Why is it necessary to measure the absorption ratio of electrical equipment?

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

The absorption ratio is defined as follows: When operating a megohmmeter (insulation resistance tester), rotate the handle at a speed of 120 revolutions per minute. Record the insulation resistance reading at 15 seconds (R15) and then at 60 seconds (R60). The absorption ratio is calculated using the formula:

Absorption Ratio = R60 / R15, which should be greater than or equal to 1.3.

Measuring the absorption ratio helps determine whether the insulation of electrical equipment is damp. When insulation material is dry, the leakage current component is very small, and the insulation resistance is primarily determined by the charging (capacitive) current. At 15 seconds, the charging current is still relatively large, resulting in a smaller insulation resistance value (R15). By 60 seconds, due to the dielectric absorption characteristics of the insulation material, the charging current has significantly decayed, leading to a larger insulation resistance value (R60). Therefore, the absorption ratio is relatively high.

However, when the insulation is damp, the leakage current component increases significantly. The time-dependent charging current becomes less dominant, and the insulation resistance shows little change over time. As a result, R60 and R15 become very close, meaning the absorption ratio decreases.

measure.jpg

Thus, the measured value of the absorption ratio can provide a preliminary assessment of whether the insulation of electrical equipment is damp.

The absorption ratio test is suitable for equipment with relatively large capacitance, such as motors and transformers, and should be interpreted in conjunction with the specific environmental conditions of the equipment. The general criterion is that if the insulation is not damp, the absorption ratio K ≥ 1.3. However, for equipment with very small capacitance (e.g., insulators), the insulation resistance reading stabilizes within just a few seconds and does not continue to rise—indicating no significant absorption effect. Therefore, performing an absorption ratio test on such small-capacitance equipment is unnecessary.

For high-capacity test specimens, relevant domestic and international standards specify that the Polarization Index (PI), defined as R10min / R1min, may be used instead of the absorption ratio test.

Temperature is inversely proportional to insulation resistance: higher temperatures result in lower insulation resistance and higher conductor resistance. Based on general experience, medium- and high-voltage cables are typically subjected to rigorous partial discharge and high-voltage tests before leaving the factory. Under normal conditions, the insulation resistance of medium-voltage cables can reach several hundred to over a thousand MΩ·km.

Give a tip and encourage the author!
Recommended
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
Why Monitoring Accuracy Matters in Power Quality Systems
Why Monitoring Accuracy Matters in Power Quality Systems
The Critical Role of Monitoring Accuracy in Power Quality Online DevicesThe measurement accuracy of online power quality monitoring devices is the core of the power system’s “perception capability,” directly determining the safety, economy, stability, and reliability of power supply to users. Inadequate accuracy leads to misjudgment, incorrect control, and flawed decision-making—potentially causing equipment damage, economic losses, or even grid failures. Conversely, high accuracy enables precis
Oliver Watts
10/30/2025
How Does Power Dispatching Ensure Grid Stability and Efficiency?
How Does Power Dispatching Ensure Grid Stability and Efficiency?
Electric Power Dispatching in Modern Power SystemsThe power system is a critical infrastructure of modern society, providing essential electrical energy for industrial, commercial, and residential use. As the core of power system operation and management, electric power dispatching aims to meet electricity demand while ensuring grid stability and economic efficiency.1. Basic Principles of Electric Power DispatchingThe fundamental principle of power dispatching is to balance supply and demand by
Echo
10/30/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.