What Are the Types and Common Faults of HV Switchgear?

Noah
Noah
Field: Design & Maintenance
Australia

High-voltage switchgear is a critical electrical device in power systems. Deterioration in switchgear operating conditions is one of the main causes of power system failures. So, what are the common faults in high-voltage switchgear?

I. Classification of High-Voltage Switchgear

(1) Outdoor and Indoor Types

Based on installation location, high-voltage switchgear can be classified as outdoor or indoor types. Indoor switchgear is commonly used for systems at 10 kV and below. According to primary circuit configurations, they can be further categorized as incoming/outgoing line switchgear, tie oil-switchgear, bus section switchgear, etc. In 10 kV incoming/outgoing switchgear, oil-immersed or vacuum circuit breakers are typically installed. These breakers are usually equipped with spring-operated or electromagnetic operating mechanisms, although some use manual or permanent magnet mechanisms. Different switchgear designs vary significantly in structure, which affects sensor selection and installation.

(2) Fixed and Withdrawable Types

Based on usage, high-voltage switchgear can be divided into fixed and withdrawable (draw-out) types. Historically, power plants preferred withdrawable switchgear for station service systems, while fixed types were more common in utility power supply systems. With technological advances and new product development, traditional practices are evolving. For example, metal-clad withdrawable switchgear has evolved from conventional fixed switchgear. This type features a fully enclosed design with functionally separated compartments. It offers improved operational safety, enhanced interlocking against misoperation, easier maintenance, and significantly increased operational reliability.

(3) Development of High-Voltage Switchgear

In recent years, with the development and widespread adoption of compact vacuum circuit breakers, medium-mounted switchgear (also known as switchgear with circuit breakers mounted in the middle compartment) has rapidly advanced as a new type of metal-enclosed, armored, withdrawable switchgear. Medium-mounted switchgear offers many advantages, the most important being the miniaturization of the draw-out unit and the mechanization of manufacturing processes, resulting in higher precision in trolley and guide rail fabrication.

Some manufacturers even ship the trolley (including the main circuit breaker) and the switchgear cabinet separately, enabling easy on-site assembly and commissioning with guaranteed smooth insertion and withdrawal. Due to excellent interchangeability, performance is minimally affected by uneven floor conditions at the site. This type of metal-clad withdrawable switchgear offers safe, reliable operation and convenient maintenance, leading to its increasing adoption in power supply systems.

switchgear.jpg

II. Analysis of Common Faults in High-Voltage Switchgear

Fault analysis shows that most switchgear failures originate from insulation, conduction, and mechanical issues.

(1) Failure to Operate or Maloperation

This is the most common fault in high-voltage switchgear, with causes falling into two categories. The first is mechanical failure in the operating mechanism and transmission system, such as mechanism jamming, component deformation, displacement or damage, loose or stuck tripping/closing solenoids, broken or loose pins, and latch failure. The second category arises from electrical control and auxiliary circuits, including poor contact in secondary wiring, loose terminals, incorrect wiring, burned-out closing/tripping coils (due to mechanism jamming or faulty selector switches), inflexible auxiliary switch operation, and failures in control power supplies, closing contactors, and limit switches.

(2) Switching and Closing Failures

These faults originate from the circuit breaker itself. In oil-immersed circuit breakers, common issues include oil spraying during short circuits, arc chamber damage, insufficient breaking capacity, and explosions during closing. In vacuum circuit breakers, typical problems are vacuum interrupter or bellows leakage, reduced vacuum level, restriking when switching capacitor banks, and ceramic housing fractures.

(3) Insulation Failures

Insulation performance involves balancing various voltages (including normal operating voltage and transient overvoltages), protective measures (e.g., surge arresters), and insulation strength to achieve a safe and economical design. Insulation faults mainly manifest as: external insulation flashover-to-ground, internal insulation flashover-to-ground, phase-to-phase flashover, lightning overvoltage flashover, flashover, pollution flashover, puncture or explosion of porcelain or capacitor bushings, insulator post flashover, and flashover, puncture, or explosion of current transformers (CTs), as well as porcelain insulator fractures.

(4) Current-Carrying Faults

For switchgear rated 7.2–12 kV, the primary cause of current-carrying faults is poor contact at the isolation stabs, leading to overheating and melting of contacts.

(5) External Forces and Other Faults

These include impacts from foreign objects, natural disasters, short circuits caused by small animals, and other unpredictable external or accidental faults.

Give a tip and encourage the author!
Recommended
How to Identify Internal Faults in a Transformer?
How to Identify Internal Faults in a Transformer?
Measure DC resistance: Use a bridge to measure the DC resistance of each high- and low-voltage winding. Check whether the resistance values among phases are balanced and consistent with the manufacturer’s original data. If phase resistance cannot be measured directly, line resistance may be measured instead. The DC resistance values can indicate whether the windings are intact, whether there are short circuits or open circuits, and whether the contact resistance of the tap changer is normal. If
Felix Spark
11/04/2025
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
Based on years of field statistics on switchgear accidents, combined with analysis focusing on the circuit breaker itself, the main causes have been identified as: failure of operation mechanism; insulation faults; poor breaking and closing performance; and poor conductivity.1.Failure of Operation MechanismFailure of operation mechanism manifests as delayed operation or unintended operation. Since the most basic and important function of a high-voltage circuit breaker is to operate correctly and
Felix Spark
11/04/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Compact Air-Insulated RMUs for Retrofit & New Substations
Compact Air-Insulated RMUs for Retrofit & New Substations
Air-insulated ring main units (RMUs) are defined in contrast to compact gas-insulated RMUs. Early air-insulated RMUs used vacuum or puffer-type load switches from VEI, as well as gas-generating load switches. Later, with the widespread adoption of the SM6 series, it became the mainstream solution for air-insulated RMUs. Similar to other air-insulated RMUs, the key difference lies in replacing the load switch with an SF6-encapsulated type—where the three-position switch for load and grounding is