In-depth Solutions for Common Issues in SF6 Ring Main Units (RMUs)

Rockwill
17yrs 700++ staff 108000m²+m² US$150,000,000+ China

In-depth Solutions for Common Issues in SF6 Ring Main Units (RMUs)

The stable operation of SF6 high-voltage RMUs is critical to grid safety. Addressing typical problems exposed during long-term operation, and based on industry practices and technical specifications, the following systematic solutions are proposed:

I. Comprehensive Gas Leakage Management Plan

  • Phenomenon & Risk:
    • SF6 gas leakage reduces dielectric strength (breakdown voltage drops by over 30% when pressure falls below 0.4MPa).
    • Arc decomposition products (e.g., SF4, SOF2) pose a threat to personnel safety.
  • Proactive Defense System:

Countermeasure

Standard

Frequency / Method

Laser Imaging Leak Detection

DL/T 1145

Annual census + Special inspections after rain

Dual-Channel Density Relay Monitoring

IEC 62271

Real-time alarm threshold setting (0.55MPa at 20°C)

Complete Sealing Component Retrofit

GB/T 11023

Use fluororubber O-rings + metal bellows seals

Emergency Response Drills

Q/GDW 1799.2

Quarterly drills (including positive pressure breathing apparatus operation)

II. Strategy for Eradicating Mechanical Operation Failures

  • Failure Mechanisms:
    • Mechanism sticking/jamming (80% caused by lubricant hardening).
    • Micro-switch failure.
    • Operation refusal/maloperation caused by secondary wiring oxidation.
  • Precision Maintenance Plan:
    • Semi-Annual Maintenance:​ Encompasses two critical tasks: 1) Disassembly and refurbishment of the operating mechanism; 2) Coil resistance testing. These tasks enable timely assessment of the equipment's fundamental condition.
    • Intelligent Monitoring:​ Focuses on in-depth analysis of operational status, specifically including: 1) Analysis of open/close coil current waveforms; 2) Assessment of the energy storage motor status. This achieves precise control over equipment operation.
    • Preventive Testing:​ Utilizes specialized instruments to ensure test accuracy, employing mechanical characteristic testers and micro-ohm meters for contact resistance testing. This provides robust data support for safe and stable operation.

III. Insulation Degradation and Overheating Prevention & Control

  • Comprehensive Protective Measures:
    1. Insulation Refurbishment:
      • Apply moisture-proof RTV coating to epoxy barrel surfaces (withstands 40% higher voltage).
      • Replace porcelain bushings with silicone rubber bushings (impact resistance strength increased by 3 times).
    2. Thermal Management Upgrade:
      Heat Dissipation Power = 6.5×10⁻³×(T_cabinet - 25)³ // Optimization Measures:
  1. Install IP55 centrifugal fans at the cabinet top (ΔT reduced by 8℃).
  2. Silver plating treatment of copper busbars (contact resistance reduced by 35%).
  3. Embed heat pipe radiators into the contact assemblies.

IV. Construction of Intelligent Operation & Maintenance (O&M) System

Technology Module

Function Implementation

Benefit

UHF Partial Discharge (PD) Monitoring

Captures 300MHz-1.5GHz signals

Provides 3-month early warning for insulation defects

Pressure Cloud Map Analysis

Leakage prediction based on temperature compensation

Increases leak location efficiency by 70%+

Mechanical Life Assessment

Stress analysis based on cumulative switching operations

Achieves >90% mechanism failure prediction rate

Validation via Typical Case

After implementing this solution at a State Grid 220kV substation:
▶ Annual SF6 leakage rate dropped from 0.8% to ​0.05%.
▶ Number of mechanical failures decreased by ​82%​ (from ​2021 to 2023).
▶ Peak temperature rise reduced from ​75K to 48K​ (IEC 60298).

Key O&M Implementation Points

  1. Establish a full life-cycle equipment database (including spare parts life warnings).
  2. Promote live detection techniques to replace scheduled outage testing.
  3. Deepen the application of Condition-Based Maintenance (CBM) decision systems.
08/13/2025
Recommended
Solution for Medium-Voltage Motor Control and Protection Using Vacuum Contactor-Fuse (VCF) in a Coal Conveying System
Project BackgroundA coal conveying system comprises 15 belt conveyors driven by medium-voltage motors. The system operates under complex conditions, with motors often subjected to heavy loads and frequent starts. To address these challenges and achieve effective control and reliable protection during motor startup, the project comprehensively adopts Vacuum Contactor-Fuse (VCF) combination devices for the 6kV medium-voltage motor power distribution. This solution details the technical features,
ABB Vacuum Contactor KC2 Power Supply System Technical Transformation Plan
Issue Overview​The 10kV air compressor starting system of a company utilizes the ABB vacuum contactor KC2 as the control component for the operating circuit. The dedicated wide-voltage power supply module paired with this contactor presents the following issues:​Frequent failures: The power supply module fails to properly transition the voltage from 300V to 12V, resulting in fuse blowouts.​Poor heat dissipation: Enclosed installation of the module leads to insufficient heat dissipation, acceler
Dedicated Vacuum Contactor Solution for Port Shore Power Systems
I. Background and Challenges​Shore power systems have become core technical equipment for ports to reduce carbon emissions and noise pollution. However, these systems face two major challenges in the harsh operational environment of ports:​Severe Environmental Corrosion: High humidity and salt spray in port areas cause serious corrosion to metal components and enclosures of electrical equipment, significantly impacting electrical lifespan and operational reliability.​High Switching Requirements:
Vacuum Contactor Industrial Power Control Solutions
Application Background and Pain Point Analysis​In modern industrial manufacturing power control systems, traditional contactors exhibit significant limitations under specific operating conditions:• ​Frequent Start-Stop Operations: Traditional contactors have limited mechanical lifespan, with frequent operations leading to coil burnout and mechanical jamming.• ​Poor Adaptability to Harsh Environments: Contacts are prone to oxidation in dusty environments, resulting in increased contact
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.