Differences Between Salient-Pole Generators and Nonsalient-Pole Generators

Salient-pole generators and nonsalient-pole generators are two common types of synchronous generators, differing significantly in structure, performance, and application. Below is a detailed comparison of the two:

1. Rotor Structure

  • Salient-Pole Generator:

    • Rotor Shape: In a salient-pole generator, the rotor has distinct magnetic poles that protrude from its surface, forming visible pole shoes. Each pole typically consists of an iron core and an excitation winding.

    • Number of Poles: Salient-pole generators usually have fewer poles (such as 2, 4, 6, 8), with noticeable gaps between the poles ( interpolar regions).

    • Application: Salient-pole generators are primarily used in low-speed, high-capacity applications, such as hydroelectric generators and steam turbine-driven generators.

  • Nonsalient-Pole Generator:

    • Rotor Shape: The rotor of a nonsalient-pole generator has a smooth, cylindrical surface without any visible protruding poles. The excitation windings are embedded in slots within the rotor.

    • Number of Poles: Nonsalient-pole generators typically have more poles (such as 12, 16, 24), distributed evenly around the rotor, with minimal interpolar regions.

    • Application: Nonsalient-pole generators are mainly used in high-speed, medium to small capacity applications, such as steam turbine generators and gas turbine-driven generators.

2. Air Gap Distribution

  • Salient-Pole Generator:

    • Non-uniform Air Gap: Due to the protruding poles, the air gap in a salient-pole generator is smaller at the poles and larger in the interpolar regions. This non-uniform air gap leads to a non-sinusoidal magnetic field distribution, affecting the quality of the output voltage waveform.

    • Harmonic Content: The non-uniform air gap can result in higher harmonic content in the output voltage, particularly third harmonics.

  • Nonsalient-Pole Generator:

    • Uniform Air Gap: The air gap in a nonsalient-pole generator is nearly uniform around the entire circumference, resulting in a more sinusoidal magnetic field distribution and better output voltage waveform quality.

    • Harmonic Content: The uniform air gap minimizes harmonic content, producing a cleaner voltage waveform.

3. Electromagnetic Characteristics

  • Salient-Pole Generator:

    • Direct Axis and Quadrature Axis Reactance: In a salient-pole generator, the direct axis reactance (Xd) and quadrature axis reactance (Xq) differ. Xd is larger because the magnetic flux through the poles encounters less reluctance, while Xq is smaller due to the higher reluctance in the interpolar regions.

    • Short-Circuit Ratio (SCR): Salient-pole generators have a lower short-circuit ratio, typically ranging from 1.0 to 2.0. This results in higher short-circuit currents but slower voltage recovery during faults.

  • Nonsalient-Pole Generator:

    • Direct Axis and Quadrature Axis Reactance: In a nonsalient-pole generator, the direct axis reactance and quadrature axis reactance are almost equal due to the uniform air gap and symmetrical flux path.

    • Short-Circuit Ratio (SCR): Nonsalient-pole generators have a higher short-circuit ratio, typically ranging from 2.0 to 3.0. This results in lower short-circuit currents and faster voltage recovery during faults.

4. Mechanical Characteristics

  • Salient-Pole Generator:

    • Large Rotor Inertia: The larger poles in a salient-pole generator contribute to a higher rotor inertia, making it suitable for low-speed, high-inertia systems, such as hydroelectric turbines.

    • Ventilation and Cooling: The gaps between the poles facilitate the design of cooling ducts, providing better ventilation and cooling performance.

  • Nonsalient-Pole Generator:

    • Small Rotor Inertia: The compact rotor structure of a nonsalient-pole generator results in lower inertia, making it suitable for high-speed, low-inertia systems, such as steam turbines.

    • Ventilation and Cooling: The smooth rotor surface of a nonsalient-pole generator makes ventilation and cooling more complex, often requiring specialized cooling systems.

