Short Circuit Ratio of a Synchronous Machine

Edwiin
Edwiin
Field: Power switch
China

The Short Circuit Ratio (SCR) of a Synchronous Machine

The Short Circuit Ratio (SCR) of a synchronous machine is defined as the ratio of the field current needed to generate rated voltage under open-circuit conditions to the field current required to sustain rated armature current during a short-circuit condition. For a three-phase synchronous machine, the SCR can be derived from its Open-Circuit Characteristic (O.C.C) at rated speed and Short-Circuit Characteristic (S.C.C), as illustrated in the figure below:

From the above figure, the short circuit ratio is given by the equation shown below.

Since the triangles Oab and Ode are similar. Therefore,

Direct Axis Synchronous Reactance (Xd)

The direct axis synchronous reactance Xd is defined as the ratio of the open-circuit voltage corresponding to a specific field current to the armature short-circuit current under the same field current condition.

For a field current of magnitude Oa, the direct axis synchronous reactance (in ohms) is expressed by the following equation:

Relationship Between SCR and Synchronous Reactance

From equation (7), it is evident that the Short Circuit Ratio (SCR) equals the reciprocal of the per-unit direct axis synchronous reactance Xd. In a saturated magnetic circuit, the value of Xd is contingent upon the degree of magnetic saturation.

Significance of the Short Circuit Ratio (SCR)

The SCR is a critical parameter for synchronous machines, influencing their operational characteristics, physical dimensions, and cost. Key implications include:

  • Voltage Regulation Impact

    • Synchronous generators with lower SCR values exhibit more pronounced terminal voltage fluctuations with load changes. Maintaining constant terminal voltage requires wide-ranging adjustments to the field current If).

  • Stability Limitations

    • A smaller SCR corresponds to reduced synchronizing power, which is essential for maintaining synchronism. This results in a lower stability limit, meaning machines with low SCR are less stable when operating in parallel with other generators.

  • Trade-offs in Design

    • High-SCR machines offer superior voltage regulation and enhanced steady-state stability but entail higher armature short-circuit fault currents. Additionally, they influence machine size and cost due to design trade-offs.

The excitation voltage of a synchronous machine is described by the equation:

For the same value of Tph Excitation voltage is directly proportional to the field flux per pole.

The synchronous inductance is given as:

Relationship Between SCR and Air Gap

Thus, the Short Circuit Ratio (SCR) is directly proportional to the air gap reluctance or air gap length. Increasing the air gap length elevates the SCR, though this requires a higher field magnetomotive force (MMF) to maintain the same excitation voltage (). To increase the field MMF, either the field current or the number of field turns must be augmented, necessitating taller field poles and an enlarged machine diameter.

Impact on Machine Design

This leads to a key conclusion: a higher SCR inherently increases the size, weight, and cost of the synchronous machine.

Typical SCR Values by Machine Type

  • Cylindrical Rotor Machines: SCR ranges from 0.5 to 0.9.

  • Salient-Pole Machines: SCR falls between 1.0 and 1.5.

  • Synchronous Compensators: SCR is typically 0.4.

These values reflect the design trade-offs between stability, voltage regulation, and physical dimensions in different synchronous machine configurations.

Give a tip and encourage the author!
Recommended
SST Technology: Full-Scenario Analysis in Power Generation, Transmission, Distribution, and Consumption
SST Technology: Full-Scenario Analysis in Power Generation, Transmission, Distribution, and Consumption
I. Research BackgroundPower System Transformation NeedsChanges in energy structure are placing higher demands on power systems. Traditional power systems are transitioning toward new-generation power systems, with the core differences between them outlined as follows: Dimension Traditional Power System New-Type Power System Technical Foundation Form Mechanical Electromagnetic System Dominated by Synchronous Machines and Power Electronic Equipment Generation-Side Form M
Echo
10/28/2025
Rectifier vs Power Transformer: Key Differences
Rectifier vs Power Transformer: Key Differences
Differences Between Rectifier Transformers and Power TransformersRectifier transformers and power transformers both belong to the transformer family, but they differ fundamentally in application and functional characteristics. The transformers commonly seen on utility poles are typically power transformers, while those supplying electrolytic cells or electroplating equipment in factories are usually rectifier transformers. Understanding their differences requires examining three aspects: working
Echo
10/27/2025
SST Transformer Core Loss Calculation and Winding Optimization Guide
SST Transformer Core Loss Calculation and Winding Optimization Guide
SST High-Frequency Isolated Transformer Core Design and Calculation Material Characteristics Impact:Core material exhibits varying loss behavior under different temperatures, frequencies, and flux densities. These characteristics form the foundation of overall core loss and require precise understanding of nonlinear properties. Stray Magnetic Field Interference:High-frequency stray magnetic fields around windings can induce additional core losses. If not properly managed, these parasitic losses
Dyson
10/27/2025
Upgrade Traditional Transformers: Amorphous or Solid-State?
Upgrade Traditional Transformers: Amorphous or Solid-State?
I. Core Innovation: A Dual Revolution in Materials and StructureTwo key innovations:Material Innovation: Amorphous AlloyWhat it is: A metallic material formed by ultra-rapid solidification, featuring a disordered, non-crystalline atomic structure.Key Advantage: Extremely low core loss (no-load loss), which is 60%–80% lower than that of traditional silicon steel transformers.Why it matters: No-load loss occurs continuously, 24/7, throughout a transformer’s lifecycle. For transformers with low loa
Echo
10/27/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.