How does the dielectric oil tan delta meter work?

Encyclopedia
Field: Encyclopedia
0
China

Working Principle of Dielectric Loss Tester for Insulating Oil

A dielectric loss tester for insulating oil is an instrument used to measure the dielectric loss factor (tan δ) and capacitance of insulating oil. Its working principle is based on measuring the loss characteristics of insulating oil under an alternating electric field. Here is a detailed explanation of the principle:

Working Principle

  1. Application of Electric Field:

    • The tester applies an alternating electric field to the insulating oil sample in the test container. Typically, this electric field is generated by a pair of parallel plate capacitors.

  2. Current Measurement:

    • The current in the capacitor can be divided into two components: displacement current (reactive current) and loss current (active current). Displacement current is related to the capacitance, while loss current is related to the dielectric loss factor.

    • The displacement current Ic and loss current 
      Id can be distinguished by measuring the total current 
       
      I and the phase difference 
       
      ϕ.

  3. Phase Difference Measurement:

    • By measuring the phase difference 
       
      ϕ between the applied voltage 
       
      V and the total current 
       
      I, the dielectric loss angle 
       
      δ can be determined.

    • The dielectric loss factor 
       
      tanδ is defined as the ratio of the loss current to the displacement current:


e0719756fa92a5db33170dc10b3a7ef8.jpeg

Capacitance Measurement:

  • The capacitance   
     
    C of the capacitor can be further verified to assess the quality of the insulating oil. The capacitance can be calculated by measuring the frequency   
     
    f and the applied voltage    V along with the current   
     
    I:

cc0ce09416cd2511f021d5b707f5efe5.jpeg

Data Processing:

    • The built-in data processing unit of the tester calculates the dielectric loss factor 
       
      tanδ and capacitance 
       
      C using the above formulas and displays the results.

Significance in Electrical Systems

  1. Insulation Performance Evaluation:

    • Insulating oil is a critical insulating material in many electrical devices, such as transformers, circuit breakers, and cables. The dielectric loss factor 
       
      tanδ reflects the aging degree and contamination level of the insulating oil. A high 
       
      tanδ value indicates that the insulating oil may have deteriorated and needs to be replaced or treated.

  2. Fault Diagnosis:

    • Regular measurement of the dielectric loss factor can help detect potential faults in electrical equipment, such as partial discharge, moisture ingress, or contamination. This aids in preventing equipment failure, reducing maintenance costs, and minimizing downtime.

  3. Quality Control:

    • During the production process, a dielectric loss tester can be used to monitor the quality of newly produced insulating oil to ensure it meets standard requirements. This helps improve product reliability and safety.

  4. Maintenance Management:

    • For electrical equipment already in use, regular measurement of the dielectric loss factor of insulating oil is an important part of maintenance management. This helps in formulating reasonable maintenance plans and extending the lifespan of the equipment.

Summary

A dielectric loss tester for insulating oil effectively evaluates the insulation performance of insulating oil by measuring its dielectric loss factor and capacitance. It helps diagnose potential faults in electrical equipment, ensures the safe and reliable operation of electrical systems, and aids in quality control and maintenance management.

Give a tip and encourage the author!

Recommended

Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Reclosing Charge Time: Why Does Reclosing Require Charging? What Effects Does Charging Time Have?
1. Function and Significance of Reclosing ChargingReclosing is a protective measure in power systems. After faults such as short circuits or circuit overloads occur, the system isolates the faulty circuit and then restores normal operation through reclosing. The function of reclosing is to ensure continuous operation of the power system, improving its reliability and safety.Before performing reclosing, the circuit breaker must be charged. For high-voltage circuit breakers, the charging time is g
12/15/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.