Inductance in Transmission Line

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

What Is Inductance In Transmission Line

Reason of Transmission Line Inductance

Generally, electric power is transmitted through the transmission line with AC high voltage and current. High valued alternating current while flowing through the conductor sets up magnetic flux of high strength with alternating nature. This high valued alternating magnetic flux makes a linkage with other adjacent conductors parallel to the main conductor. Flux linkage in a conductor happens internally and externally. Internally flux linkage is due to self-current and externally flux linkage due to external flux. Now the term inductance is closely related to the flux linkage, denoted by λ. Suppose a coil with N number of turn is linked by flux Φ due to current I, then,
But for transmission line N = 1. We have to calculate only the value of flux Φ, and hence, we can get the transmission line inductance.

Calculation of Inductance of Single Conductor

Calculation of Internal Inductance due to Internal Magnetic Flux of a Conductor

Suppose a conductor is carrying current I through its length l, x is the internal variable radius of the conductor and r is the original radius of the conductor. Now the cross-sectional area with respect to radius x is πx2 square – unit and current Ix is flowing through this cross-sectional area. So the value of Ix can be expressed in term of original conductor current I and cross-sectional area πr2 square – unit
inductance of single conductorNow consider small thickness dx with the 1m length of the conductor, where Hx is the magnetizing force due to current Ix around the area πx2.

And magnetic flux density Bx = μHx, where μ is the permeability of this conductor. Again, µ = µ0µr. If it is considered that the relative permeability of this conductor µr = 1, then µ = µ0. Hence, here Bx = μ0 Hx.
dφ for small strip dx is expressed by
Here entire cross-sectional area of the conductor does not enclose the above expressed flux. The ratio of the cross sectional area inside the circle of radius x to the total cross section of the conductor can be thought about as fractional turn that links the flux. Therefore the flux linkage is

Now, the total flux linkage for the conductor of 1m length with radius r is given by

Hence, the internal inductance is
External Inductance due to External Magnetic Flux of a Conductor

Let us assume, due to skin effect conductor current I is concentrated near the surface of the conductor. Consider, the distance y is taken from the center of the conductor making the external radius of the conductor.

external inductance due to external magnetic flux of a conductorHy is the magnetizing force and By is the magnetic field density at y distance per unit length of the conductor.
Let us assume magnetic flux dφ is present within the thickness dy from D1 to D2 for 1 m length of the conductor as per the figure.
As the total current I is assumed to flow in the surface of the conductor, so the flux linkage dλ is equal to dφ.
But we have to consider the flux linkage from conductor surface to any external distance, i.e. r to D



Inductance of Two Wire Single Phase Transmission Line

Suppose conductor A of radius rA carries a current of IA in opposite direction of current IB through the conductor B of radius rB. Conductor A is at a distance D from conductor B and both are of length l. They are in close vicinity with each other so that flux linkage takes place in both of the conductors due to their electromagnetic effects.
two wire single phaseLet us consider the magnitude of current in both conductors are same and hence IA = – IB,

Now, total flux linkage in conductor A = flux linkage by self-current of conductor A + flux linkage on conductor A due to current in the conductor B.

Similarly, flux linkage in conductor B = flux linkage by self-current of conductor B + flux linkage on conductor B due to current through conductor A.
flux of two wire single phaseNow if we consider a point P in close vicinity both conductor A and B, the flux linkage at point P would be, flux linkage at point P for current carrying conductor A + flux linkage at point P for current carrying conductor B i.e.

Now,……… shown in the figure below in figure (a) and (b).

  • λAAP is the flux linkage at point P for conductor A due to current through conductor A itself.

  • λABP is the flux linkage at point P for conductor A due to current through conductor B.

  • λBAP is the flux linkage at point P for conductor B due to current through conductor A.

  • λBBP is the flux linkage at point P for conductor B due to current through conductor B itself.



λABP and λBAP are negative in value because the directions current are opposite with respect to each other.

If we consider that both conductor are with same radius, i.e. rA = rB = r and point P is shifted to infinite distance then we can write that


If conductor A becomes bundled conductor, then its geometrical mean radius (GMR) will be calculated for n number of conductors per bundle.
Where, d is the distance between the central axis of conductors within the bundle.

Inductance in Three Phase Transmission Line

In the three phase transmission line, three conductors are parallel to each other. The direction of the current is same through each of the conductors.

Let us consider conductor A produces magnetic flux φA,
Conductor B produces magnetic flux φB,
And conductor C produces magnetic flux φC.
When they carry the current of the same magnitude “I”, they are in flux linkage with each other.
three phase transmission lineNow, let us consider a point P near three conductors. So, flux linkage at point P due to current through conductor A is,
Flux linkage at point P for conductor A due to current through conductor A =

Flux linkage at point P for conductor A due to current through conductor B =
Flux linkage at point P for conductor A due to current through conductor C =
Therefore, flux linkage at point P for conductor A,

As,andin balanced system, then we can write that



If we arrange them in matrix form, then we get

Where, λA, λB, λC are the total flux linkages of conductor A, B and C.
LAA, LBB and LCC are the
self inductances of conductor A, B and C.
LAB, LAC, LBC, LBA, LCA, LCB are the
mutual inductances of between conductors A, B and C.

Again balanced system

And

In balanced system, then we can write that

Similarly,

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Solid insulation assistance combined with dry air insulation is a development direction for 24 kV ring main units. By balancing insulation performance and compactness, the use of solid auxiliary insulation allows passing insulation tests without significantly increasing phase-to-phase or phase-to-ground dimensions. Encapsulation of the pole can address the insulation of the vacuum interrupter and its connected conductors.For the 24 kV outgoing busbar, with the phase spacing maintained at 110 mm,
Dyson
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
What Is THD? How It Affects Power Quality & Equipment
What Is THD? How It Affects Power Quality & Equipment
In the field of electrical engineering, the stability and reliability of power systems are of paramount importance. With the advancement of power electronics technology, the widespread use of nonlinear loads has led to an increasingly serious problem of harmonic distortion in power systems.Definition of THDTotal Harmonic Distortion (THD) is defined as the ratio of the root mean square (RMS) value of all harmonic components to the RMS value of the fundamental component in a periodic signal. It is
Encyclopedia
11/01/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.