• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What is a Transformer Tap?

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

What is a Transformer Tap?



Transformer tap definition


The transformer tap refers to a number of connection points set on the winding of the transformer, allowing the transformer ratio (voltage ratio) to be adjusted by changing the number of effective turns of the winding, so as to achieve the regulation of the output voltage. The use of transformer taps can greatly improve the flexibility and reliability of the power system, especially when voltage levels need to be adjusted or in response to load changes.


Tap action


Voltage regulation


  •  Adjusting the output voltage: By changing the ratio of the transformer, the output voltage can be adjusted to keep it at a desired level. This is very important for voltage control in the grid, especially in the case of large load changes or grid voltage fluctuations.



  • No-load regulation: The tap position is adjusted when the transformer is not loaded, which is suitable for situations where frequent regulation is not required.



  • On-load voltage regulation: allows the tap position to be adjusted when the transformer is loaded, which is suitable for frequent voltage regulation.


Load matching


Adapt to load changes: By adjusting the transformer ratio, the load demand can be better matched to ensure the stability and reliability of the power supply.


Fault protection


  • Overvoltage protection: When the power grid voltage is too high, the output voltage can be reduced by adjusting the tap to protect downstream devices from overvoltage.



  • Overload protection: When the load is too large, the current can be reduced by adjusting the tap to avoid the overload of the transformer.


System equilibrium


Balanced voltage distribution: When multiple transformers are running in parallel, the voltage distribution between the transformers can be balanced by adjusting the tap to ensure the stability of the system operation.


Economic operation


Energy-saving operation: By adjusting the tap, the operation state of the transformer can be optimized, the energy loss can be reduced, and the economy of the system can be improved.


Tap position


Taps are usually set on the high voltage side winding of the transformer, because the high voltage side of the current is smaller, it is easier to achieve the switch of taps. In some special cases, taps may also be installed on the low pressure side.


Types of taps


According to different use occasions and needs, taps can have different types:


  • Fixed tap: The position has been set at the time of manufacturing, and cannot be adjusted.



  • Adjustable tap: Allows the position to be adjusted on the fly to suit different operating requirements.



  • Load regulator tap: can be adjusted with load, suitable for frequent adjustment.



  • No load regulator tap: can only be adjusted when the load is disconnected, suitable for situations that do not require frequent adjustment.


Tap switching device


In order to achieve the switching of taps, special switching devices need to be used, common are:


  • Tap changer: It is used to switch the tap position during the operation of the transformer, which is divided into no-load tap changer and on-load tap changer.



  • Switching switch: Used to manually or automatically switch the tap position in the state of power failure.


Application scenario


Transformer taps are widely used in all aspects of power systems:


  • Power transmission: In long-distance transmission, the line voltage drop is compensated by adjusting the tap to ensure that the end voltage is stable.



  • Distribution network: In the urban distribution network, the tap is adjusted to cope with load changes in different periods of time to maintain voltage stability.


  • Industrial applications: In industrial electrical equipment, the tap is adjusted to meet the voltage requirements under different load conditions.


Give a tip and encourage the author!
Recommended
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
When installing an arc suppression coil, it is important to identify the conditions under which the coil should be taken out of service. The arc suppression coil should be disconnected under the following circumstances: When a transformer is being de-energized, the neutral-point disconnector must be opened first before performing any switching operations on the transformer. The energizing sequence is the reverse: the neutral-point disconnector should be closed only after the transformer is energ
Echo
11/05/2025
What fire prevention measures are available for power transformer failures?
What fire prevention measures are available for power transformer failures?
Failures in power transformers are commonly caused by severe overload operation, short circuits due to winding insulation degradation, aging of transformer oil, excessive contact resistance at connections or tap changers, failure of high- or low-voltage fuses to operate during external short circuits, core damage, internal arcing in oil, and lightning strikes.Since transformers are filled with insulating oil, fires can have severe consequences—ranging from oil spraying and ignition to, in extrem
Noah
11/05/2025
What are the common faults encountered during the operation of power transformer longitudinal differential protection?
What are the common faults encountered during the operation of power transformer longitudinal differential protection?
Transformer Longitudinal Differential Protection: Common Issues and SolutionsTransformer longitudinal differential protection is the most complex among all component differential protections. Misoperations occasionally occur during operation. According to 1997 statistics from the North China Power Grid for transformers rated 220 kV and above, there were 18 incorrect operations in total, of which 5 were due to longitudinal differential protection—accounting for approximately one-third. Causes of
Felix Spark
11/05/2025
How to Identify Internal Faults in a Transformer?
How to Identify Internal Faults in a Transformer?
Measure DC resistance: Use a bridge to measure the DC resistance of each high- and low-voltage winding. Check whether the resistance values among phases are balanced and consistent with the manufacturer’s original data. If phase resistance cannot be measured directly, line resistance may be measured instead. The DC resistance values can indicate whether the windings are intact, whether there are short circuits or open circuits, and whether the contact resistance of the tap changer is normal. If
Felix Spark
11/04/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.