• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Why Does Magnetizing Inrush Current Occur in Arc Furnace Transformers and Its Effects?

Echo
Field: Transformer Analysis
China

Magnetizing inrush current in electric arc furnace transformers is a problem that troubles many electrical engineers. So, why does magnetizing inrush current occur in arc furnace transformers? First, let's understand what magnetizing inrush current is.

Magnetizing inrush current refers to the transient current generated in the secondary winding of an arc furnace transformer due to core saturation, increased magnetic field strength, and other factors. This phenomenon is very common during the operation of arc furnace transformers, especially during startup and shutdown of the furnace, when the magnitude of the inrush current changes abruptly, significantly affecting equipment operation.

The main causes of magnetizing inrush current include the following:

  • Core Saturation: When the current in the secondary winding of the arc furnace transformer increases, the magnetic flux in the core also increases. Once the flux exceeds the maximum magnetic induction limit of the core material, the core enters a saturated state. If the winding current continues to rise under saturation, the nonlinear increase in flux easily leads to magnetizing inrush current.

  • Increased Magnetic Field Strength: The secondary windings of arc furnace transformers are typically made of copper wire with low resistance. When the magnetic field strength increases rapidly, the current in the secondary winding rises sharply, making it prone to generating magnetizing inrush current.

  • Furnace Startup and Shutdown: During the startup or shutdown of the arc furnace, the current in the secondary winding changes abruptly, which can trigger magnetizing inrush current. Particularly during startup, the sudden surge in current may cause the inrush current to reach several or even dozens of times the normal operating current.

Magnetizing inrush current has several significant adverse effects on the operation of arc furnace transformers:

  • Equipment Heating: Inrush current causes rapid heat generation in the windings, affecting equipment performance and service life.

  • Equipment Vibration: The electromagnetic forces from high currents induce mechanical vibration in the windings, compromising operational stability.

  • Protection Misoperation: The peak inrush current may be mistaken by protective relays as a fault current, causing false tripping and interrupting normal operation.

To address these issues, it is essential to thoroughly analyze the root causes of magnetizing inrush current in arc furnace transformers and implement targeted suppression measures. Only then can inrush current be effectively prevented, ensuring safe and stable system operation.

Give a tip and encourage the author!

Recommended

What’s the Difference Between Rectifier Transformers and Power Transformers?
What is a Rectifier Transformer?"Power conversion" is a general term encompassing rectification, inversion, and frequency conversion, with rectification being the most widely used among them. Rectifier equipment converts input AC power into DC output through rectification and filtering. A rectifier transformer serves as the power supply transformer for such rectifier equipment. In industrial applications, most DC power supplies are obtained by combining a rectifier transformer with rectifier equ
01/29/2026
How to Judge, Detect and Troubleshoot Transformer Core Faults
1. Hazards, Causes, and Types of Multi-Point Grounding Faults in Transformer Cores1.1 Hazards of Multi-Point Grounding Faults in the CoreUnder normal operation, a transformer core must be grounded at only one point. During operation, alternating magnetic fields surround the windings. Due to electromagnetic induction, parasitic capacitances exist between the high-voltage and low-voltage windings, between the low-voltage winding and the core, and between the core and the tank. The energized windin
01/27/2026
Analysis of Four Major Power Transformer Burnout Cases
Case OneOn August 1, 2016, a 50kVA distribution transformer at a power supply station suddenly sprayed oil during operation, followed by burning and destruction of the high-voltage fuse. Insulation testing revealed zero megohms from the low-voltage side to ground. Core inspection determined that damage to the low-voltage winding insulation had caused a short circuit. Analysis identified several primary causes for this transformer failure:Overloading: Load management has historically been a weak
12/23/2025
Power Transformer Condition Monitoring: Reducing Outages & Maintenance Costs
1. Definition of Condition-Based MaintenanceCondition-based maintenance refers to a maintenance approach where repair decisions are determined by the real-time operational status and health condition of equipment. There are no fixed schedules or predetermined maintenance dates. The prerequisite for condition-based maintenance is the establishment of equipment parameter monitoring systems and comprehensive analysis of various operational information, enabling reasonable maintenance decisions base
12/22/2025
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.