What is Overcurrent Relay?

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

 What is Overcurrent Relay?

Definition

An overcurrent relay is defined as a relay that activates only when the current value exceeds the relay's set value. It safeguards the equipment in the power system from fault currents.

Classification Based on Operation Time

Based on the time it takes to operate, the overcurrent relay can be categorized into the following types:

  • Instantaneous Overcurrent Relay

  • Inverse Time Overcurrent Relay

  • Definite Time Overcurrent Relay

  • Inverse Definite Time Overcurrent Relay

  • Very Inverse Definite Time Overcurrent Relay

  • Extremely Inverse Definite Time Overcurrent Relay

Instantaneous Overcurrent Relay

The instantaneous overcurrent relay has no deliberately introduced time delay in its operation. When the current within the relay exceeds the operating value, its contacts close immediately. The time span between the moment the current reaches the pick - up value and the closing of the relay contacts is extremely short.

The most notable advantage of the instantaneous relay is its rapid operating time. It commences operation as soon as the current value surpasses the relay setting. This relay functions only when the impedance between the power source and the relay is lower than the impedance specified for the section.

The key feature of this relay is its operational speed. It protects the system from earth faults and is also utilized to protect the system from circulating currents. The instantaneous overcurrent relay is typically installed in the outgoing feeder.

Inverse - Time Overcurrent Relay

The inverse - time overcurrent relay operates when the magnitude of its operating current is inversely proportional to the magnitude of the energizing quantities. As the current increases, the operating time of the relay decreases, meaning its operation depends on the magnitude of the current.

The characteristic curve of this relay is presented in the figure below. The relay remains inactive when the current value is less than the pick - up value. It is employed for the protection of distribution lines. The inverse - time relay is further classified into three subtypes.

relay.jpegInverse Definite Minimum Time (IDMT) Relay

The Inverse Definite Minimum Time (IDMT) relay is a type of protective relay whose operating time is approximately inversely proportional to the magnitude of the fault current. The operating time of this relay can be adjusted by setting the time delay. The IDMT relay incorporates an electromagnetic core. This is because the electromagnetic core can readily saturate when the current magnitude exceeds the pick - up current. The IDMT relay is widely used for the protection of distribution lines. It strikes a balance between the speed of response and the selectivity required in such power distribution systems.

Very Inverse Relay

The very inverse relay exhibits an inverse time - current characteristic that is more pronounced than that of the IDMT relay. This type of relay finds applications in feeders and long - distance transmission lines. It is particularly useful in locations where the magnitude of the short - circuit current drops rapidly due to the significant distance from the power source. The very inverse relay is designed to sense fault currents regardless of the fault location. This makes it suitable for protecting long - line sections where the impedance varies along the line, and the fault current magnitude can be highly dependent on the distance from the source.

Extremely Inverse Relay

The extremely inverse relay has a time - current characteristic that shows an even more exaggerated inverse relationship compared to the IDMT and very inverse relays. This relay is commonly employed for protecting equipment such as cables and transformers. In situations where the pick - up value of the current exceeds the relay's setting, the extremely inverse relay can operate instantaneously. It provides fast operation even under fault current conditions, which is crucial for protecting equipment from severe over - currents. Additionally, it is often used to detect overheating in machines, as its characteristic can be tuned to respond quickly to abnormal current increases associated with overheating.

Inverse time relays, including the IDMT, very inverse, and extremely inverse relays, are extensively used in distribution networks and power plants. Their ability to provide rapid operation under fault conditions, owing to their unique fault - time characteristics, makes them an essential component in safeguarding power systems from various electrical faults.

Give a tip and encourage the author!
Recommended
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
Based on years of field statistics on switchgear accidents, combined with analysis focusing on the circuit breaker itself, the main causes have been identified as: failure of operation mechanism; insulation faults; poor breaking and closing performance; and poor conductivity.1.Failure of Operation MechanismFailure of operation mechanism manifests as delayed operation or unintended operation. Since the most basic and important function of a high-voltage circuit breaker is to operate correctly and
Felix Spark
11/04/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Compact Air-Insulated RMUs for Retrofit & New Substations
Compact Air-Insulated RMUs for Retrofit & New Substations
Air-insulated ring main units (RMUs) are defined in contrast to compact gas-insulated RMUs. Early air-insulated RMUs used vacuum or puffer-type load switches from VEI, as well as gas-generating load switches. Later, with the widespread adoption of the SM6 series, it became the mainstream solution for air-insulated RMUs. Similar to other air-insulated RMUs, the key difference lies in replacing the load switch with an SF6-encapsulated type—where the three-position switch for load and grounding is
Echo
11/03/2025
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Expected service life of 30–40 years, front access, compact design equivalent to SF6-GIS, no SF6 gas handling – climate-friendly, 100% dry air insulation. The Nu1 switchgear is metal-enclosed, gas-insulated, featuring a withdrawable circuit breaker design, and has been type-tested according to relevant standards, approved by the internationally recognized STL laboratory.Compliance Standards Switchgear: IEC 62271-1 High-voltage switchgear and controlgear – Part 1: Common specifications for altern
Edwiin
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.