Characteristics of Series Wound DC Generator

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

Series Generator Definition

A series wound DC generator is defined as a generator where the field windings, armature windings, and external load circuit are connected in series, causing the same current to flow through each part.

6384c2c4ed7e37c553f19ff196067cd0.jpeg

 In these types of generators the field windings, armature windings and external load circuit all are connected in series as shown in figure below.

Therefore, the same current flows through armature winding, field winding and the load.

Let, I = Ia = Isc = IL

Here, Ia = armature current

Isc = series field current

IL = load current

There are generally three most important characteristics of series wound DC generator which show the relation between various quantities such as series field current or excitation current, generated voltage, terminal voltage and load current.

Magnetic Characteristic Curve

The curve which shows the relation between no load voltage and the field excitation current is called magnetic or open circuit characteristic curve. As during no load, the load terminals are open circuited, there will be no field current in the field since, the armature, field and load are series connected and these three make a closed loop of circuit. So, this curve can be obtained practically be separating the field winding and exciting the DC generator by an external source.

In the diagram, the AB curve shows the magnetic characteristic of a series wound DC generator. The curve is linear until the poles reach saturation. After this point, the terminal voltage doesn’t increase significantly with additional field current. Due to residual magnetism, there is an initial voltage across the armature, so the curve starts slightly above the origin at point A.

Internal Characteristic Curve

The internal characteristic curve shows the relationship between the voltage generated in the armature and the load current. This curve accounts for the drop caused by the armature reaction’s demagnetizing effect, making the actual generated voltage (Eg) less than the no-load voltage (E0). Therefore, the curve drops slightly from the open circuit characteristic curve. In the diagram, the OC curve represents this internal characteristic.

External Characteristic Curve

8b10a3e22241adc27b8a7e58dcfcf090.jpeg

The external characteristic curve shows the variation of terminal voltage (V) with the load current (IL). Terminal voltage of this type of generator is obtained by subtracting the ohomic drop due to armature resistance (Ra) and series field resistance (Rsc) from the actually generated voltage (Eg).

Terminal voltage V = Eg – I(Ra + Rsc)

The external characteristic curve lies below the internal characteristic curve because the value of terminal voltage is less than the generated voltage. Here in the figure OD curve is showing the external characteristic of the series wound DC generator.

From the characteristics of a series wound DC generator, we can see that as the load increases (and therefore the load current), the terminal voltage initially rises. However, after reaching a peak, it starts to decrease due to the demagnetizing effect of the armature reaction. The dotted line in the figure shows this phenomenon, indicating that the current remains roughly constant despite changes in load resistance.

When the load increases, so does the field current, as the field is series connected with the load. Similarly, the armature current increases as it is also series connected. However, due to saturation, the magnetic field strength and induced voltage do not significantly increase. The increased armature current leads to a greater armature reaction, causing a drop in load voltage. If the load voltage drops, the load current also decreases, as current is proportional to voltage (Ohm’s law). These simultaneous effects mean there is no significant change in load current in the dotted portion of the external characteristic curve. This behavior makes the series DC generator a constant current generator.

Constant Current Generator

A series wound DC generator is known as a constant current generator because the load current remains nearly constant despite variations in load resistance.

Give a tip and encourage the author!
Recommended
SST Technology: Full-Scenario Analysis in Power Generation, Transmission, Distribution, and Consumption
SST Technology: Full-Scenario Analysis in Power Generation, Transmission, Distribution, and Consumption
I. Research BackgroundPower System Transformation NeedsChanges in energy structure are placing higher demands on power systems. Traditional power systems are transitioning toward new-generation power systems, with the core differences between them outlined as follows: Dimension Traditional Power System New-Type Power System Technical Foundation Form Mechanical Electromagnetic System Dominated by Synchronous Machines and Power Electronic Equipment Generation-Side Form M
Echo
10/28/2025
SST Transformer Core Loss Calculation and Winding Optimization Guide
SST Transformer Core Loss Calculation and Winding Optimization Guide
SST High-Frequency Isolated Transformer Core Design and Calculation Material Characteristics Impact:Core material exhibits varying loss behavior under different temperatures, frequencies, and flux densities. These characteristics form the foundation of overall core loss and require precise understanding of nonlinear properties. Stray Magnetic Field Interference:High-frequency stray magnetic fields around windings can induce additional core losses. If not properly managed, these parasitic losses
Dyson
10/27/2025
Design of a Four-Port Solid-State Transformer: Efficient Integration Solution for Microgrids
Design of a Four-Port Solid-State Transformer: Efficient Integration Solution for Microgrids
The use of power electronics in industry is increasing, ranging from small-scale applications such as chargers for batteries and LED drivers, to large-scale applications like photovoltaic (PV) systems and electric vehicles. Typically, a power system consists of three parts: power plants, transmission systems, and distribution systems. Traditionally, low-frequency transformers are used for two purposes: electrical isolation and voltage matching. However, 50-/60-Hz transformers are bulky and heavy
Dyson
10/27/2025
SST vs Traditional Transformer: Key Advantages
SST vs Traditional Transformer: Key Advantages
Solid-State Transformers (SST): The Future of Intelligent Power ConversionA solid-state transformer (SST), also known as a power electronic transformer (PET), is a static power conversion device that integrates power electronics, high-frequency transformation, and advanced control systems based on electromagnetic induction. It enables the conversion of electrical energy from one set of voltage, current, and frequency characteristics to another—while offering active control, bidirectional power f
Echo
10/27/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.