What Is a Ring Main Unit? Types & Benefits

Noah
Noah
Field: Design & Maintenance
Australia

1. Product Overview

A Ring Main Unit (RMU) is an electrical apparatus composed of high-voltage switching equipment enclosed in a metal or non-metal insulated cabinet, or configured as modular compartments forming a ring-type power supply unit. Its core components typically include load switches and fuses, offering advantages such as simple structure, compact size, low cost, improved power parameters and performance, and enhanced power supply safety.

RMUs are widely used in distribution substations and prefabricated (container-type) transformer substations located at load centers, including urban residential communities, high-rise buildings, large public facilities, and industrial enterprises.

2. Working Principle and Applications

2.1 Ring Network Power Supply

To improve power supply reliability, allowing users to receive power from two directions, power grids are often interconnected into a closed loop—known as ring network Ring Network Supply.

In 10kV AC distribution systems for industrial plants, residential areas, ports, and high-rise buildings—where load capacities are generally moderate—the high-voltage circuits commonly employ load switches or vacuum contactors for control, combined with high-voltage fuses for protection. Such systems are typically referred to as ring network systems, and the switchgear used is commonly known as a Ring Main Unit.

The "ring" refers to a closed-loop distribution network: the main feeder forms a continuous loop, powered by one or more sources. From this loop, power is distributed through individual high-voltage switchgear units.

This configuration allows each distribution branch to draw power from either side of the loop:

  • If the left-side feeder fails, power is supplied from the right.

  • If the right-side feeder fails, power is supplied from the left.

Although the overall system may have a single power source, each branch effectively enjoys dual-source redundancy, significantly improving supply reliability.

Each outgoing circuit is equipped with a dedicated switchgear unit (outgoing switch cabinet), whose busbar also serves as part of the ring main. The entire ring is formed by connecting the busbars of all outgoing cabinets. Each such cabinet is called a Ring Main Unit.

Note: A standalone RMU does not inherently exhibit "ring" functionality; its benefits are realized only when integrated into a complete ring network.

2.2 Key Configuration

Since RMUs typically serve moderate loads (e.g., transformers up to 1250kVA), they do not require complex circuit breakers. Instead, they use simplified load switches combined with high-voltage fuses:

  • The load switch handles normal load current switching.

  • The fuse interrupts short-circuit currents.

Together, they replace the function of a circuit breaker—within certain capacity limits. This design reduces complexity, cost, and maintenance needs, making it ideal for infrequent operation scenarios.

Over time, due to widespread adoption, the term "RMU" has evolved beyond strict ring networks and now generally refers to any high-voltage switchgear using a load switch as the primary switching device.

2.3 Market Drivers and Advantages

RMUs have gained rapid popularity despite their relatively recent emergence, driven by:

  • The rise of medium- and small-capacity users (transformers ≤1250kVA).

  • Demand for stable, long-term power supply with infrequent switching.

  • Urban development requiring compact, oil-free electrical equipment in high-rise buildings (due to fire safety and space constraints).

RMUs meet these needs with:

  • Simple structure

  • High operational reliability and safety

  • Minimal maintenance

  • Low operating costs

Compared to circuit breaker-based switchgear, RMUs offer outstanding advantages. This demand has spurred innovation in smaller, higher-performance load switches, further advancing RMU technology. Today’s RMUs are not only high-performing but also standardized and series-produced, greatly expanding their application range.

3. Common RMU Models

moudle..jpg

moudle..jpg

4. Protection Overview

4.1 Microprocessor-Based Protection Relay

Modern RMUs increasingly adopt microprocessor-based protection relays—a high-tech automation product integrating protection, monitoring, control, and communication functions. Developed based on extensive domestic and international experience and tailored to China’s integrated automation systems, it is ideal for building intelligent switchgear.

Key features:

  • Built-in library of over 20 standard protection functions.

  • Comprehensive data acquisition for analog signals (voltage, current via CTs) and digital status signals.

4.2 Protection Requirements

moudle..jpg

Give a tip and encourage the author!
Recommended
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
Based on years of field statistics on switchgear accidents, combined with analysis focusing on the circuit breaker itself, the main causes have been identified as: failure of operation mechanism; insulation faults; poor breaking and closing performance; and poor conductivity.1.Failure of Operation MechanismFailure of operation mechanism manifests as delayed operation or unintended operation. Since the most basic and important function of a high-voltage circuit breaker is to operate correctly and
Felix Spark
11/04/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Compact Air-Insulated RMUs for Retrofit & New Substations
Compact Air-Insulated RMUs for Retrofit & New Substations
Air-insulated ring main units (RMUs) are defined in contrast to compact gas-insulated RMUs. Early air-insulated RMUs used vacuum or puffer-type load switches from VEI, as well as gas-generating load switches. Later, with the widespread adoption of the SM6 series, it became the mainstream solution for air-insulated RMUs. Similar to other air-insulated RMUs, the key difference lies in replacing the load switch with an SF6-encapsulated type—where the three-position switch for load and grounding is
Echo
11/03/2025
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Expected service life of 30–40 years, front access, compact design equivalent to SF6-GIS, no SF6 gas handling – climate-friendly, 100% dry air insulation. The Nu1 switchgear is metal-enclosed, gas-insulated, featuring a withdrawable circuit breaker design, and has been type-tested according to relevant standards, approved by the internationally recognized STL laboratory.Compliance Standards Switchgear: IEC 62271-1 High-voltage switchgear and controlgear – Part 1: Common specifications for altern
Edwiin
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.