How to Identify Internal Faults in a Transformer?

Felix Spark
Felix Spark
Field: Failure and maintenance
China
  • Measure DC resistance: Use a bridge to measure the DC resistance of each high- and low-voltage winding. Check whether the resistance values among phases are balanced and consistent with the manufacturer’s original data. If phase resistance cannot be measured directly, line resistance may be measured instead. The DC resistance values can indicate whether the windings are intact, whether there are short circuits or open circuits, and whether the contact resistance of the tap changer is normal. If the DC resistance changes significantly after switching tap positions, the issue likely lies in the tap contact points rather than in the windings themselves. This test also verifies the quality of connections between bushing studs and leads, and between leads and windings.

  • Measure insulation resistance: Measure the insulation resistance between windings and between each winding and ground, as well as the polarization index (R60/R15). Based on these measured values, it is possible to determine whether the insulation of any winding has become damp, or whether there is a risk of breakdown or flashover between windings or to ground.

  • Measure dielectric loss factor (tan δ): Use a GY-type Schering bridge to measure the dielectric loss factor (tan δ) between windings and between windings and ground. The test results can indicate whether the winding insulation is damp or has undergone overall degradation.

  • Take an insulating oil sample for simplified testing: Use a flash point tester to check whether the flash point of the insulating oil has decreased. Inspect the oil for carbon particles, paper fibers, and note whether it has a burnt odor. If a gas chromatography analyzer is available, the gas content in the oil can be measured. These methods help identify the type and nature of internal faults.

  • No-load test: Perform a no-load test on the transformer to measure the three-phase no-load current and no-load power loss. These values help determine whether there are faults between the silicon steel laminations in the core, short circuits in the magnetic circuit, or short circuits within the windings.


Give a tip and encourage the author!
Recommended
UHV Transformer Production: Slow, Precise, Essential
UHV Transformer Production: Slow, Precise, Essential
1. Overview Ultra-high-voltage (UHV) transformers are core equipment in modern power systems. Understanding their voltage ratings, complex structure, precision manufacturing processes, and critical production techniques reveals why they represent the pinnacle of a nation’s power equipment manufacturing capability. Voltage Level DefinitionThe term "ultra-high-voltage transformer" typically refers to transformers used in AC transmission lines rated at 1,000 kV or higher, or DC transmission lines r
Echo
11/11/2025
What causes a transformer to be noisier under no-load conditions?
What causes a transformer to be noisier under no-load conditions?
When a transformer is operating under no-load conditions, it often produces louder noise than under full load. The primary reason is that, with no load on the secondary winding, the primary voltage tends to be slightly higher than nominal. For example, while the rated voltage is typically 10 kV, the actual no-load voltage may reach around 10.5 kV.This elevated voltage increases the magnetic flux density (B) in the core. According to the formula:B = 45 × Et / S(where Et is the designed volts-per-
Noah
11/05/2025
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
When installing an arc suppression coil, it is important to identify the conditions under which the coil should be taken out of service. The arc suppression coil should be disconnected under the following circumstances: When a transformer is being de-energized, the neutral-point disconnector must be opened first before performing any switching operations on the transformer. The energizing sequence is the reverse: the neutral-point disconnector should be closed only after the transformer is energ
Echo
11/05/2025
What fire prevention measures are available for power transformer failures?
What fire prevention measures are available for power transformer failures?
Failures in power transformers are commonly caused by severe overload operation, short circuits due to winding insulation degradation, aging of transformer oil, excessive contact resistance at connections or tap changers, failure of high- or low-voltage fuses to operate during external short circuits, core damage, internal arcing in oil, and lightning strikes.Since transformers are filled with insulating oil, fires can have severe consequences—ranging from oil spraying and ignition to, in extrem
Noah
11/05/2025