Air Break Circuit Breaker

Edwiin
Edwiin
Field: Power switch
China

In an air break circuit breaker, the arc is initiated and extinguished in substantially static air as the arc moves. These breakers are used for low voltages, generally up to 15 kV, with rupturing capacities of 500 MVA. As an arc-quenching medium, air circuit breakers offer several advantages over oil, including:

  • Elimination of risks and maintenance associated with oil use.

  • Absence of mechanical stress caused by gas pressure and oil movement.

  • Elimination of costs from regular oil replacement due to oil deterioration from successive breaking operations.

In air break circuit breakers, contact separation and arc extinction occur in air at atmospheric pressure, employing the high-resistance principle. The arc is expanded via arc runners and chutes, while arc resistance is increased through splitting, cooling, and lengthening.

Arc resistance is heightened until the voltage drop across the arc exceeds the system voltage, extinguishing the arc at the current zero point of the AC wave.

Air break circuit breakers are used in DC circuits and AC circuits up to 12,000 V. Typically indoor types, they are installed on vertical panels or indoor draw-out switchgear, widely applied in indoor medium- and low-voltage switchgear for AC systems.

Plain Break Type Air Break Circuit Breaker

The simplest variant features two horn-shaped contacts. Arcing initially occurs across the shortest distance between the horns and is steadily driven upward by convection currents from arc-heated air and the interaction of magnetic and electric fields. As the horns fully separate, the arc extends from tip to tip, achieving lengthening and cooling.

The process’s relative slowness and the risk of arc spreading to adjacent metal components limit its application to approximately 500 V and low-power circuits.

Magnetic Blow-Out Type Air Break Circuit Breaker

Used in circuits with voltages up to 11 kV, arc extinction in some air circuit breakers is achieved via a magnetic field from blowout coils connected in series with the interrupted circuit. These coils move the arc into chutes—they do not extinguish the arc themselves. In the chutes, the arc is lengthened, cooled, and extinguished. Arc shields prevent arc spreading to adjacent networks.

Polarity, Arc Chutes, and Operational Details of Air Break Circuit Breakers
Importance of Coil Polarity

Correct coil polarity is critical to direct the arc upward, leveraging electromagnetic forces to enhance arc movement. This principle becomes more effective with higher fault currents, enabling such breakers to achieve higher rupturing capacities.

Arc Chute Functionality

An arc chute is a key device for arc extinction in air, performing three interrelated roles:

  • Arc Confinement: Restricts the arc to a defined space, preventing uncontrolled spread.

  • Magnetic Control: Guides arc movement via magnetic fields to facilitate extinction within the chute.

  • Rapid Cooling: Deionizes arc gases through intense cooling, ensuring arc quenching.

Air Chute Air Break Circuit Breaker Design

For low- and medium-voltage circuits, this breaker features:

  • Dual Contact Sets:

    • Main Contacts: Copper-based, silver-plated for low resistance, conducting normal current in the closed position.

    • Arcing (Auxiliary) Contacts: Heat-resistant copper alloy, designed to withstand arcing during fault interruption. They close before and open after the main contacts to protect the main contacts from damage.

  • Blowout Mechanism: Steel inserts in the arcing chutes create magnetic fields that accelerate upward arc movement. These plates split the arc into series of short arcs, increasing total voltage drop (anode + cathode drops) across the arcs. If this sum exceeds the system voltage, the arc extinguishes rapidly.

  • Cooling Action: Arc contact with cool steel plates rapidly cools and deionizes the arc, aided by natural or magnetic blowout forces.

Working Principle

  • Fault Occurrence: Main contacts separate first, shifting current to the arcing contacts.

  • Arc Formation: As arcing contacts separate, an arc draws between them.

  • Arc Movement: Electromagnetic and thermal forces drive the arc upward along arc runners.

  • Arc Splitting & Extinction: The arc is split by splitter plates, lengthened, cooled, and deionized, leading to extinction.

Applications

  • Power Station Auxiliaries & Industrial Plants: Suitable for environments requiring fire/explosion hazard mitigation.

  • DC Systems: Employ arc lengthening, runners, and magnetic blowout for breakers up to 15 kV.

Limitation

  • Low-Current Inefficiency: Arc chutes are less effective at low currents due to weaker electromagnetic fields, causing slower arc movement into the chute and potentially delayed interruption.

This design balances simplicity and reliability for medium/low-voltage applications, though its performance varies with current magnitude.

Give a tip and encourage the author!
Recommended
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
Based on years of field statistics on switchgear accidents, combined with analysis focusing on the circuit breaker itself, the main causes have been identified as: failure of operation mechanism; insulation faults; poor breaking and closing performance; and poor conductivity.1.Failure of Operation MechanismFailure of operation mechanism manifests as delayed operation or unintended operation. Since the most basic and important function of a high-voltage circuit breaker is to operate correctly and
Felix Spark
11/04/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Compact Air-Insulated RMUs for Retrofit & New Substations
Compact Air-Insulated RMUs for Retrofit & New Substations
Air-insulated ring main units (RMUs) are defined in contrast to compact gas-insulated RMUs. Early air-insulated RMUs used vacuum or puffer-type load switches from VEI, as well as gas-generating load switches. Later, with the widespread adoption of the SM6 series, it became the mainstream solution for air-insulated RMUs. Similar to other air-insulated RMUs, the key difference lies in replacing the load switch with an SF6-encapsulated type—where the three-position switch for load and grounding is
Echo
11/03/2025
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Expected service life of 30–40 years, front access, compact design equivalent to SF6-GIS, no SF6 gas handling – climate-friendly, 100% dry air insulation. The Nu1 switchgear is metal-enclosed, gas-insulated, featuring a withdrawable circuit breaker design, and has been type-tested according to relevant standards, approved by the internationally recognized STL laboratory.Compliance Standards Switchgear: IEC 62271-1 High-voltage switchgear and controlgear – Part 1: Common specifications for altern
Edwiin
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.