• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Reliability Analysis of Fault Current Limiters in High-Voltage Substations

Oliver Watts
Field: Inspection and testing
China

1 Introduction

To meet the rapidly growing demand for electric energy, power generation, transmission, and distribution systems must develop accordingly. One of the critical issues arising from this development is the rapid increase in short-circuit currents. The rise in short-circuit currents leads to several hazards:

  • overheating of series-connected devices along the fault path;
  • increased transient and recovery voltages during current interruption, which may damage insulation systems;
  • generation of extremely high mechanical forces in coil-based equipment (e.g., transformers, generators, reactors);
  • potential system instability depending on the magnitude and clearing time of the fault current;
  • existing circuit breakers may no longer be capable of interrupting the increased fault current, necessitating costly replacements in time and money; to avoid such expenses, parallel power transformers may be limited or system interconnectivity reduced, which compromises transmission capacity and system reliability;
  • increased fault currents prolong corrective actions, leading to longer outage durations and greater economic losses;
  • reduced grid reliability.

Currently, three main solutions are available to mitigate these effects:

  • constructing grid structures with minimal fault probability;
  • using circuit breakers with higher interrupting capacity or replacing weaker breakers with more capable ones;
  • modifying the grid to reduce short-circuit levels. A combination of these solutions is typically employed to achieve optimal network design while maintaining system reliability within acceptable limits. However, the possibility of faults can never be entirely eliminated, and designing power equipment based on ever-increasing short-circuit currents is commercially impractical. The third solution can be further divided into:
    • reducing system interconnectivity (e.g., bus splitting);
    • applying fault current limiters (FCLs).

Replacing circuit breakers with higher interrupting capacity is a costly solution and may not be feasible in certain cases. Moreover, protection systems exhibit delays in fault detection based on relay specifications. Circuit breaker operation and arc extinction are not instantaneous, typically requiring 3–5 cycles to fully clear a fault. Consequently, fault currents usually cannot be interrupted within the first 2–8 cycles after a fault occurs. During this period, very high currents flow through series devices in the fault path, and even this brief duration can be destructive, especially during the first cycle when the DC component of the fault current is particularly high.

Bus splitting and reduced system interconnectivity can be considered as alternatives to address this issue. However, they introduce other operational challenges, such as reduced transmission capacity, altered power flow, and increased losses. The need for FCLs arises from the necessity to protect costly and vulnerable equipment. Generally, all proposed FCL strategies are based on inserting high impedance into the series path during a fault, differing only in implementation. The desired characteristics of an ideal FCL are typically:

  • very low impedance under normal power system conditions;
  • insertion of high impedance during a fault;
  • fast operation to limit the DC component of the fault current;
  • capability for multiple operations within a short time and self-recovery;
  • no introduction of harmonics into the power system;
  • minimization of transient overvoltages;
  • high reliability.

2 Reliability of Fault Current Limiters

The application of FCLs in substations is generally motivated by two main reasons:

  • avoiding the expensive solution of replacing installed circuit breakers with ones having higher short-circuit capacity;
  • maintaining substation topology and avoiding bus splitting due to operational or reliability issues. Currently, no reliable sources or references on the reliability characteristics of FCLs are available; thus, in this study, we aim to analyze this issue by considering technical characteristics. Some FCLs employ highly complex technologies, which may reduce their reliability.

There are various types of FCLs, among which resonant-type and superconducting FCLs are more prominent.

A. Resonant-Type FCLs

Numerous configurations for resonant-type FCLs have been proposed. They are generally classified as series resonant-type and parallel resonant-type FCLs. Resonant-type FCLs possess several favorable characteristics for fault limitation, including:

  • Operation without current interruption;
  • Fast response to faults;
  • Ability to carry short-circuit current during fault duration;
  • Reset capability.

However, resonant-type FCLs typically consist of multiple components, and the overall reliability depends on the correct operation of each component. Additionally, some resonant-type FCLs require an external triggering device, meaning extra components are needed to sense the short circuit and initiate triggering. This increases system complexity and reduces reliability. Therefore, self-triggered FCLs are evidently more reliable.

B. Superconducting FCLs

Compared to resonant-type FCLs, superconducting FCLs require fewer components and are self-triggered. The fault current limiting strategy is simple and based on the natural behavior of superconducting materials. Superconductivity exists only at very low temperatures, so superconducting FCLs require additional cooling equipment, increasing investment costs. The concept proposed in this paper is limited to evaluating the impact of FCL application on substation reliability.

3 Failure Modes of FCLs

Like other components in high-voltage substations, FCLs exhibit different failure modes that should be considered when assessing the reliability of transmission substations incorporating FCLs. This section compares the failure rates of different types of FCLs.

There is a fundamental relationship between the reliability of a complete system and the number of its subsystems, all of which must operate correctly to achieve the desired overall function.

  • A. Active failure modes
  • B. Passive failure modes
  • C. Fixed failure modes

Clearly, FCLs requiring a triggering system (externally triggered FCLs) have higher failure rates. In general, any FCL involving triggering or commutation involves sequential operations of multiple switching devices, requiring precise synchronization and coordination, significantly increasing complexity compared to conventional circuit breakers.

