• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Fault Diagnosis and Troubleshooting of 10kV High-Voltage Switchgear

Garca
Garca
Field: Design & Maintenance
Congo

I. Common Fault Types and Diagnostic Methods

Electrical Faults

  • Circuit Breaker Failure to Operate or Maloperation: Check the energy storage mechanism, closing/tripping coils, auxiliary switches, and secondary circuits.

  • High-Voltage Fuse Blown: Measure voltage across the fuse terminals; inspect busbar joints, cable terminations, and protection relay settings.

  • Busbar Discharge or Insulator Damage: Listen for discharge sounds, check temperature at busbar connections, and visually inspect insulators for flashover traces.

Mechanical Faults

  • Disconnector Stuck or Jammed: Inspect lubrication of mechanical linkages, operating spring condition, and auxiliary switches.

  • Operating Mechanism Spring Failure: Check for spring fatigue or aging; test the energy storage mechanism.

Insulation Faults

  • Insulator Damage or Busbar Discharge: Visually inspect insulator surfaces for flashover marks; use an infrared thermal imager to monitor temperature at busbar joints.

Control Circuit Faults

  • Relay Protection Maloperation: Verify protection relay settings, inspect CT secondary circuits, and check stability of control power supply.

II. Fault Handling Methods

Electrical Fault Handling

  • Circuit Breaker Failure to Operate or Maloperation: Manually store energy and test closing operation; replace damaged coils; repair or replace faulty auxiliary switches.

  • High-Voltage Fuse Blown: Tighten busbar joints, adjust protection settings, and replace the fuse.

  • Busbar Discharge or Insulator Damage: Tighten busbar connection bolts, clean dust from insulator surfaces, and install dehumidification devices.

Mechanical Fault Handling

  • Disconnector Stuck or Jammed: Lubricate linkage mechanisms, replace springs, and manually reset auxiliary switches.

  • Operating Mechanism Spring Failure: Replace the spring, apply lubricant, and manually test the energy storage function.

Insulation Fault Handling

  • Insulator Damage or Busbar Discharge: Replace damaged insulators; perform power-frequency withstand voltage tests on the busbar.

Control Circuit Fault Handling

  • Relay Protection Maloperation: Recalibrate protection settings, repair CT secondary circuits, and stabilize the control power supply.

III. Preventive Maintenance Measures

  • Perform regular infrared thermography to detect overheating issues.

  • Conduct partial discharge (PD) testing to identify early signs of insulation aging.

  • Maintain mechanical components by lubricating moving parts to prevent jamming.

  • Inspect cable terminations regularly to prevent loosening or oxidation, reducing arc discharge risks.

  • Clean dust and moisture periodically to improve insulation performance.

Note: These methods should be applied flexibly according to actual site conditions. Always ensure safety during troubleshooting. When necessary, contact qualified professionals for assistance.

Give a tip and encourage the author!
Recommended
How to Identify Internal Faults in a Transformer?
How to Identify Internal Faults in a Transformer?
Measure DC resistance: Use a bridge to measure the DC resistance of each high- and low-voltage winding. Check whether the resistance values among phases are balanced and consistent with the manufacturer’s original data. If phase resistance cannot be measured directly, line resistance may be measured instead. The DC resistance values can indicate whether the windings are intact, whether there are short circuits or open circuits, and whether the contact resistance of the tap changer is normal. If
Felix Spark
11/04/2025
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
Based on years of field statistics on switchgear accidents, combined with analysis focusing on the circuit breaker itself, the main causes have been identified as: failure of operation mechanism; insulation faults; poor breaking and closing performance; and poor conductivity.1.Failure of Operation MechanismFailure of operation mechanism manifests as delayed operation or unintended operation. Since the most basic and important function of a high-voltage circuit breaker is to operate correctly and
Felix Spark
11/04/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Compact Air-Insulated RMUs for Retrofit & New Substations
Compact Air-Insulated RMUs for Retrofit & New Substations
Air-insulated ring main units (RMUs) are defined in contrast to compact gas-insulated RMUs. Early air-insulated RMUs used vacuum or puffer-type load switches from VEI, as well as gas-generating load switches. Later, with the widespread adoption of the SM6 series, it became the mainstream solution for air-insulated RMUs. Similar to other air-insulated RMUs, the key difference lies in replacing the load switch with an SF6-encapsulated type—where the three-position switch for load and grounding is
Echo
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.