Low temperature ambient effect for outdoor vacuum circuit breaker (VCB) operation

Edwiin
Edwiin
Field: Power switch
China

The vacuum arc - interrupting performance relies on the arcing within the metal vapor, which is generated from the contact material. Significantly, this process remains unaffected by low temperatures.

A vacuum interrupter is typically fabricated from metals and ceramics and undergoes brazing at approximately 800 degrees Celsius. The material characteristics of both metal and ceramic, as well as the brazed joints between them, are inherently resistant to low - temperature impacts.
Sliding guides are employed to direct the moving electrode assembly of the vacuum interrupter (VI). Metal - based guides are impervious to low temperatures, while plastic - made guides can withstand the required low - temperature conditions.

Vacuum circuit breaker (VCB) mechanisms are low - energy systems, traditionally composed of springs and linkages. Through proper design, these components can be engineered to be immune to low - temperature effects. In more recent mechanism designs that utilize the stored magnetic energy from permanent magnets, material selections are made such that the components can tolerate the necessary low temperatures. Additionally, the installation of heaters can further enhance the operational performance of these mechanisms.

In conclusion, a vacuum circuit breaker can be specifically designed to function effectively at low temperatures ranging from - 30°C to - 50°C. The accompanying photo depicts a 36 kV VCB situated within a test chamber for conducting both low - and high - temperature tests.

Give a tip and encourage the author!
Recommended
What are the causes of dielectric withstand failure in vacuum circuit breakers?
What are the causes of dielectric withstand failure in vacuum circuit breakers?
Causes of Dielectric Withstand Failure in Vacuum Circuit Breakers: Surface contamination: The product must be thoroughly cleaned before dielectric withstand testing to remove any dirt or contaminants.Dielectric withstand tests for circuit breakers include both power-frequency withstand voltage and lightning impulse withstand voltage. These tests must be performed separately for phase-to-phase and pole-to-pole (across the vacuum interrupter) configurations.Circuit breakers are recommended to be t
Felix Spark
11/04/2025
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
Based on years of field statistics on switchgear accidents, combined with analysis focusing on the circuit breaker itself, the main causes have been identified as: failure of operation mechanism; insulation faults; poor breaking and closing performance; and poor conductivity.1.Failure of Operation MechanismFailure of operation mechanism manifests as delayed operation or unintended operation. Since the most basic and important function of a high-voltage circuit breaker is to operate correctly and
Felix Spark
11/04/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Compact Air-Insulated RMUs for Retrofit & New Substations
Compact Air-Insulated RMUs for Retrofit & New Substations
Air-insulated ring main units (RMUs) are defined in contrast to compact gas-insulated RMUs. Early air-insulated RMUs used vacuum or puffer-type load switches from VEI, as well as gas-generating load switches. Later, with the widespread adoption of the SM6 series, it became the mainstream solution for air-insulated RMUs. Similar to other air-insulated RMUs, the key difference lies in replacing the load switch with an SF6-encapsulated type—where the three-position switch for load and grounding is
Echo
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.