Common Methods for VFD Repair

RW Energy
13yrs + staff 30000+m² US$100,000,000+ China

  1. Preparation Before Repair
  1. Safety Measures
    • Power off the VFD and verify capacitor discharge is complete (use a multimeter to check DC bus voltage is below 36V).
    • Wear insulated gloves and safety goggles to prevent electric shock or component explosion.
  2. Tool Preparation
    • Multimeter, oscilloscope, LCR meter (bridge meter), insulation tester, screwdrivers, soldering station, etc.
  3. Fault Diagnosis
    • Check the fault code on the VFD display (e.g., Overcurrent (OC), Overvoltage (OV), Overheating (OH)).
    • Record fault phenomena (e.g., failure to start, unstable output, abnormal noise).

II. Common Faults and Repair Methods

  1. Power Supply Failure
    • Phenomenon: No display, cannot power on.
    • Possible Causes:
      • Input power phase loss or unstable voltage.
      • Damaged rectifier bridge, fuse, or filter capacitor.
    • Repair Steps:
      • Check if input power voltage is normal (380V/220V).
      • Use a multimeter to check if the rectifier bridge is shorted; replace damaged rectifier modules.
      • Inspect filter capacitors for bulging or leakage; replace failed capacitors.
  2. Overcurrent (OC Fault)​
    • Phenomenon: Frequent overcurrent alarms during operation.
    • Possible Causes:
      • Motor short circuit, poor insulation, or excessive load.
      • Faulty current detection circuit (e.g., damaged Hall sensor).
      • Drive circuit abnormality (damaged IGBT module).
    • Repair Steps:
      • Disconnect the motor and test the VFD under no-load conditions.
      • Check motor winding insulation resistance (using a megohmmeter).
      • Test IGBT module for short circuits (measure pin-to-pin resistance using the diode test function).
      • Inspect drive circuit components (opto-isolators, resistors, capacitors) for damage.
  3. Overvoltage (OV Fault)​
    • Phenomenon: Overvoltage alarm during deceleration.
    • Possible Causes:
      • Faulty braking resistor or braking unit.
      • Deceleration time setting too short, preventing regenerative energy release.
    • Repair Steps:
      • Check if braking resistance value is normal (infinite resistance if burnt out).
      • Extend deceleration time (via parameter adjustment).
      • Test if the braking unit triggers correctly.
  4. Overheating (OH Fault)​
    • Phenomenon: Overheating alarm after operating for some time.
    • Possible Causes:
      • Cooling fan jammed or damaged.
      • Excessive dust buildup on heat sink, poor ventilation.
      • Temperature sensor failure.
    • Repair Steps:
      • Clean the heat sink and air vents.
      • Test fan voltage; replace damaged fan if necessary.
      • Check temperature sensor resistance for abnormalities.
  5. Communication Fault
    • Phenomenon: Unable to communicate with PLC or host computer.
    • Possible Causes:
      • Poor contact at communication port connections.
      • Incorrect communication protocol or baud rate settings.
      • Damaged isolation chip (e.g., RS485 chip).
    • Repair Steps:
      • Check terminal connections for looseness or oxidation.
      • Verify parameter settings (e.g., Modbus address, baud rate).
      • Replace damaged communication chip.
  6. Parameter Setting Error
    • Phenomenon: Abnormal motor operation (e.g., reverse rotation, incorrect speed).
    • Repair Steps:
      • Restore factory settings and re-enter motor parameters (power, rated current, pole count, etc.).
      • Check if the starting method (e.g., V/F control, vector control) is appropriate.
  7. Hardware Damage
    • Common Vulnerable Components:
      • Capacitors: Aged filter capacitors causing reduced capacitance or leakage.
      • IGBT Modules: Shorted due to overcurrent or overheating.
      • Drive Circuit: Damaged opto-isolators or gate resistors.
    • Repair Methods:
      • Replace components with identical specifications; pay attention to soldering temperature and time.
      • Apply new thermal paste after module replacement to ensure proper heat dissipation.

III. Post-Repair Testing

  1. No-Load Test:​
    • Power on without motor connection; observe display and parameters for normalcy.
  2. Load Test:​
    • Connect motor; operate at low speed, gradually increase load; monitor output current and temperature.
  3. Extended Run Test:​
    • Operate continuously for 1-2 hours to confirm no abnormal alarms occur.

IV. Preventive Maintenance

  1. Periodically clean internal dust and inspect cooling fans.
  2. Tighten power and motor terminal connections to prevent poor contact.
  3. Test capacitor capacitance and insulation resistance every six months.
  4. Update VFD firmware (if newer versions are available).

V. Precautions

  • Safety First:​​ Working on live equipment is absolutely prohibited; capacitor discharge must be thorough.
  • Component Replacement:​​ IGBT modules must match the required voltage, current rating, and package type.
  • Professional Support:​​ For complex faults (e.g., chip-level repair), contact the manufacturer or a specialized service provider.

Through systematic troubleshooting and targeted repairs, most VFD faults can be effectively resolved. If problems persist, further analysis using circuit diagrams to trace signal flow and locate hidden faults is necessary.

08/21/2025
Recommended
Solution for Medium-Voltage Motor Control and Protection Using Vacuum Contactor-Fuse (VCF) in a Coal Conveying System
Project BackgroundA coal conveying system comprises 15 belt conveyors driven by medium-voltage motors. The system operates under complex conditions, with motors often subjected to heavy loads and frequent starts. To address these challenges and achieve effective control and reliable protection during motor startup, the project comprehensively adopts Vacuum Contactor-Fuse (VCF) combination devices for the 6kV medium-voltage motor power distribution. This solution details the technical features,
ABB Vacuum Contactor KC2 Power Supply System Technical Transformation Plan
Issue Overview​The 10kV air compressor starting system of a company utilizes the ABB vacuum contactor KC2 as the control component for the operating circuit. The dedicated wide-voltage power supply module paired with this contactor presents the following issues:​Frequent failures: The power supply module fails to properly transition the voltage from 300V to 12V, resulting in fuse blowouts.​Poor heat dissipation: Enclosed installation of the module leads to insufficient heat dissipation, acceler
Dedicated Vacuum Contactor Solution for Port Shore Power Systems
I. Background and Challenges​Shore power systems have become core technical equipment for ports to reduce carbon emissions and noise pollution. However, these systems face two major challenges in the harsh operational environment of ports:​Severe Environmental Corrosion: High humidity and salt spray in port areas cause serious corrosion to metal components and enclosures of electrical equipment, significantly impacting electrical lifespan and operational reliability.​High Switching Requirements:
Vacuum Contactor Industrial Power Control Solutions
Application Background and Pain Point Analysis​In modern industrial manufacturing power control systems, traditional contactors exhibit significant limitations under specific operating conditions:• ​Frequent Start-Stop Operations: Traditional contactors have limited mechanical lifespan, with frequent operations leading to coil burnout and mechanical jamming.• ​Poor Adaptability to Harsh Environments: Contacts are prone to oxidation in dusty environments, resulting in increased contact
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.