In resonant-type FCLs (both externally and self-triggered), fixed failure modes may arise due to variations in resonant element characteristics caused by changes in operating conditions such as temperature, or operation under non-rated conditions.

Superconducting FCLs only exhibit such failure modes under excessive cooling, which rarely occurs. Thus, it can be said that superconducting FCLs essentially do not have this failure mode. In most cases, superconducting FCLs can be designed with predictable parameters and withstand thousands of activation and recovery cycles. Furthermore, using smaller FCLs instead of larger ones can improve both reliability and current-limiting capability. Table 1 briefly compares the occurrence rates of different failure modes across various FCL types.

4 Practical Application

A sample substation shown in Fig. 1 is used to evaluate the impact of implementing FCLs on substation reliability. It is well known that during maintenance, using bus-sectioning circuit breakers to manage protection schemes and enhance the flexibility of substation configurations is common practice. When the fault current level in a substation exceeds the interrupting capacity of the circuit breakers, replacing the bus-sectioning breaker with an FCL becomes a viable solution. Indeed, Inter-Bus FCL is one of the most common applications of FCLs.

Assume that all loads connected to the 330 kV bus are identical. The reliability assessment focuses on Load 1 at the left 330 kV bus and Load 5 at the right 330 kV bus. Load reliability is evaluated using the following indices: (1) Load loss probability (%); (2) Annual outage time (U). The 330 kV bus is assumed to be fully reliable. To avoid unnecessary calculations, failure modes involving the simultaneous failure of more than three components are not considered. Since the occurrence rate of such failure modes is very low, this assumption does not introduce significant error.

Table 2 shows the failure rates and repair times of the components. For the initial analysis, we start by calculating the reliability indices associated with the left 330 kV bus. To make an informed and comprehensive comparison, theoretically, we should calculate the reliability indices for all load points from L1 to L7. However, given that these loads are similar and connected to the same bus, they will have similar failure modes. Therefore, we only need to calculate the reliability indices for Load Point 1 (L1) on the left bus and Load Point 5 (L5) on the right bus.

As mentioned above, two probabilistic indices are used for the analysis: load loss probability (in f/yr) and annual outage time (in hours/year, A). These indices are evaluated for the case of a single component failure.

For the case of simultaneous failure of two components, the equivalent failure rate (λₑ), average outage duration (r), and annual outage time (u) are expressed as follows:

For the case of simultaneous failure at three levels, it is expressed as follows:

Considering all failure modes, the total failure rate and the total annual outage time can be calculated as follows:

Table 3 shows the reliability analysis results for the loads.

Now, the same calculation is performed for the feeders on the other 230 kV bus. Table 4 shows the results related to load point LS.

5 Conclusion

This paper presents the application of fault current limiters (FCLs) in enhancing substation reliability, describes the mathematical model and procedure for reliability calculation, and evaluates the impact of FCL implementation on substation reliability. The results indicate that substation reliability is improved by employing FCLs. A sensitivity analysis is also conducted to examine the influence of various parameters—such as the active failure rate, passive failure rate, and repair time of the FCL—on the reliability indices.

Give a tip and encourage the author!
Recommended
Ultimate Guide to AC Contactor Abnormal Noise: From Electromagnetic Noise to Mechanical Vibration, Accurate Diagnosis and Handling
In electrical control systems, AC contactors are among the commonly used electrical components, and they are also a common source of various electrical faults. After long-term use—especially in harsh environments with high levels of dust—AC contactors may sometimes emit squeaking or rattling noises after being pulled in and held. The causes of this phenomenon are analyzed as follows.Squeaking Noise After Pull-In and HoldingA fully functional AC contactor makes no noise when energized and pulled
Felix Spark
09/11/2025
Comprehensive Guide to High-Frequency Fault Handling of AC Contactors: 90% of Problems Solved with One Method
1. Fault Phenomena, Cause Analysis and Handling MethodsContactor does not operate or operates abnormally after coil energization Open circuit in coil control circuit; Check if there is wire breakage or loosening at the terminal blocks. If there is a wire breakage, replace the corresponding wire; if there is loosening, fasten the corresponding terminal block. Coil damage; Measure the coil resistance with a multimeter. If the resistance is ∞, replace the coil. Thermal relay not reset after operati
Felix Spark
09/11/2025
Application and Maintenance of AC Contactors | Comprehensive Analysis of Common Fault Handling, Master It in One Article
1 Analysis of Key Components of AC ContactorsAn AC contactor is an automated electromagnetic switch used for long-term, high-frequency switching of AC main circuits and control circuits. It features advantages such as automatic operation, under-voltage and no-voltage protection, high-capacity operation, strong stability, and low maintenance requirements. In the electrical control circuits of machine tools, AC contactors are mainly used to control electric motors and other loads.The key component
Felix Spark
09/11/2025
Dielectric Withstand Capability of AC Vacuum Contactors and Countermeasures
During operation, AC vacuum contactors are often subjected to various overvoltages such as lightning overvoltage and switching overvoltage. Therefore, AC vacuum contactors must have a certain voltage withstand capacity.An AC vacuum contactor is composed of a vacuum interrupter (its structure is shown in Figure 1), a housing, an electromagnetic system, a secondary circuit, and other components. Among these, the vacuum interrupter is the "heart" of the AC vacuum contactor, and its performance dire
Felix Spark
09/09/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.