• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


How to Calculate Short Circuit Current of Circuit Breaker

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

How To Calculate Short Circuit Current

When there is a short circuit fault in the electrical system, a huge short circuit current flows through the system including the circuit breaker (CB) contacts, unless the fault is cleared by tripping the CB. When the short circuit current flows through the CB, the different current carrying parts of the circuit breaker are subjected to huge mechanical and thermal stresses.

If the conducting parts of the CB do not have sufficient cross-sectional area, there may be a chance of dangerously high temperature rise. This high temperature may affect insulation quality of the CB.

The CB contacts also experience high temperature. The thermal stresses of CB contacts are proportional to I2Rt, where R is the contact resistance, depends upon contact pressure and contact surface condition. I is the rms value of short circuit current and t is duration for which the short circuit current has flown through the contacts.

After initiating fault, the short circuit current stays until the interrupting unit of CB, breaks. Hence, time t is breaking time of the circuit breaker. As this time is very less in scale of mili second, it is assumed that all the heat produced during fault is absorbed by the conductor since there is no sufficient time for convention and radiation of heat.
The temperature rise can be determined by the following formula,
Where, T is the temperature rise per second in degree centigrade.
I is the
current (rms symmetrical) in Ampere.
A is the cross-sectional area of the conductor.
ε is the temperature coefficient of
resistivity of the conductor at 20oC.

As it is known to us, that aluminum above 160oC losses its mechanical strength and becomes soft, it is desired to limit the temperature rise below this temperature. This requirement actually sets the permissible temperature rise during short circuit. This limit can be achieved by controlling CB breaking time and proper designing of conductor dimension.

Short Circuit Force

The electromagnetic force developed between two parallel electric current carrying conductors, is given by the formula,
Where, L is the length of the both conductors in inch.

S is the distance between them in inch.
I is the current carried by each of the
conductors.

It is experimentally proved that, electromagnetic short circuit force is maximum when the value of short circuit current I, is 1.75 times the initial rms value of the symmetrical short circuit current wave.

However, in certain circumstances it is possible that, forces greater than these may develop, such as, for instance in the case of very rigid bars or due to resonance in the case of bars liable to mechanical vibration. Experiments have also shown that the reactions produced in a non resonating structure by an alternating current at the instant of application or removal of the forces may exceed the reactions experienced while the current is flowing.

Thus it is advisable to error on the side of safety and to allow for all contingencies, for which one should take into account the maximum force which could be developed by the initial peak value of the asymmetrical short circuit current. This force may be taken as having a value which is twice of that calculated from the above formula.

The formula is strictly useful for circular cross-sectional conductor. Although L is a finite length of the portions of conductors run parallel to each other, but the formula is only suitable where the total length of each conductor is assumed as infinite.

In practical cases the total length of the conductor is not infinite. It is also considered in mind, that, the flux density near the ends of current carrying conductor is considerably different than its middle portion.

Hence, if we use above formula for short conductor, the force calculated would be much higher than actual.

It is seen that, this error may be eliminated considerably if we use the term,
is stead of L/S in the above formula.
The formula then becomes,
The formula, represented by equation (2), gives error free result when the ratio L/S is greater than 20. When 20 > L/S > 4, formula (3) is suitable for error free result.
If L/S < 4, formula (2) is suitable for error free result. The above formulas are only applicable for circular cross-sectional conductors. But for rectangular cross-sectional conductor, the formula needs to have some correction factor. Say this factor is K. Hence, the above formula ultimately becomes,
Although the effect of shape of cross-section of conductor reduces rapidly if spacing between the conductor increases the value of K is maximum for strip like conductor whose thickness is quite less than its width. K is negligible when shape of cross-section of conductor is perfectly square. K is unity for perfectly circular cross-sectional conductor. This holds true for both standard and remote control circuit breaker.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
Based on years of field statistics on switchgear accidents, combined with analysis focusing on the circuit breaker itself, the main causes have been identified as: failure of operation mechanism; insulation faults; poor breaking and closing performance; and poor conductivity.1.Failure of Operation MechanismFailure of operation mechanism manifests as delayed operation or unintended operation. Since the most basic and important function of a high-voltage circuit breaker is to operate correctly and
Felix Spark
11/04/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Compact Air-Insulated RMUs for Retrofit & New Substations
Compact Air-Insulated RMUs for Retrofit & New Substations
Air-insulated ring main units (RMUs) are defined in contrast to compact gas-insulated RMUs. Early air-insulated RMUs used vacuum or puffer-type load switches from VEI, as well as gas-generating load switches. Later, with the widespread adoption of the SM6 series, it became the mainstream solution for air-insulated RMUs. Similar to other air-insulated RMUs, the key difference lies in replacing the load switch with an SF6-encapsulated type—where the three-position switch for load and grounding is
Echo
11/03/2025
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Expected service life of 30–40 years, front access, compact design equivalent to SF6-GIS, no SF6 gas handling – climate-friendly, 100% dry air insulation. The Nu1 switchgear is metal-enclosed, gas-insulated, featuring a withdrawable circuit breaker design, and has been type-tested according to relevant standards, approved by the internationally recognized STL laboratory.Compliance Standards Switchgear: IEC 62271-1 High-voltage switchgear and controlgear – Part 1: Common specifications for altern
Edwiin
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.