24kV Maintenance-Free Eco Gas Insulated RMU with Smart Monitoring – Urban Grid Ready

Garca
Garca
Field: Design & Maintenance
Congo

Compared with 12kV, 24kV can supply more electrical energy, reduce line losses, and is widely used in overseas markets.

SF₆ is a greenhouse gas whose ozone layer depletion potential is over 20,000 times that of CO₂. Its use must be restricted; therefore, medium-voltage switchgear must not use SF₆ as an insulating gas.

For switchgear, environmentally friendly gases refer to those that do not contain SF₆ as insulating or arc-extinguishing media. Examples include naturally occurring gases (such as nitrogen and carbon dioxide), gas mixtures, and synthetic gases.

The key challenge for environmentally friendly gas-insulated switchgear lies in meeting insulation requirements. While 12kV environmentally friendly gas-insulated ring main units (RMUs) are quite mature, 24kV models have relatively few developers. This is because domestic demand for 24kV equipment is low and its insulation design is more complex—only a handful of complete set manufacturers with export needs are developing such products.

In essence, 24kV switchgear design can be simplified through the following approaches:

  • Solid composite insulation: This ensures the busbar meets voltage withstand requirements. Increasing the isolation gap or expanding the gas tank size can also satisfy voltage withstand standards.

  • Increased gas pressure: Raising the relative pressure from 0.04MPa to 0.14MPa addresses both insulation and gap voltage withstand requirements, with the only additional step being the replacement of the arc-extinguishing chamber with a 24kV-rated one.

Alternatively, C4/C5 synthetic gas mixed with CO₂ can be used, as its insulation strength is similar to that of SF₆. Minor enhancements to the insulation system of SF₆-based RMUs can make them meet 24kV voltage withstand requirements. However, C4/C5 is also a greenhouse gas—though its global warming potential (GWP) is only 1/20 that of SF₆. Additionally, it decomposes into toxic gases after arc extinction, which is not conducive to sustainable development.

The clearance between live parts of the switch is determined by the impulse withstand voltage:

  • For 24kV equipment, the impulse withstand voltage is 125kV, corresponding to an air clearance of 220mm (or 95mm if 3M heat-shrinkable sleeves and BPTM round busbars are used).

  • For 12kV equipment, the impulse withstand voltage is 75kV, with an air clearance of 120mm (or 55mm with the same 3M sleeves and BPTM busbars).

For side-mounted switch units in RMUs, the clearance requirements for composite insulation can be fully met.

Parameter Table.jpg


 The earliest 24kV solid-insulated ring main units include Eaton's SVS and Xirui's products. Due to the fact that the switches designed by Xirui for overseas markets are two-position—meaning the switch is either in the closed position or the grounded position—this design failed to meet China's requirement for three-position operation with step-by-step control, so an isolation position had to be added between the two positions.

How to achieve product miniaturization, cost-effectiveness, and environmental adaptability determines the development direction of 24kV eco-friendly gas-insulated ring main units. Solid composite insulation has high cost and still finds it difficult to solve the voltage withstand problem of isolation breaks. Meanwhile, because alternative gases such as dry air and nitrogen have insufficient insulation strength, the break distance and ground distance need to be similar to those required for natural air, i.e., ≥220mm. This makes such rotary three-position switches require a large size, while linear-motion switches face certain difficulties in either increasing the height dimension or the width dimension. The adoption of double-break isolation and grounding switches can solve the problem of oversized isolation switches.

To provide gas filling pressure, the problem of enclosure strength needs to be solved. The use of an aluminum alloy cylindrical structure enables dimension optimization, uniform electric field, and good heat dissipation. The internal busbars are arranged in a delta (triangular) configuration, and the three-position switch and vacuum interrupter are installed vertically, which maximizes the use of spatial dimensions and achieves small size and high power capacity.

Give a tip and encourage the author!
Recommended
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
Based on years of field statistics on switchgear accidents, combined with analysis focusing on the circuit breaker itself, the main causes have been identified as: failure of operation mechanism; insulation faults; poor breaking and closing performance; and poor conductivity.1.Failure of Operation MechanismFailure of operation mechanism manifests as delayed operation or unintended operation. Since the most basic and important function of a high-voltage circuit breaker is to operate correctly and
Felix Spark
11/04/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Compact Air-Insulated RMUs for Retrofit & New Substations
Compact Air-Insulated RMUs for Retrofit & New Substations
Air-insulated ring main units (RMUs) are defined in contrast to compact gas-insulated RMUs. Early air-insulated RMUs used vacuum or puffer-type load switches from VEI, as well as gas-generating load switches. Later, with the widespread adoption of the SM6 series, it became the mainstream solution for air-insulated RMUs. Similar to other air-insulated RMUs, the key difference lies in replacing the load switch with an SF6-encapsulated type—where the three-position switch for load and grounding is
Echo
11/03/2025
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Expected service life of 30–40 years, front access, compact design equivalent to SF6-GIS, no SF6 gas handling – climate-friendly, 100% dry air insulation. The Nu1 switchgear is metal-enclosed, gas-insulated, featuring a withdrawable circuit breaker design, and has been type-tested according to relevant standards, approved by the internationally recognized STL laboratory.Compliance Standards Switchgear: IEC 62271-1 High-voltage switchgear and controlgear – Part 1: Common specifications for altern
Edwiin
11/03/2025