A Quick Verification Method for Low-Voltage Current Transformers

Oliver Watts
07/16/2025

To ensure safe operation of the power system, power equipment operation must be monitored/measured. General devices can’t connect to primary high - voltage equipment directly; instead, large primary currents are scaled down for current transformation, electrical isolation, and use by measurement/protection devices. For AC large - current measurement, conversion to a unified current eases secondary instrument use.
Current transformers split into measurement - and protection - type, with accuracy levels based on usage. 0.2S - rated ones serve for metering (billing) and current measurement. Their accuracy impacts power companies’ billing, so each metering transformer needs verification.
Low - voltage transformers (1kV >, 36V < AC) come in types like LMZ (LMZJ), LMK (BH), SDH, LQX, etc. Commonly used for 0.4kV, with accuracies (0.5, 0.5S, 0.2, 0.2S) and primary inputs (20–6000A, secondary outputs 1A/5A).
Many low - voltage branches in power systems mean numerous current transformers, with varied models/ratios. Regulations require verification before on - site installation, making work complex. Improving efficiency is key. This paper proposes a fast verification wiring method, enhancing efficiency based on conventional low - voltage current transformer verification analysis.
1. Verification of Low - voltage Current Transformers
Per “JJG313 - 2010 Verification Regulation for Measuring Current Transformers”, verification items include:
  • Visual inspection: Check nameplates, markings, terminals, polarity, multi - ratio wiring, and critical defects.
  • Insulation resistance test: Measure insulation to prevent leaks/short - circuits.
  • Power frequency withstand voltage test: Apply high voltage (exceeding rated) to test insulation for 1 minute, detecting concentrated defects.
  • Demagnetization: Remove residual magnetism in ferromagnetic materials post - magnetization.
  • Winding polarity check: Ensure secondary current direction matches primary, using a calibrator.
  • Basic error measurement (ratio/angle errors): Select standards per accuracy, follow wiring rules:
    • a) Define L1 (primary) and K1 (secondary) as same - name terminals.
    • b) Connect same - name primary terminals of standard and DUT; ground/indirectly ground current booster output.
    • c) Connect same - name secondary terminals to calibrator’s K (near ground, not direct).
    • d) Link K2 of standard/DUT to calibrator’s T0 (standard) and TX (test).
    • e) Attach load to DUT’s secondary.
  • Stability test: Compare current/previous results; ratio/phase differences ≤ 2/3 of basic error limits.
Key items (basic error, stability) reflect transformers’ measurement traits. Verification wiring is vital but cumbersome—different wires/terminals (fixed by nuts, matched to transformers, as in Figure 1) take much time, reducing efficiency.
2. Improvement of Verification Wiring
Traditional primary wires have drawbacks: verifying transformers with different ratios requires frequent primary wire replacements (to ensure accuracy), which is cumbersome and reduces efficiency. For example, testing the LDF1 - 0.66 low - voltage anti - theft current transformer (small aperture) causes issues as the primary wire can’t pass through the core.
Key inefficiencies: 1) Many transformer types/ratios, varying primary core diameters. 2) Diverse primary rated currents/core sizes demand soft wires with different cross - sections and terminals. 3) Nut - screwed terminals add complexity.
Soft wires require matching terminals, causing messy wiring. Thus, copper rods replace soft wires—they offer good conductivity, sufficient strength, and simplify connections. Using workbench clamps and a rocker for fixation streamlines primary wiring, cutting time and boosting efficiency.
3. Comparative Analysis of Verification Data
To verify the effectiveness of the copper rod wiring verification method, the conventional primary test line and copper rod wiring are respectively used to verify the same current transformer (model: LMZ1 - 0.5, transformation ratio: 150/5, class: 0.2S, rated burden: 5VA, factory number: 200000203). The key error data such as ratio difference and angle difference are shown in Tables 1 and 2.
By comparing the error data in Tables 1 and 2, it can be seen that the errors of both verification methods meet the requirements of the verification regulations, and the error curves are good. The wiring method does not affect the verification error data or the verification conclusion. Through sufficient and repeated tests, the effectiveness of the copper rod verification wiring method is verified.
4. Conclusion
This paper proposes a fast verification wiring method for low - voltage current transformers. A copper rod is used to replace the primary test line, making the wiring simple and convenient. The error data of the two wiring verification methods are compared and analyzed. Through repeated tests, the error curves are good and do not affect the verification data. This method improves work efficiency and avoids difficulties in verification.
Oliver Watts

Hey! I'm Oliver Watts, an electrical engineer in Inspection and Testing. With years of hands - on experience, I ensure electrical systems meet top safety and performance standards. Using advanced gear, I conduct diverse tests, easily spotting issues in both large - scale industrial and small - scale commercial setups. I love teaming up, sharing knowledge, and keeping up with industry regs. Also, I'm skilled at data analysis with software. If you're into electrical inspection or just want to chat engineering, reach out. Let's connect and explore!

Research on the Withstand Voltage Test Method for UHV Oil - immersed Reactors
Research on the Withstand Voltage Test Method for UHV Oil - immersed Reactors
1 Investigation of Insulation Defects in UHV Oil - immersed ReactorsKey challenges in high - voltage oil - filled reactors during operation include insulation faults, iron - core magnetic leakage heating, vibration/noise, and oil leakage.1.1 Insulation FaultsParallel - connected reactors, once connected to the main grid’s primary coil and put into use, operate at full power long - term. Sustained high voltage raises operating temperatures, accelerating aging of coil insulation materials an
Oliver Watts
07/24/2025
Research on the Evaluation Method of Uncertainty in the Verification and Measurement Results of Electronic Voltage Transformers in Power Grids
Research on the Evaluation Method of Uncertainty in the Verification and Measurement Results of Electronic Voltage Transformers in Power Grids
1. IntroductionGrid electronic voltage transformers, as indispensable measuring components in power systems, have their measurement accuracy directly tied to the stable operation and efficient management of power systems. However, in practice, due to the inherent characteristics of electronic components, environmental factors, and limitations of measurement methods, the measurement results of voltage transformers often involve uncertainty. This uncertainty not only impacts the accuracy of power
Oliver Watts
07/24/2025
Research on Calibration Technology and Application of DC Electronic Current Transformers
Research on Calibration Technology and Application of DC Electronic Current Transformers
In modern power systems, DC electronic current transformers play a crucial role. They are not only used for high-precision current measurement but also serve as key tools for grid optimization, fault detection, and energy management. With the rapid development of high-voltage direct current (HVDC) transmission technology and its widespread deployment globally, the performance requirements for DC current transformers have become increasingly stringent, especially in terms of measurement accuracy
Echo
07/23/2025
Test of 10 kV Electronic Current Transformer
Test of 10 kV Electronic Current Transformer
1 Performance AdvantagesIn recent years, electronic current transformers (ECTs) have emerged as a key industry trend. National standards classify them into two types: Active Optical Current Transformers (AOCTs, active hybrid type) and Optical Current Transformers (OCTs, passive optical type). Active hybrid ECTs use low-power electromagnetic transformers and Rogowski coils as core sensing elements (Figure 1).Rogowski coils outperform traditional sensors with non-saturation and wide dynamic ranges
Oliver Watts
07/22/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!