• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Case Analysis of Abnormal Secondary Circuits in Voltage Transformers

Felix Spark
Field: Failure and maintenance
China

1. Fault Situation

In September 2023, as a front - line fault maintenance worker, I detected abnormal voltage on the 10kV Section I bus of a substation during monitoring duty and informed the operation and maintenance team. The monitoring system showed: U0 = 0 kV, Ua = 6.06 kV, Ub = 5.93 kV, Uc = 6.05 kV, Uab = 10.05 kV, Ubc = 5.94 kV

My team and I rushed to the site. We suspected the secondary air circuit breaker of the 10kV Section I bus voltage transformer was closed and found the U - phase fuse blown. After disconnecting this breaker, the 900 bus - sectioning circuit breaker auto - activated, tripping the 95A breaker on the No. 1 main transformer’s 10kV side and inter - tripping lines 911–915, then closing 900.

After restoring the secondary circuit, we checked the voltage transformer’s main body and fuse (both normal). Inspecting the secondary circuit, I found a loose A660 terminal in the cabinet. Tightening it restored normal voltage on the 10kV Section I bus.

2. Cause Analysis

The 10kV Section I bus has 6 feeders, 5 (911–915) connected to small hydropower. At full generation, the No. 1 main transformer’s 10kV side load current drops, raising bus voltage.

Operation and maintenance staff, relying on experience, disconnected the voltage transformer’s secondary air circuit breaker without analyzing impacts on protection devices. At this point, the 95A breaker’s current (≈48A) met the auto - backup’s no - voltage/current condition (secondary value: 25V, 0.02A). The auto - backup activated, tripping the 95A breaker and inter - tripping the 5 small - hydropower feeders. The root cause was failing to exit auto - backup during voltage transformer abnormal handling, causing misoperation.

3. Preventive Measures

Capacitive voltage transformers have various faults, with abnormal secondary voltage output being common. Front - line operation and maintenance staff should:

  • Strengthen department management, collect more data, and monitor alarms to detect abnormalities early.

  • Analyze danger points in voltage transformer handling, update on - site operation regulations. Before replacing fuses (or similar tasks), check the main transformer’s current and auto - backup settings. If the current is below the no - current threshold, follow procedures to exit auto - backup.

  • Regularly revise measures for “three - mistake” (mis - operation, mis - wiring, mis - setting) accidents, conduct training. Standardize emergency disposal processes to avoid improper actions.

  • Enhance on - site risk control; clearly label equipment at risk of misoperation.

Give a tip and encourage the author!
Recommended
Ultimate Guide to AC Contactor Abnormal Noise: From Electromagnetic Noise to Mechanical Vibration, Accurate Diagnosis and Handling
In electrical control systems, AC contactors are among the commonly used electrical components, and they are also a common source of various electrical faults. After long-term use—especially in harsh environments with high levels of dust—AC contactors may sometimes emit squeaking or rattling noises after being pulled in and held. The causes of this phenomenon are analyzed as follows.Squeaking Noise After Pull-In and HoldingA fully functional AC contactor makes no noise when energized and pulled
Felix Spark
09/11/2025
Comprehensive Guide to High-Frequency Fault Handling of AC Contactors: 90% of Problems Solved with One Method
1. Fault Phenomena, Cause Analysis and Handling MethodsContactor does not operate or operates abnormally after coil energization Open circuit in coil control circuit; Check if there is wire breakage or loosening at the terminal blocks. If there is a wire breakage, replace the corresponding wire; if there is loosening, fasten the corresponding terminal block. Coil damage; Measure the coil resistance with a multimeter. If the resistance is ∞, replace the coil. Thermal relay not reset after operati
Felix Spark
09/11/2025
Application and Maintenance of AC Contactors | Comprehensive Analysis of Common Fault Handling, Master It in One Article
1 Analysis of Key Components of AC ContactorsAn AC contactor is an automated electromagnetic switch used for long-term, high-frequency switching of AC main circuits and control circuits. It features advantages such as automatic operation, under-voltage and no-voltage protection, high-capacity operation, strong stability, and low maintenance requirements. In the electrical control circuits of machine tools, AC contactors are mainly used to control electric motors and other loads.The key component
Felix Spark
09/11/2025
Dielectric Withstand Capability of AC Vacuum Contactors and Countermeasures
During operation, AC vacuum contactors are often subjected to various overvoltages such as lightning overvoltage and switching overvoltage. Therefore, AC vacuum contactors must have a certain voltage withstand capacity.An AC vacuum contactor is composed of a vacuum interrupter (its structure is shown in Figure 1), a housing, an electromagnetic system, a secondary circuit, and other components. Among these, the vacuum interrupter is the "heart" of the AC vacuum contactor, and its performance dire
Felix Spark
09/09/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.