• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Lightning Protection for Distribution Transformers: Arrester Installation Position Analysis

James
Field: Electrical Operations
China

Lightning Protection for Distribution Transformers: Arrester Installation Position Analysis

In China's economic development, the power system holds an extremely important position. Transformers, as devices utilizing electromagnetic induction to convert AC voltage and current, represent a crucial component of the power system. Lightning damage to distribution transformers is quite common, particularly significant in humid tropical areas with frequent lightning activity. A research team has proposed that Y/Z0 connected distribution transformers demonstrate better lightning protection performance than Y/Y0 connected transformers.

Y/Z0 transformers are therefore more suitable for lightning-prone regions. Consequently, lightning protection for distribution transformers should not solely rely on arresters installed on the high-voltage side; protective measures on the low-voltage side must also be strengthened. Installing a set of FYS-0.22 zinc oxide low-voltage arresters on the low-voltage side is an effective method to prevent lightning waves from intruding along low-voltage power lines. This article discusses the installation position of arresters on the high-voltage side of distribution transformers, aiming to enhance the professional knowledge of electrical design engineers.

Problem Description and Impacts: In high-voltage distribution system diagrams, the installation position of surge arresters on the high-voltage side of distribution transformers with Yyn0 or Dyn11 connections is often improper, as shown in Figure (a), rendering them ineffective in protecting the transformer's high-voltage winding.

Incorrect Installation Position.jpg

Incorrect Installation Position.jpg

Cause Analysis:

The misunderstanding stems from the requirement that "lightning arresters shall be installed on the high-voltage side of distribution transformers with Yyn0 or Dyn11 connections when located inside a building or attached to its exterior wall." In reality, when "distribution transformers with Yyn0 or Dyn11 connections are installed within a building or attached to its exterior wall," a lightning strike to the building's lightning protection system causes potential rise in the grounding system, which consequently raises the potential of the transformer enclosure.

Since the phase windings on the transformer's high-voltage side are interconnected, they can be considered at the same low potential relative to the high lightning-induced potential on the enclosure. This high potential on the enclosure may break down the insulation of the high-voltage windings. Therefore, arresters must be installed on the high-voltage side. When the arrester flashes over, the high-voltage windings will be at a potential close to that of the enclosure, thus protecting the windings (excerpted from explanatory notes of clause 5, section 4.3.8 of the Code for Design Protection of Structures Against Lightning GB50057-2010).

Distribution Transformers...jpg

Article 5.5.1 of the Design Code for Overvoltage Protection and Insulation Coordination of AC Electrical Installations GB/T50064-2014 also stipulates: "Metal oxide arresters (MOAs) shall be installed close to the transformer on the high-voltage side of distribution transformers in 10~35kV distribution systems. The grounding conductor of this MOA shall be connected together with the transformer metal enclosure for common grounding."

Corrective Measures:

In high-voltage distribution system diagrams, lightning arresters for distribution transformers with Yyn0 or Dyn11 connections should be installed between the transformer's high-voltage side and the last-stage isolating switch.

Give a tip and encourage the author!
Recommended
How to Test Insulation Resistance of Distribution Transformers
In practical work, insulation resistance of distribution transformers is generally measured twice: the insulation resistance between thehigh-voltage (HV) windingand thelow-voltage (LV) winding plus the transformer tank, and the insulation resistance between theLV windingand theHV winding plus the transformer tank.If both measurements yield acceptable values, it indicates that the insulation among the HV winding, LV winding, and transformer tank is qualified. If either measurement fails, pairwise
12/25/2025
Design Principles for Pole-Mounted Distribution Transformers
Design Principles for Pole-Mounted Distribution Transformers(1) Location and Layout PrinciplesPole-mounted transformer platforms should be located near the load center or close to critical loads, following the principle of “small capacity, multiple locations” to facilitate equipment replacement and maintenance. For residential power supply, three-phase transformers may be installed nearby based on current demand and future growth projections.(2) Capacity Selection for Three-Phase Pole-Mounted Tr
12/25/2025
Analysis of Common Faults and Causes in Routine Inspection of Distribution Transformers
Common Faults and Causes in Routine Inspection of Distribution TransformersAs the terminal component of power transmission and distribution systems, distribution transformers play a critical role in supplying reliable electricity to end users. However, many users have limited knowledge of power equipment, and routine maintenance is often carried out without professional support. If any of the following conditions are observed during transformer operation, immediate action should be taken: Excess
12/24/2025
Analysis of Lightning Protection Measures for Distribution Transformers
Analysis of Lightning Protection Measures for Distribution TransformersTo prevent lightning surge intrusion and ensure the safe operation of distribution transformers, this paper presents applicable lightning protection measures that can effectively enhance their lightning withstand capability.1. Lightning Protection Measures for Distribution Transformers1.1 Install surge arresters on the high-voltage (HV) side of the distribution transformer.According to SDJ7–79 Technical Code for Overvol
12/24/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.