Arc Flash Protection | -Active Arc Elimination Technology

Garca
Garca
Field: Design & Maintenance
Congo

An arc flash is one of the most destructive industrial incidents you might encounter. In an instant, your switchgear can be destroyed, downstream equipment severely damaged, operations shut down for days or weeks, and personnel seriously injured or killed.

In certain facilities or applications, the potential risk of arc flash is very low; conventional (arc-flash unprotected) switchgear can be used with minimal risk. However, in most applications, it makes far more sense to rely on equipment incorporating features designed to mitigate arc flash hazards—providing a prudent "insurance policy" against the catastrophic consequences of an arc incident.

The destructive potential is immense. The energy released during an arc flash in 11kV switchgear is equivalent to the energy required to launch six space shuttles. Temperatures can reach up to 20,000°C—five times hotter than the surface of the sun—capable of vaporizing metal.

Arc faults may be rare, but they represent the most severe type of fault that can occur in a switchgear system. Potential causes are varied, including human error (the most common), technical/equipment failure, and environmental factors.

You can choose from several methods to reduce the risk of arc flash damage and injury. Three of the most common are described below.

Passive Internal Arc Protection

With passive internal arc protection, an arc fault is interrupted after it occurs by conventional protective relays. The average time between arc initiation and relay tripping ranges from 100 to 1,000 milliseconds (ms)—literally within the blink of an eye, which is typically measured at 100 to 400 ms.

Although this duration is extremely brief, the arc event will almost certainly cause sufficient damage to require switchgear repair or replacement of parts. Production processes dependent on the switchgear may also suffer severe disruption.

Switchgear with passive internal arc protection incorporates a type of ducting system that provides an "escape route" for high-pressure, high-temperature, and potentially toxic gases. Some switchgear includes a duct leading to an external area. This solution is typically used in smaller switchgear rooms. If the switchgear is located in a larger room or away from exterior walls, the ducting may vent into the room where the switchgear is installed.

Both ventilation strategies reduce or eliminate the ejection of arc gases from the front of the switchgear, helping to minimize potential injury. They also help dissipate explosive pressure, reducing internal damage to the switchgear.

Active Internal Arc Interruption

In switchgear equipped with active internal arc interruption, the protection circuit operates independently of the protective relay. The typical arc interruption time is approximately 60–80 ms, which is the sum of the time required to detect the arc, initiate the circuit breaker, and complete the breaker operation.

Sensing technology sends a signal to the upstream circuit breaker to interrupt the circuit, detecting the arc very quickly. Two common arc detection methods are current-sensing devices and/or optical light sensors that "see" the flash. The response time is faster than passive internal arc protection, but still insufficient to prevent potentially significant damage and injury.

It is well known that spring-operated circuit breakers can increase their tripping time as they age, resulting in longer arc extinguishing times. Longer tripping times are directly linked to increased arc flash damage. This is not an issue with magnetic circuit breakers, which do not slow down over time.

Active Arc Elimination

The two methods above help reduce the potential damage and injury caused by arcs, but it is important to note that both are reactive—they respond only after an arc has occurred. The third method, active arc elimination, is designed to respond so quickly that it can almost entirely eliminate the arc.

Technically, like the previous methods, it also reacts to an arc once it occurs, but its response is so rapid that damage to the switchgear is typically minimal, and the risk of injury to personnel is negligible or nonexistent. It achieves a significantly faster response—usually less than 1.5 ms and never exceeding 4 ms. Instead of tripping the upstream circuit breaker, it uses an Ultra-Fast Earthing Switch (UFES) to initiate a three-phase grounded short-circuit when an arc fault occurs.

The UFES, combined with fast and reliable fault detection via various sensing methods, helps ensure that an arc fault is extinguished almost immediately after it occurs. This results in a dramatic reduction in heat and pressure. Resetting the switchgear typically requires only wiping the interior and replacing primary switching elements—all of which can usually be completed within a few hours.

Summary

If a fire breaks out in your home, having a detection and alarm system that immediately alerts the fire department, bringing them within minutes, is reassuring. But even more reassuring would be a system that prevents the fire from starting in the first place. This is analogous to how active arc elimination distinguishes itself from other arc fault management methods.

Active arc elimination is arguably the most effective method for reducing arc flash hazards, though it comes at a slightly higher cost compared to other protection methods. For switchgear lacking any arc protection design, active arc elimination represents a relatively small investment relative to the value of the switchgear it protects. When evaluating cost-benefit, it is also important to consider additional costs arising from production or process interruptions following an arc event.

To help provide the highest level of protection for your personnel and switchgear, and to minimize the risk of operational disruption, active arc elimination via an ultra-fast earthing switch is the right choice for your switchgear.

Give a tip and encourage the author!
Recommended
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
Based on years of field statistics on switchgear accidents, combined with analysis focusing on the circuit breaker itself, the main causes have been identified as: failure of operation mechanism; insulation faults; poor breaking and closing performance; and poor conductivity.1.Failure of Operation MechanismFailure of operation mechanism manifests as delayed operation or unintended operation. Since the most basic and important function of a high-voltage circuit breaker is to operate correctly and
Felix Spark
11/04/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Compact Air-Insulated RMUs for Retrofit & New Substations
Compact Air-Insulated RMUs for Retrofit & New Substations
Air-insulated ring main units (RMUs) are defined in contrast to compact gas-insulated RMUs. Early air-insulated RMUs used vacuum or puffer-type load switches from VEI, as well as gas-generating load switches. Later, with the widespread adoption of the SM6 series, it became the mainstream solution for air-insulated RMUs. Similar to other air-insulated RMUs, the key difference lies in replacing the load switch with an SF6-encapsulated type—where the three-position switch for load and grounding is
Echo
11/03/2025
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Expected service life of 30–40 years, front access, compact design equivalent to SF6-GIS, no SF6 gas handling – climate-friendly, 100% dry air insulation. The Nu1 switchgear is metal-enclosed, gas-insulated, featuring a withdrawable circuit breaker design, and has been type-tested according to relevant standards, approved by the internationally recognized STL laboratory.Compliance Standards Switchgear: IEC 62271-1 High-voltage switchgear and controlgear – Part 1: Common specifications for altern
Edwiin
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.