5. Starting Characteristics

  • Salient-Pole Generator:

    • High Starting Torque: Due to the larger poles, salient-pole generators provide higher electromagnetic torque during startup, making them suitable for applications requiring significant starting torque.

  • Nonsalient-Pole Generator:

    • Lower Starting Torque: Nonsalient-pole generators have relatively lower starting torque but exhibit better dynamic response during high-speed operation.

6. Applications

  • Salient-Pole Generator:

    • Primarily used in low-speed, high-capacity power generation systems, such as hydroelectric power plants and nuclear power plants. The low-speed characteristics of salient-pole generators make them ideal for use with hydro turbines or low-speed steam turbines.

  • Nonsalient-Pole Generator:

    • Primarily used in high-speed, medium to small capacity power generation systems, such as thermal power plants and gas turbine power plants. The high-speed characteristics of nonsalient-pole generators make them ideal for use with steam turbines or gas turbines.

Summary

  • Salient-Pole Generator: Features distinct magnetic poles, non-uniform air gap, and is suitable for low-speed, high-capacity applications like hydroelectric generators. Its advantages include higher starting torque and better cooling performance, but it may have more harmonic content in the output voltage.

  • Nonsalient-Pole Generator: Has a smooth rotor surface, uniform air gap, and is suitable for high-speed, medium to small capacity applications like steam turbine generators. Its advantages include better output voltage waveform quality and faster short-circuit recovery, but it has lower starting torque.

The choice between a salient-pole generator and a nonsalient-pole generator depends on the specific application requirements, including speed, capacity, starting characteristics, and the mechanical and electrical needs of the system.

Give a tip and encourage the author!
Recommended
SST Technology: Full-Scenario Analysis in Power Generation, Transmission, Distribution, and Consumption
SST Technology: Full-Scenario Analysis in Power Generation, Transmission, Distribution, and Consumption
I. Research BackgroundPower System Transformation NeedsChanges in energy structure are placing higher demands on power systems. Traditional power systems are transitioning toward new-generation power systems, with the core differences between them outlined as follows: Dimension Traditional Power System New-Type Power System Technical Foundation Form Mechanical Electromagnetic System Dominated by Synchronous Machines and Power Electronic Equipment Generation-Side Form M
Echo
10/28/2025
SST Transformer Core Loss Calculation and Winding Optimization Guide
SST Transformer Core Loss Calculation and Winding Optimization Guide
SST High-Frequency Isolated Transformer Core Design and Calculation Material Characteristics Impact:Core material exhibits varying loss behavior under different temperatures, frequencies, and flux densities. These characteristics form the foundation of overall core loss and require precise understanding of nonlinear properties. Stray Magnetic Field Interference:High-frequency stray magnetic fields around windings can induce additional core losses. If not properly managed, these parasitic losses
Dyson
10/27/2025
Design of a Four-Port Solid-State Transformer: Efficient Integration Solution for Microgrids
Design of a Four-Port Solid-State Transformer: Efficient Integration Solution for Microgrids
The use of power electronics in industry is increasing, ranging from small-scale applications such as chargers for batteries and LED drivers, to large-scale applications like photovoltaic (PV) systems and electric vehicles. Typically, a power system consists of three parts: power plants, transmission systems, and distribution systems. Traditionally, low-frequency transformers are used for two purposes: electrical isolation and voltage matching. However, 50-/60-Hz transformers are bulky and heavy
Dyson
10/27/2025
SST vs Traditional Transformer: Key Advantages
SST vs Traditional Transformer: Key Advantages
Solid-State Transformers (SST): The Future of Intelligent Power ConversionA solid-state transformer (SST), also known as a power electronic transformer (PET), is a static power conversion device that integrates power electronics, high-frequency transformation, and advanced control systems based on electromagnetic induction. It enables the conversion of electrical energy from one set of voltage, current, and frequency characteristics to another—while offering active control, bidirectional power f
Echo
10/27/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.