What is an Electrical Isolation Switch?


Isolator Definition


An isolator in electrical systems is a manually operated mechanical switch that separates a part of the circuit for safe maintenance.

 


08cc5898dfb53f73626af4223e16392e.jpeg

 


A circuit breaker trips the circuit, but its open contacts are not visible from the outside. Therefore, it is unsafe to touch an electrical circuit by just switching off the breaker. For better safety, we need a way to visibly confirm that the circuit is open before touching it. An isolator is a mechanical switch that separates part of the circuit for safe maintenance. An isolator is defined as a manually operated mechanical switch that separates a part of the electrical power system. Isolators are used to open a circuit under no load. The main purpose of an isolator is to separate one part of the circuit from another and it should not be opened while current is flowing. Isolators are usually placed on both ends of a circuit breaker to allow safe repair or replacement.

 


Purpose


The main purpose of an isolator is to ensure safety by isolating a part of the circuit; it should not be operated under load.

 


Types


There are different types of isolators available depending upon system requirement such as

 


  • Double Break Isolator

  • Single Break Isolator

  • Pantograph type Isolator.


Depending upon the position in the power system, the isolators can be categorized as

 


  • Bus side isolator – the isolator is directly connected with main bus



  • Line side isolator – the isolator is situated at line side of any feeder


  • Transfer bus side isolator – the isolator is directly connected with transfer bus.

 


Constructional Features of Double Break Isolators

 


ec66e064b9340f10c896be69b05c5de2.jpeg

 


Let’s discuss constructional features of Double Break Isolators. These have three stacks of post insulators as shown in the figure. The central post insulator carries a tubular or flat male contact which can be rotated horizontally with a rotation of central post insulator. This rod type contact is also called moving contact.

 


The female type contacts are fixed on the top of the other post insulators which fitted at both sides of the central post insulator. The female contacts are generally in the form of spring-loaded figure contacts. The rotational movement of the male contact allows it to connect with the female contacts, closing the isolator. Rotating the male contact in the opposite direction disconnects it from the female contacts, opening the isolator.

 


536fb4f737207a7772557a8160c08633.jpeg

 


Rotation of the central post insulator is done by a driving lever mechanism at the base of the post insulator, and it is connected to operating handle (in case of hand operation) or motor (in case of motorized operation) of the isolator through a mechanical tie rod.

 


Constructional features of Single Break Isolators


The contact arm is divided into two parts one carries male contact and other carries female contact. The contact arm moves due to rotation of the post insulator upon which the contact arms are fitted. Rotating both post insulators stacks in opposite directions closes the contact arm, closing the isolator. Counter-rotation opens the contact arm, turning off the isolator. This type of isolator is usually motorized, but an emergency hand-operated mechanism is also available.

 


Earthing Switches


Earthing switches are mounted on the base of line side isolator. Earthing switches are usually vertically broken switches. Earthing arms (contact arm of earthing switch) usually are aligned horizontally at off condition during switching on the operation, these earthing arms rotate and move to vertical position and make contact with earth female contacts fitted at the top of the post insulator stack of the isolator at its outgoing side. The earthing arms are so interlocked with the main isolator moving contacts that it can be closed only when the primary contacts of the isolator are in open position. Similarly, the main isolator contacts can be closed only when the earthing arms are in open position.

 


Operation of Electrical Isolator


Since isolators do not have arc quenching techniques, they must be operated without current flowing through the circuit. An isolator should not open or close a live circuit to prevent arcing. Therefore, isolators must be opened after the circuit breaker and closed before the circuit breaker. The isolator can be operated by hand locally as well as by motorized mechanism from a remote position. Motorized operation arrangement costs more compared to hand operation; hence decision must be taken before choosing an isolator for the system whether hand operated or motor operated economically optimum for the system. For voltages up to 145 KV system hand operated isolators are used whereas for higher voltage systems like 245 KV or 420 KV and above motorized isolators are used.


Give a tip and encourage the author!
Recommended
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
Based on years of field statistics on switchgear accidents, combined with analysis focusing on the circuit breaker itself, the main causes have been identified as: failure of operation mechanism; insulation faults; poor breaking and closing performance; and poor conductivity.1.Failure of Operation MechanismFailure of operation mechanism manifests as delayed operation or unintended operation. Since the most basic and important function of a high-voltage circuit breaker is to operate correctly and
Felix Spark
11/04/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Compact Air-Insulated RMUs for Retrofit & New Substations
Compact Air-Insulated RMUs for Retrofit & New Substations
Air-insulated ring main units (RMUs) are defined in contrast to compact gas-insulated RMUs. Early air-insulated RMUs used vacuum or puffer-type load switches from VEI, as well as gas-generating load switches. Later, with the widespread adoption of the SM6 series, it became the mainstream solution for air-insulated RMUs. Similar to other air-insulated RMUs, the key difference lies in replacing the load switch with an SF6-encapsulated type—where the three-position switch for load and grounding is
Echo
11/03/2025
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Expected service life of 30–40 years, front access, compact design equivalent to SF6-GIS, no SF6 gas handling – climate-friendly, 100% dry air insulation. The Nu1 switchgear is metal-enclosed, gas-insulated, featuring a withdrawable circuit breaker design, and has been type-tested according to relevant standards, approved by the internationally recognized STL laboratory.Compliance Standards Switchgear: IEC 62271-1 High-voltage switchgear and controlgear – Part 1: Common specifications for altern
Edwiin
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.