• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


10kV SF₆ Ring Main Units (RMUs) Common Fault Prevention Measures

Rockwill
17yrs 700++ staff 108000m²+m² US$150,000,000+ China

10kV SF₆ Ring Main Units (RMUs) Common Fault Prevention Measures

During the development of urban distribution network cabling, 10kV SF₆ Ring Main Units (RMUs) (European-style), serving as ring power supply nodes, have been widely adopted due to their features such as full insulation, complete enclosure, maintenance-free operation, compact size, and flexible, convenient installation. However, as the number of RMUs in use increases, the occurrence of faults within RMUs has also gradually risen.

1 Common Faults

  • RMU Busbar Connection Faults:​ RMU expansion busbars mostly utilize plug-in silicone rubber connectors, fully insulated and shielded to ensure electrical conductivity reliability and resistance to surrounding environmental influences. They allow for arbitrary connection and combination based on actual needs. However, leakage of SF₆ gas, caused by various reasons, reduces the RMU's insulation level and arc-extinguishing capability, making busbar connection faults and insulation breakdowns still likely to occur.
  • Faults at the Junction between RMU and Three-Core Cable:​ During the installation of three-core cables, phase sequence verification is often necessary, requiring the application of external torsional force before fixing. After installation, the internal stress generated by this twisting gradually releases, creating a restoring torque acting on the bushings. This easily leads to bushing cracks, causing high-voltage short circuits.
  • Faults at the RMU Cable Termination:​ The cable compartment space in RMUs is relatively small, placing high demands on the cable termination manufacturing process. Inadequate handling of the conductor, semiconductor layer, or shielding layer can easily lead to cable breakdown due to insufficient creepage distance at the termination.

