Power factor test on circuit breakers

Edwiin
Edwiin
Field: Power switch
China

Assessing the Integrity of Internal and External Insulation

To ensure the reliability and safety of circuit breakers, it is essential to evaluate both their internal and external insulation. Testing equipment typically has an output voltage of 10 kV and is designed to be portable so that it can be used in all substation environments. While this testing is primarily used for oil circuit breakers (CBs), it can also be applied to SF6 switchgear.

Purpose of Power Factor Tests

Power factor tests are conducted to detect contamination and/or deterioration within the breaker’s insulating system, allowing for corrective actions to maintain the integrity of the breaker. This is achieved by measuring the dielectric loss and capacitance of the insulation and calculating the power factor. An increase in dielectric loss and power factor indicates a rise in contamination levels within the insulating system, which can reveal:

  • Moisture contamination: Resulting from leaks or incomplete cleaning and drying.

  • Deterioration of line-to-ground and contact-grading capacitors.

  • Surface contamination of weather sheds.

  • Deterioration of insulating components such as operating rods, interrupters, and interrupter supports caused by corrosive arc by-products.

  • Impurities, contaminants, and/or particles within the insulating medium.

Test Equipment

The figure below illustrates three types of power factor test sets. These devices assist technicians in accurately assessing the condition of insulation, enabling timely detection of potential issues and facilitating necessary repairs. This helps extend the lifespan of the equipment and enhances overall system reliability.

Note: Although images cannot be directly displayed here, please refer to specific equipment manuals or resources for detailed illustrations of the test setups. Additionally, always follow the technical documentation and manufacturer recommendations for the specific equipment when conducting tests in practical applications.

Give a tip and encourage the author!
Recommended
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
Based on years of field statistics on switchgear accidents, combined with analysis focusing on the circuit breaker itself, the main causes have been identified as: failure of operation mechanism; insulation faults; poor breaking and closing performance; and poor conductivity.1.Failure of Operation MechanismFailure of operation mechanism manifests as delayed operation or unintended operation. Since the most basic and important function of a high-voltage circuit breaker is to operate correctly and
Felix Spark
11/04/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Compact Air-Insulated RMUs for Retrofit & New Substations
Compact Air-Insulated RMUs for Retrofit & New Substations
Air-insulated ring main units (RMUs) are defined in contrast to compact gas-insulated RMUs. Early air-insulated RMUs used vacuum or puffer-type load switches from VEI, as well as gas-generating load switches. Later, with the widespread adoption of the SM6 series, it became the mainstream solution for air-insulated RMUs. Similar to other air-insulated RMUs, the key difference lies in replacing the load switch with an SF6-encapsulated type—where the three-position switch for load and grounding is
Echo
11/03/2025
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Expected service life of 30–40 years, front access, compact design equivalent to SF6-GIS, no SF6 gas handling – climate-friendly, 100% dry air insulation. The Nu1 switchgear is metal-enclosed, gas-insulated, featuring a withdrawable circuit breaker design, and has been type-tested according to relevant standards, approved by the internationally recognized STL laboratory.Compliance Standards Switchgear: IEC 62271-1 High-voltage switchgear and controlgear – Part 1: Common specifications for altern
Edwiin
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.