• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Transformer Protection Settings: Zero-Sequence & Overvoltage Guide

Vziman
Field: Manufacturing
China

1. Zero-Sequence Overcurrent Protection

The operating current for zero-sequence overcurrent protection of grounding transformers is typically determined based on the transformer's rated current and the maximum allowable zero-sequence current during system ground faults. The general setting range is approximately 0.1 to 0.3 times the rated current, with operating time usually set between 0.5 to 1 second to quickly clear ground faults.

2.Overvoltage Protection

Overvoltage protection is a critical component of grounding transformer protection configuration. For ungrounded neutral systems, when a single-phase ground fault occurs, the voltage of sound phases will rise. The overvoltage protection setting value is generally set at 1.2 to 1.3 times the rated phase voltage to prevent transformer insulation damage from overvoltage conditions.

3.Differential Protection

Differential protection for grounding transformers can effectively distinguish between internal and external transformer faults. The calculation of differential protection operating current must consider factors such as transformer turns ratio and unbalanced current. It is typically set to avoid magnetizing inrush current during transformer energization, approximately 2 to 3 times the rated current.

4.Overcurrent Protection

Overcurrent protection serves as backup protection for grounding transformers. The operating current must avoid the transformer's maximum load current, typically set at 1.2 to 1.5 times the rated current. Operating time is determined based on coordination with upstream and downstream protection devices, generally ranging from 1 to 3 seconds.

5.Zero-Sequence Overvoltage Protection

Zero-sequence overvoltage protection primarily addresses abnormal increases in zero-sequence voltage in the system. Its setting value is determined based on normal zero-sequence voltage fluctuation range during system operation, typically 15 to 30V (secondary side), with operating time generally set between 0.5 to 1 second.

6.Temperature Protection

Temperature protection is crucial for ensuring safe operation of grounding transformers. Resistance temperature detectors (RTDs) or thermocouples are typically used to measure transformer oil and winding temperatures. When oil temperature exceeds 85°C or winding temperature exceeds 100°C, an alarm signal is issued. When exceeding higher set values (oil temperature 95°C, winding temperature 110°C), the protection trips the circuit breaker.

7.Negative-Sequence Current Protection

For grounding transformers, negative-sequence current protection is also an important configuration. The negative-sequence current setting value is determined based on the transformer's capability to withstand negative-sequence current, generally 0.05 to 0.1 times the rated current, to protect the transformer from negative-sequence current effects caused by asymmetrical faults.

8.Over-Excitation Protection

Over-excitation protection is indispensable in grounding transformer protection systems. The over-excitation multiple is typically determined based on the transformer core's saturation characteristics, usually set at 1.1 to 1.2 times rated. When over-excitation occurs, the protection promptly operates to safeguard the equipment.

9.Buchholz Relay Protection (Light Gas)

Light gas protection for grounding transformers activates when minor internal faults occur, producing small amounts of gas that accumulate in the Buchholz relay, causing the oil level to drop. When the oil level drops to a certain degree (typically 25-35mm), the light gas protection operates to send an alarm signal, alerting maintenance personnel to investigate.

10.Buchholz Relay Protection (Heavy Gas)

Heavy gas protection is a critical defense line for grounding transformer protection. When serious internal faults occur in the transformer, producing large amounts of gas and oil flow that impact the Buchholz relay, the heavy gas protection operates to trip the circuit breaker. Its operating flow velocity is generally set between 0.6 to 1 m/s.

Give a tip and encourage the author!
Recommended
Intelligent Grounding Transformers for Island Grid Support
1. Project BackgroundDistributed photovoltaic (PV) and energy storage projects are developing rapidly across Vietnam and Southeast Asia, yet face significant challenges:1.1 Grid Instability:Vietnam's power grid experiences frequent fluctuations (particularly in northern industrial zones). In 2023, coal power shortages triggered large-scale blackouts, resulting in daily losses exceeding USD 5 million. Traditional PV systems lack effective neutral grounding management capabilities, making equipmen
12/18/2025
Functions and Selection of Grounding Transformers in Photovoltaic Power Stations
1.Neutral Point Establishment and System StabilityIn photovoltaic power stations, grounding transformers effectively establish a system neutral point. According to relevant power regulations, this neutral point ensures the system maintains certain stability during asymmetric faults, functioning like a "stabilizer" for the entire power system.2.Overvoltage Limitation CapabilityFor photovoltaic power stations, grounding transformers can effectively limit overvoltages. Generally, they can control o
12/17/2025
Electrical Protection: Grounding Transformers and Bus Charging
1. High-Resistance Grounding SystemHigh-resistance grounding can limit ground fault current and appropriately reduce ground overvoltage. However, there is no need to connect a large high-value resistor directly between the generator neutral point and ground. Instead, a small resistor can be used together with a grounding transformer. The primary winding of the grounding transformer is connected between the neutral point and ground, while the secondary winding is connected to a small resistor. Ac
12/17/2025
Wiring Methods and Parameters of Grounding Transformers
Grounding Transformer Winding ConfigurationsGrounding transformers are classified by winding connection into two types: ZNyn (zigzag) or YNd. Their neutral points can be connected to an arc suppression coil or a grounding resistor. Currently, the zigzag (Z-type) grounding transformer connected via an arc suppression coil or a low-value resistor is more commonly used.1. Z-Type Grounding TransformerZ-type grounding transformers come in both oil-immersed and dry-type insulation versions. Among them
12/05/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.