• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What Are the Factors Influencing the Impact of Lightning on 10kV Distribution Lines?

Echo
Echo
Field: Transformer Analysis
China

1. Induced Lightning Overvoltage

Induced lightning overvoltage refers to the transient overvoltage generated on overhead distribution lines due to nearby lightning discharges, even when the line is not directly struck. When a lightning flash occurs in the vicinity, it induces a large amount of charge on the conductors—opposite in polarity to the charge in the thundercloud.

Statistical data shows that lightning-related faults caused by induced overvoltages account for approximately 90% of total faults on distribution lines, making it the primary cause of outages in 10 kV distribution systems. Research indicates that if a 10 kV line is 10 meters above ground and lightning strikes 50 meters away, a lightning current of up to 100 kA can be induced. Without proper lightning protection, the resulting overvoltage may reach peak values as high as 500 kV. If the line’s insulation level is inadequate, this overvoltage can easily puncture or even shatter the insulation, leading to flashovers or conductor failure.

2. Insulation Level

Insulation failure, particularly due to insulator breakdown or explosion, is another major cause of distribution line faults. The performance of insulators directly determines the overall insulation strength of a 10 kV distribution line and thus significantly impacts system reliability.

Over long-term operation, insulators may degrade due to environmental pollution, moisture, aging, or mechanical stress. Without regular inspection, maintenance, or timely replacement, the insulation level of the entire line can deteriorate significantly. This degradation increases the likelihood of flashover under overvoltage conditions—especially during thunderstorms—further raising the risk of lightning-induced outages.

Therefore, routine inspection and maintenance of insulators are essential to ensure sustained insulation integrity and system safety.

3. Lightning Protection Installation

3.1 Transformer Protection

When lightning overvoltage reaches several times the rated voltage, it can easily puncture the insulation around the transformer’s neutral point. In most current installations in China, surge arresters are typically installed only on the high-voltage side of transformers, while protection on the low-voltage side remains inadequate.

Surge arresters can be installed either ahead of the main fuse or at the outgoing feeder side of the distribution line. During installation, the low-voltage terminal of the arrester must be properly grounded.

It is critical to note that the neutral conductor (N-line) downstream of a current-type protective device must not be repeatedly grounded. Otherwise, the protective device may fail to operate correctly, compromising the entire protection scheme. Therefore, the grounding lead of the low-voltage arrester should be connected to the primary terminal of the transformer’s neutral conductor, before any repeated grounding points.

3.2 Pole-Mounted Switches and Disconnectors

Installing pole-mounted circuit breakers and disconnect switches can greatly improve the reliability and safety of 10 kV distribution lines. However, in practice, many lines lack proper lightning protection for these critical devices. Without surge arresters installed on both sides of such switches, they are vulnerable to damage from lightning overvoltages, potentially leading to equipment failure and prolonged outages.

3.3 Surge Protection for Switchgear and Other Units

A 10 kV distribution system consists of multiple critical units, including switchgear, capacitor banks, and distribution panels. Surge arresters can be installed on every unit (comprehensive protection) or selectively on key units only.

While the former approach involves higher initial costs, it provides significantly higher reliability and system resilience. Selective installation reduces cost but may leave certain sections exposed. The choice should be based on risk assessment, criticality of load, and local lightning activity.

Give a tip and encourage the author!
Recommended
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Why is it difficult to increase the voltage level?
Why is it difficult to increase the voltage level?
The solid-state transformer (SST), also known as a power electronic transformer (PET), uses voltage level as a key indicator of its technological maturity and application scenarios. Currently, SSTs have reached voltage levels of 10 kV and 35 kV on the medium-voltage distribution side, while on the high-voltage transmission side, they remain in the stage of laboratory research and prototype validation. The table below clearly illustrates the current status of voltage levels across different appli
Echo
11/03/2025
Compact Air-Insulated RMUs for Retrofit & New Substations
Compact Air-Insulated RMUs for Retrofit & New Substations
Air-insulated ring main units (RMUs) are defined in contrast to compact gas-insulated RMUs. Early air-insulated RMUs used vacuum or puffer-type load switches from VEI, as well as gas-generating load switches. Later, with the widespread adoption of the SM6 series, it became the mainstream solution for air-insulated RMUs. Similar to other air-insulated RMUs, the key difference lies in replacing the load switch with an SF6-encapsulated type—where the three-position switch for load and grounding is
Echo
11/03/2025
Standards and Calculation of LTAC Test for Power Transformers
Standards and Calculation of LTAC Test for Power Transformers
1 IntroductionAccording to the provisions of the national standard GB/T 1094.3-2017, the primary purpose of the line terminal AC withstand voltage test (LTAC) for power transformers is to evaluate the AC dielectric strength from the high-voltage winding terminals to ground. It does not serve to assess inter-turn insulation or phase-to-phase insulation.Compared with other insulation tests (such as full lightning impulse LI or switching impulse SI), the LTAC test imposes a relatively more stringen
Oliver Watts
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.