| Brand | Switchgear parts |
| Model NO. | HXGN17-12 Series 11KV 630A Ring Main Unit |
| Rated voltage | 12kV |
| Rated normal current | 630A |
| Rated frequency | 50/60Hz |
| Series | HXGH17 |
The HXGN17-12 AC Metal-enclosed Ring Main Unit Switchgear (hereinafter referred to as "ring main unit") is a new product designed and developed by from oversea advanced latest techniques. The technical indicators of the product reaches standard of IEC62271-200 and GB3906. The product is characterized by small volume,light weight,operation flexibility,maintenance convenience, and quality stability & reliability, and it comes out with perfect interlock protection functions and IP3X protecton grade, so it is an ideal product for mains grid reconstruction. The product is mainly applicable to three-phase AC network for receiving and distributing energy.
Mainly applicable in urban power grid construction and renovation project. industrial and mining enterprises.high-rise buildings and communal facilities .For power distribution .controlling and protection on electric equipment as the loop power supply unit or termina equipment. It also can be installed in preloaded substation.
Working Environment
1.Altitude: Not exceed 2500m above sea level
2.Ambient temperature:-25℃ ~ +45℃, the highest temperature is not exceed25℃
3.Ambient humidity: Daily average RH ≤ 95%; Monthly average RH ≤ 90%
4.Earthquake intensity: ≤ 8°
5.No flammable, explosive, no serious pollution, No chemical corrosion and severe vibration.
Technical Parameters

|
No. |
Item |
Unit |
Data |
||
|
FN12-10 |
FZN25-12 |
||||
|
1 |
Rated voltage |
kV |
12 |
12 |
|
|
2 |
Rated current |
load break switchgear |
A |
630 |
630 |
|
Combined switchgear |
A |
125 |
125 |
||
|
3 |
Rated frequency |
Hz |
50 |
50 |
|
|
4 |
Rated short-circuit breaking current |
kA |
31.5 |
31.5 |
|
|
Rated short-time withstand current |
kA |
20 |
20 |
||
|
Rated active on-load breaking current |
A |
630 |
630 |
||
|
5 |
Rated peak withstand current |
kA |
50 |
50 |
|
|
6 |
Rated power frequency voltage withstands inter-phase, to earth and to the open contact |
kV |
42 |
48 |
|
|
7 |
Thundering withstands voltage inter-phase, to earth and to the open the contact |
kV |
75 |
85 |
|
|
8 |
Mechanical life |
times |
10000 |
10000 |
|
|
9 |
Rated take-over current |
A |
3150 |
3150 |
|
|
10 |
Protection level |
IP2X |
IP2X |
||
|
11 |
Operating mode |
Manual or automatic |
Manual or automatic |
||
|
12 |
Control circuit rated voltage |
V |
DC: 110, AC:220 |
DC: 110, AC:220 |
|