• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Rockwill Smart Auto Recloser Quick Operation Guide

Rockwill
Rockwill
Field: Manufacturing
China

1. Local Quick Operation Procedure (On-site Panel)

Step 1: Open the Control Cabinet
Use the standard cabinet key to unlock the controller and open the door.

Step 2: Power Check and System Status

  • Ensure the controller is powered (battery level is sufficient or external AC/DC is connected).

  • Observe the LED indicators or HMI screen:

    • Breaker status (Open/Closed)

    • Fault or Lockout indicators

    • Communication and battery indicators

Step 3: Manually Open or Close the Recloser

  • To open (trip) the circuit: press the “OFF” button.

  • Wait for the LED or screen to confirm the recloser is open.

  • After clearing the fault, press the “ON” button to reclose.

Step 4: Switch Operation Mode

  • Use the mode selector switch or HMI setting to choose “Manual” or “Auto” mode.

  • In “Auto” mode, the recloser will automatically execute its reclosing logic after faults.

Step 5: Reset After Lockout (if applicable)

  • If a fault lockout has occurred, press the “RESET” button.

  • Confirm that lockout indicators are cleared before re-energizing.

2. Remote Quick Operation Procedure (Via SCADA/RTU)

Step 1: Confirm Connection
Ensure the recloser is communicating via SCADA using GPRS, 4G, or fiber. The remote interface (SCADA/DMS) must show online status.

Step 2: Send Remote Control Commands

  • Use the SCADA interface to issue “Open” or “Close” command.

  • Confirm that the recloser changes status and feedback is updated.

Step 3: Monitor Live Data

  • Observe real-time values such as current, voltage, fault alarms, and breaker position from the SCADA interface.

Step 4: Remote Reset (if available)

  • If lockout occurs and remote reset is enabled, send the “Reset” command.

  • Otherwise, reset must be performed locally.

3. Summary of Key Actions

  • To Open (Trip): Press “OFF” on HMI or send “Open” via SCADA

  • To Close (Reclose): Press “ON” on HMI or send “Close” via SCADA

  • To Switch Mode: Set the selector to “Auto” for automatic reclose, “Manual” for local control

  • To Reset Fault Lockout: Press “RESET” on HMI after fault clearance

  • To Monitor Status: Check HMI screen or SCADA dashboard for live breaker status and fault indicators

4. Important Notes

  • Always confirm the system is free from faults before reclosing.

  • In Auto mode, the recloser may automatically reclose based on configured time-delay sequences.

  • Ensure safety protocols and PPE are followed at all times.

  • Protection settings and reclosing sequences should be pre-configured using authorized software tools.

Give a tip and encourage the author!
Recommended
Causes of Failure in Off-Circuit (De-energized) Tap Changers
Causes of Failure in Off-Circuit (De-energized) Tap Changers
I. Faults in Off-Circuit (De-energized) Tap Changers1. Causes of Failure Insufficient spring pressure on tap changer contacts, uneven roller pressure reducing effective contact area, or inadequate mechanical strength of the silver-plated layer leading to severe wear—ultimately burning out the tap changer during operation. Poor contact at tap positions, or poor connections/welding of leads, unable to withstand short-circuit current surges. Incorrect tap position selection during switching, causin
Felix Spark
11/05/2025
What causes a transformer to be noisier under no-load conditions?
What causes a transformer to be noisier under no-load conditions?
When a transformer is operating under no-load conditions, it often produces louder noise than under full load. The primary reason is that, with no load on the secondary winding, the primary voltage tends to be slightly higher than nominal. For example, while the rated voltage is typically 10 kV, the actual no-load voltage may reach around 10.5 kV.This elevated voltage increases the magnetic flux density (B) in the core. According to the formula:B = 45 × Et / S(where Et is the designed volts-per-
Noah
11/05/2025
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
When installing an arc suppression coil, it is important to identify the conditions under which the coil should be taken out of service. The arc suppression coil should be disconnected under the following circumstances: When a transformer is being de-energized, the neutral-point disconnector must be opened first before performing any switching operations on the transformer. The energizing sequence is the reverse: the neutral-point disconnector should be closed only after the transformer is energ
Echo
11/05/2025
What fire prevention measures are available for power transformer failures?
What fire prevention measures are available for power transformer failures?
Failures in power transformers are commonly caused by severe overload operation, short circuits due to winding insulation degradation, aging of transformer oil, excessive contact resistance at connections or tap changers, failure of high- or low-voltage fuses to operate during external short circuits, core damage, internal arcing in oil, and lightning strikes.Since transformers are filled with insulating oil, fires can have severe consequences—ranging from oil spraying and ignition to, in extrem
Noah
11/05/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.