What is the difference between an electromagnetic release and a thermal release in a circuit breaker?

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

Differences Between Magnetic Trip Units and Thermomagnetic Trip Units in Circuit Breakers

In circuit breakers, magnetic trip units (Magnetic Trip Unit) and thermomagnetic trip units (Thermomagnetic Trip Unit) are two different protection mechanisms that detect and respond to overcurrent conditions in distinct ways. Below are the main differences between them:

1. Working Principle

Magnetic Trip Unit

Working Principle: A magnetic trip unit detects short circuits or instantaneous high currents through electromagnetic induction. When the current exceeds a preset threshold, the electromagnet generates enough force to actuate the tripping mechanism, rapidly disconnecting the circuit.

  • Response Speed: The magnetic trip unit is highly sensitive to instantaneous high currents and can respond within a few milliseconds, making it ideal for short-circuit protection.

  • Current Range: It is typically used to detect short-circuit currents, which are significantly higher than the rated current.

  • Temperature Influence: The magnetic trip unit is not affected by temperature changes because its operation is based on electromagnetic induction, not temperature.

Thermomagnetic Trip Unit

  • Working Principle: A thermomagnetic trip unit combines both thermal and magnetic effects. It uses a bimetallic strip (composed of two metals with different coefficients of thermal expansion) to detect prolonged overload currents. When the current exceeds the rated value, the bimetallic strip deforms due to heat, triggering the tripping mechanism. Additionally, it includes a magnetic trip component to detect instantaneous high currents.

  • Response Speed: For overload currents, the thermomagnetic trip unit responds more slowly, as it relies on the thermal expansion of the bimetallic strip. This typically takes several seconds to a few minutes. For short-circuit currents, the magnetic part of the thermomagnetic trip unit can respond quickly.

  • Current Range: The thermomagnetic trip unit provides protection against both overload and short-circuit currents, covering a wider range of current levels, especially for prolonged overload conditions.

  • Temperature Influence: The thermal trip portion of the thermomagnetic unit is significantly influenced by ambient temperature, as it operates based on the thermal expansion of the bimetallic strip. Therefore, the design of thermomagnetic trip units often accounts for temperature variations to ensure accurate operation under different conditions.

2. Application Scenarios

Magnetic Trip Unit

  • Applicable Scenarios: Primarily used for short-circuit protection in applications requiring rapid response to instantaneous high currents. Examples include industrial equipment, power distribution systems, and motors.

  • Advantages: Fast response time, effectively cutting off short-circuit currents to prevent equipment damage.

  • Disadvantages: Only suitable for short-circuit protection and cannot effectively handle prolonged overload currents.

Thermomagnetic Trip Unit

  • Applicable Scenarios: Suitable for both overload and short-circuit protection, especially in situations where both types of overcurrent need to be addressed. Examples include residential circuits, commercial buildings, and small industrial equipment.

  • Advantages: Can handle both overload and short-circuit currents, providing a broader range of protection. For overload currents, it offers a delayed response, preventing nuisance trips due to brief current surges.

  • Disadvantages: Slower response to short-circuit currents compared to a pure magnetic trip unit.

3. Structure and Design

Magnetic Trip Unit

  • Simple Structure: The magnetic trip unit has a relatively simple structure, consisting mainly of an electromagnet and a tripping mechanism. It lacks complex mechanical components, enhancing reliability.

  • Independence: The magnetic trip unit typically operates as an independent protection unit, specifically for short-circuit protection.

Thermomagnetic Trip Unit

  • Complex Structure: The thermomagnetic trip unit combines a bimetallic strip and an electromagnet, resulting in a more complex structure. It has both a thermal trip section and a magnetic trip section, allowing it to handle both overload and short-circuit conditions.

  • Integration: The thermomagnetic trip unit is usually integrated into the circuit breaker as a single protection device, suitable for multiple protection needs.

4. Cost and Maintenance

Magnetic Trip Unit

  • Lower Cost: Due to its simple structure, the magnetic trip unit is generally less expensive and requires minimal maintenance.

  • Simple Maintenance: Maintenance for the magnetic trip unit is straightforward, primarily involving checking the condition of the electromagnet and tripping mechanism.

Thermomagnetic Trip Unit

  • Higher Cost: The more complex structure of the thermomagnetic trip unit makes it relatively more expensive, especially for high-quality units.

  • Complex Maintenance: Maintenance for the thermomagnetic trip unit is more involved, requiring periodic inspection of the bimetallic strip to ensure proper operation under varying temperatures.

Summary

  • Magnetic Trip Unit: Best suited for short-circuit protection, offering fast response times, a simple structure, and lower costs. However, it only handles instantaneous high currents.

  • Thermomagnetic Trip Unit: Suitable for both overload and short-circuit protection, with a slower response to overload currents but a broader application range. It is more complex and costly but provides comprehensive protection.

Give a tip and encourage the author!
Recommended
 Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes of Fire and Explosion in Oil Circuit Breakers When the oil level in an oil circuit breaker is too low, the oil layer covering the contacts becomes too thin. Under the effect of the electric arc, the oil decomposes and releases flammable gases. These gases accumulate in the space beneath the top cover, mixing with air to form an explosive mixture, which can ignite or explode under high temperature. If the oil level inside the tank is too high, the released gases have limited space to expan
Felix Spark
11/06/2025
LTB vs DTB vs GIS: HV Circuit Breaker Comparison
LTB vs DTB vs GIS: HV Circuit Breaker Comparison
The basic meaning of a high-voltage circuit breaker is, simply put, that under normal conditions, it is used to open (interrupt, trip) and close (make, reclose) circuits, feeders, or specific loads—such as those connected to transformers or capacitor banks. When a fault occurs in the power system, protective relays activate the circuit breaker to interrupt either load current or short-circuit current, thereby ensuring the safe operation of the power system.A high-voltage circuit breaker is a typ
James
11/06/2025
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
Based on years of field statistics on switchgear accidents, combined with analysis focusing on the circuit breaker itself, the main causes have been identified as: failure of operation mechanism; insulation faults; poor breaking and closing performance; and poor conductivity.1.Failure of Operation MechanismFailure of operation mechanism manifests as delayed operation or unintended operation. Since the most basic and important function of a high-voltage circuit breaker is to operate correctly and
Felix Spark
11/04/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.