and rely on air or resin insulation. Vulnerable components are primarily insulation materials, cooling fans, and connection parts.

1. Insulation Materials

  • Epoxy Resin/Glass Fiber: Used in winding encapsulation. Long-term high temperature or partial discharge can cause resin cracking and carbonization.
    Replacement Cycle: Design life is 20–30 years; insulation defects may appear 5–10 years earlier under frequent overloads or high humidity.

2. Cooling Fans

  • Enhance heat dissipation. Motor bearings and blades are prone to aging.
    Replacement Cycle: 3–5 years.

3. Winding Connection Terminals

  • High/low-voltage terminals may experience oxidation or loosening due to current heating, increasing contact resistance and overheating.
    Replacement Cycle: Inspect and tighten every 3–5 years if no overheating; replace immediately if signs of burning are present.

4. Temperature Sensors/Thermostats

  • Monitor winding temperature. May give false alarms due to wiring aging or sensor failure over time.
    Replacement Cycle: Calibrate every 2–3 years; replace when faulty.

Key Factors Affecting Replacement Cycles

  • Operating Environment: High temperature, humidity, dust, or corrosive gases accelerate insulation aging and metal corrosion.

  • Load Conditions: Prolonged overloading or frequent shock loads increase hot-spot temperatures and mechanical stress in windings.

  • Maintenance Level: Regular oil chromatography analysis, infrared thermography, and cleaning of cooling systems can extend component life; neglecting inspections may allow hidden issues to escalate.

Replacement of vulnerable transformer components should be based on condition monitoring, combined with periodic testing and operational data, rather than strictly adhering to fixed intervals. For critical components, it is recommended to engage professional organizations for condition assessment to avoid unnecessary downtime or excessive maintenance.

Give a tip and encourage the author!
Recommended
What causes a transformer to be noisier under no-load conditions?
What causes a transformer to be noisier under no-load conditions?
When a transformer is operating under no-load conditions, it often produces louder noise than under full load. The primary reason is that, with no load on the secondary winding, the primary voltage tends to be slightly higher than nominal. For example, while the rated voltage is typically 10 kV, the actual no-load voltage may reach around 10.5 kV.This elevated voltage increases the magnetic flux density (B) in the core. According to the formula:B = 45 × Et / S(where Et is the designed volts-per-
Noah
11/05/2025
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
When installing an arc suppression coil, it is important to identify the conditions under which the coil should be taken out of service. The arc suppression coil should be disconnected under the following circumstances: When a transformer is being de-energized, the neutral-point disconnector must be opened first before performing any switching operations on the transformer. The energizing sequence is the reverse: the neutral-point disconnector should be closed only after the transformer is energ
Echo
11/05/2025
What fire prevention measures are available for power transformer failures?
What fire prevention measures are available for power transformer failures?
Failures in power transformers are commonly caused by severe overload operation, short circuits due to winding insulation degradation, aging of transformer oil, excessive contact resistance at connections or tap changers, failure of high- or low-voltage fuses to operate during external short circuits, core damage, internal arcing in oil, and lightning strikes.Since transformers are filled with insulating oil, fires can have severe consequences—ranging from oil spraying and ignition to, in extrem
Noah
11/05/2025
What are the common faults encountered during the operation of power transformer longitudinal differential protection?
What are the common faults encountered during the operation of power transformer longitudinal differential protection?
Transformer Longitudinal Differential Protection: Common Issues and SolutionsTransformer longitudinal differential protection is the most complex among all component differential protections. Misoperations occasionally occur during operation. According to 1997 statistics from the North China Power Grid for transformers rated 220 kV and above, there were 18 incorrect operations in total, of which 5 were due to longitudinal differential protection—accounting for approximately one-third. Causes of
Felix Spark
11/05/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.