2 Prevention Measures

  • Securing Large Cross-Sectional Cables Entering the RMU:
    Three-core cables entering the RMU ​must be secured​ using cable clamps directly below the high-voltage bushings. Otherwise, the cable will exert twisting or pulling forces on the bushings. Sustained stress can damage the seal between the bushings and the cabinet, leading to SF₆ gas leakage, bushing cracks, and ultimately high-voltage short circuits.
    Ensure the vertical symmetry of the cable cores without twisting. The branch glove should be installed as low as possible, and the cable clamp position should also be as low as possible, with a ​minimum vertical distance of 750mm​ from the bushing.
    During construction, when feeding the cable from under the RMU foundation into the cable compartment, ​cut off​ the end of the cable damaged during pulling. Then, verify the phase sequence, correct the entry angle of the cable into the RMU to align the three cores with their respective bushings. If the cable entry angle is excessive, withdraw the cable back into the cable trench, adjust the angle, re-feed it into the RMU, and secure it with a cable clamp.
  • Cable Phase Separation and Termination:
    When performing phase separation, ​first secure the lower end of the cable branch glove​ with a cable clamp, and then trim the cable core lengths.
    Align the L2 core with the L2 bushing. Slightly bend the L1 and L3 cores outward from the root first, then align them vertically upwards with their bushings. Screw on the double-ended fixing bolt, temporarily hang the cable lug on the bushing, compare the cable length, and saw off any excess core. ​Ensure the three cable cores are of correct, equal length and flush​ to avoid stress on the bushings and poor contact between the cable lug and the bushing face.
    Failing to secure the cable before trimming the core lengths means there is no reference point, leading to errors. Therefore, securing the cable first is crucial.
    Pay attention to the following points during cable stripping:
    • Stripping dimensions ​must strictly follow​ the specifications provided by the cable T-body connector manufacturer and their accompanying process dimensions.
    • Extreme care must be taken​ when removing outer layers to avoid damaging inner layers.
    • Absolutely avoid​ longitudinal scratches on the core insulation to prevent internal creepage.
    • Always use​ the manufacturer's designated special cleaning wipes; avoid using alternatives like industrial alcohol.
    • For installation lubricant, ​it is recommended to use polyfluoropolyether (PFPE)​ grease products. These are non-reactive with silicone rubber, ensuring long-term sealing and insulation performance. ​Avoid using silicone-based greases, as mutual dissolution and drying with silicone rubber can create a risk of interfacial creepage.
  • Ensuring Proper Fit Between Stress Cone and Cable Cross-Section:
    The interference fit (overlap) must be appropriate. Excessive interference makes installation difficult and risks cracking the components. Insufficient interference compromises sealing and can lead to severe surface discharge.
    For cable T-body connectors, the stress cone, insulating outer sheath, and the cable itself have specific relative positioning requirements, offering less flexibility. Installation ​must be performed strictly according to the requirements​ (standards vary between manufacturers) to meet stress control and insulation sealing demands.
    Furthermore, during installation, ensure the stress cone body is positioned within the ​vertical section​ of the cable where possible, to guarantee the best sealing effect. ​Take special care to prevent sharp objects​ from scratching the inner or outer surfaces of silicone rubber stress cone components. Apply the designated installation lubricant ​evenly and separately​ to the contact surfaces forming the interference fit.
  • Installing Elbow Connectors:
    The conductor connection within cable elbow connectors is completed inside the insulated outer housing, making the contact condition difficult to observe and inconvenient to test. Therefore, ​it must be ensured​ that the lug face is ​parallel and in flush contact​ with the conductive face of the RMU bushing. This minimizes the stress exerted by the lug on the bushing while ensuring full, good contact to prevent heating during operation.
    The crimping of cable lugs onto wire cores ​must follow​ the installation procedure. ​Pay strict attention​ to the orientation of the lug face; it should be parallel to the copper face of the busbar bushing to ensure flush contact. When using a crimping tool, ​hold the dies closed for 10-15 seconds​ after reaching the full crimp position to allow the metal at the crimp to stabilize plastically. After crimping, use a file to smooth any burrs or sharp edges on the lug surface, then clean both the core insulation and the lug. Slide the cable lug onto the fixing stud, push the cable elbow connector into the bushing, and install it ensuring the lug face is ​in tight, flush contact​ with the copper face of the bushing.
08/13/2025
Recommended
Solution for Medium-Voltage Motor Control and Protection Using Vacuum Contactor-Fuse (VCF) in a Coal Conveying System
Project BackgroundA coal conveying system comprises 15 belt conveyors driven by medium-voltage motors. The system operates under complex conditions, with motors often subjected to heavy loads and frequent starts. To address these challenges and achieve effective control and reliable protection during motor startup, the project comprehensively adopts Vacuum Contactor-Fuse (VCF) combination devices for the 6kV medium-voltage motor power distribution. This solution details the technical features,
ABB Vacuum Contactor KC2 Power Supply System Technical Transformation Plan
Issue Overview​The 10kV air compressor starting system of a company utilizes the ABB vacuum contactor KC2 as the control component for the operating circuit. The dedicated wide-voltage power supply module paired with this contactor presents the following issues:​Frequent failures: The power supply module fails to properly transition the voltage from 300V to 12V, resulting in fuse blowouts.​Poor heat dissipation: Enclosed installation of the module leads to insufficient heat dissipation, acceler
Dedicated Vacuum Contactor Solution for Port Shore Power Systems
I. Background and Challenges​Shore power systems have become core technical equipment for ports to reduce carbon emissions and noise pollution. However, these systems face two major challenges in the harsh operational environment of ports:​Severe Environmental Corrosion: High humidity and salt spray in port areas cause serious corrosion to metal components and enclosures of electrical equipment, significantly impacting electrical lifespan and operational reliability.​High Switching Requirements:
Vacuum Contactor Industrial Power Control Solutions
Application Background and Pain Point Analysis​In modern industrial manufacturing power control systems, traditional contactors exhibit significant limitations under specific operating conditions:• ​Frequent Start-Stop Operations: Traditional contactors have limited mechanical lifespan, with frequent operations leading to coil burnout and mechanical jamming.• ​Poor Adaptability to Harsh Environments: Contacts are prone to oxidation in dusty environments, resulting in increased contact
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.