Why does inrush current occur in arc furnace transformers?

Echo
08/06/2025

Magnetizing inrush current in electric arc furnace transformers is a problem that troubles many electrical engineers. So, why does magnetizing inrush current occur in arc furnace transformers? First, let's understand what magnetizing inrush current is.

Magnetizing inrush current refers to the transient current generated in the secondary winding of an arc furnace transformer due to core saturation, increased magnetic field strength, and other factors. This phenomenon is very common during the operation of arc furnace transformers, especially during startup and shutdown of the furnace, when the magnitude of the inrush current changes abruptly, significantly affecting equipment operation.

The main causes of magnetizing inrush current include the following:

  • Core Saturation: When the current in the secondary winding of the arc furnace transformer increases, the magnetic flux in the core also increases. Once the flux exceeds the maximum magnetic induction limit of the core material, the core enters a saturated state. If the winding current continues to rise under saturation, the nonlinear increase in flux easily leads to magnetizing inrush current.
  • Increased Magnetic Field Strength: The secondary windings of arc furnace transformers are typically made of copper wire with low resistance. When the magnetic field strength increases rapidly, the current in the secondary winding rises sharply, making it prone to generating magnetizing inrush current.
  • Furnace Startup and Shutdown: During the startup or shutdown of the arc furnace, the current in the secondary winding changes abruptly, which can trigger magnetizing inrush current. Particularly during startup, the sudden surge in current may cause the inrush current to reach several or even dozens of times the normal operating current.

Magnetizing inrush current has several significant adverse effects on the operation of arc furnace transformers:

  • Equipment Heating: Inrush current causes rapid heat generation in the windings, affecting equipment performance and service life.
  • Equipment Vibration: The electromagnetic forces from high currents induce mechanical vibration in the windings, compromising operational stability.
  • Protection Misoperation: The peak inrush current may be mistaken by protective relays as a fault current, causing false tripping and interrupting normal operation.

To address these issues, it is essential to thoroughly analyze the root causes of magnetizing inrush current in arc furnace transformers and implement targeted suppression measures. Only then can inrush current be effectively prevented, ensuring safe and stable system operation.

Echo

As an expert in the application and trends of electrical equipment, I have a profound mastery of knowledge in circuits, power electronics, etc. I possess a comprehensive set of abilities including equipment design, fault diagnosis, and project management. I can precisely grasp the industry's pulse and lead the development of the electrical field.

Advantages of SF6 Fully Insulated Ring Main Units in Power Supply Systems
Advantages of SF6 Fully Insulated Ring Main Units in Power Supply Systems
Current Power Supply Method Using SF6 Ring Main UnitsTo enhance grid performance, the design of traditional SF6 ring main units (RMUs) has been further optimized. A key feature of second-generation SF6 RMUs is the use of a grounded, enclosed epoxy resin housing, with SF6 gas as the insulating medium. Two three-position load switches and one three-position arc-rotating circuit breaker are integrated into a single sealed unit, equipped with a pressure relief safety valve. In the event of arc-quenc
Echo
08/09/2025
Analysis of Interlocking Protection Circuit for Furnace Transformer
Analysis of Interlocking Protection Circuit for Furnace Transformer
Currently, the company operates two electric arc furnace (EAF) transformers. The secondary voltage ranges from 121 V to 260 V, with a rated current of 504 A / 12,213 A. The high-voltage side has a total of eight tap positions, utilizing motor-driven off-circuit voltage regulation. The equipment is equipped with a reactor of corresponding capacity, connected in series to designated taps on the high-voltage side. These transformers have been in operation for over 20 years. Throughout this period,
Dyson
08/07/2025
Analysis of the Causes of Light Gas Generation in Electric Furnace Transformers and Improvements
Analysis of the Causes of Light Gas Generation in Electric Furnace Transformers and Improvements
A 25 MVA electric arc furnace transformer at a certain company is an equipment imported from the former Soviet Union. It consists of three single-phase transformers, each rated at 8.333 MVA, with a connection group of D,d0. The primary voltage is 10 kV, and the secondary voltage ranges from 140 to 230.4 V. The tap-changing method is on-load tap changing with 21 steps (steps 11, 12, and 13 are combined as one step, totaling 23 positions). Each phase can be regulated independently, allowing separa
Felix Spark
08/06/2025
Why do arc furnace transformers and inrush currents cause voltage sags?
Why do arc furnace transformers and inrush currents cause voltage sags?
An electric arc furnace is a device that melts metal using the high temperature generated by an electric arc. It converts electrical energy into thermal energy through a transformer, then transfers the heat via the arc to the furnace charge, causing it to melt. When the arc furnace starts operating, the transformer load increases suddenly, leading to a drop in grid voltage. Additionally, due to the operational characteristics of the arc furnace, the load continues to rise over a period of time,
Leon
08/06/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!