Polarity Test of a Transformer – Circuit Diagram and Working

Edwiin
05/15/2025

Polarity in Two-Winding Transformers
In two-winding transformers, one terminal of a winding is always positive relative to the other at any instant. Transformer polarity refers to the relative direction of induced voltages between the high-voltage (HV) and low-voltage (LV) windings. In practical transformers, winding terminals are brought out as leads, and polarity defines how these leads are connected and labeled.
Significance of Transformer Polarity
Understanding polarity is critical for several operational and engineering tasks:
  • Instrument Transformer Connection (CTs and PTs):Proper polarity ensures accurate measurement of current and voltage in power systems.
  • Protective Relay Coordination:Correct polarity is essential for relays to detect faults and operate reliably.
  • Three-Phase Transformer Construction:Polarity determines how single-phase windings are interconnected to form three-phase configurations (e.g., delta or wye).
  • Parallel Operation of Transformers:Transformers in parallel must have identical polarity to avoid circulating currents and magnetic flux cancellation.

Terminal Markings and Polarity Identification

Instead of using traditional dot markings, it is often clearer to use H1/H2 for primary (HV) windings and X1/X2 for secondary (LV) windings to denote polarity:
  • H1 and H2: Markers for the primary winding terminals, indicating the start and end of the HV winding.
  • X1 and X2: Corresponding markers for the secondary winding terminals (LV side).
During polarity testing, these labels help identify:
  • The instantaneous voltage relationship between HV and LV windings (e.g., H1 and X1 are "in-phase" if polarity is additive).
  • Whether the transformer has additive (series-aiding) or subtractive (series-opposing) polarity, which impacts how windings are connected in circuits.

Key Consideration

Incorrect polarity can lead to:
  • Faulty measurements in instrument transformers.
  • Malfunctioning protective relays.
  • Excessive circulating currents or overheating in parallel-connected transformers.
By standardizing on clear terminal markings (H1/H2 and X1/X2), engineers and technicians can ensure proper transformer polarity, enhancing the safety, reliability, and efficiency of power systems.
Transformer Polarity
The dot convention (or dot notation) is a standard method used to denote the polarity of windings in a transformer.
Transformer Polarity and Dot Convention
In Figure A, two dots are placed on the same side of the primary and secondary windings. This indicates that the current entering the dotted terminal of the primary winding has the same direction as the current leaving the dotted terminal of the secondary winding. Consequently, the voltages at the dotted ends are in phase—if the voltage at the dotted point of the primary is positive, the voltage at the dotted point of the secondary will also be positive.
 
In Figure B, the dots are positioned on opposite sides of the windings, signifying that the windings are wound in opposite directions around the core. Here, the voltages at the dotted points are out of phase: a positive voltage at the primary’s dotted terminal corresponds to a negative voltage at the secondary’s dotted terminal.
Additive vs. Subtractive Polarity
Transformer polarity can be classified as additive or subtractive. To determine which type applies, connect one terminal of the primary winding to one terminal of the secondary winding and attach a voltmeter across the remaining terminals of both windings.
Additive Polarity
  • Voltmeter Reading: Measures the sum of the primary voltage VA and secondary voltage VB, denoted as VC.
  • Formula: VC = VA + VB.
  • Winding Configuration: The windings are oriented such that their magnetic fluxes oppose each other when currents flow into the dotted terminals.

The circuit diagram of additive polarity is shown in the figure below.

Subtractive Polarity

In subtractive polarity, the voltmeter measures the difference between the primary voltage and the secondary voltage. Denoted as VC, the voltmeter reading is expressed by the equation:
The circuit diagram of subtractive polarity is shown in the figure below.
 

 

Circuit Diagram of Polarity Test

The circuit diagram of the polarity test is shown in the figure below.

Polarity Testing of Transformers
The primary winding terminals are denoted as A1, A2, and the secondary winding terminals as a1, a2. As shown in the figure, a voltmeter VA is connected across the primary winding, VB across the secondary winding, and VC between the primary terminal A1 and secondary terminal a1.
An autotransformer is used to provide a variable AC supply to the primary winding. All voltmeter readings are recorded under this configuration:
  • If the voltmeter VC reads the sum of VA and VB, the transformer exhibits additive polarity.
  • If VC) reads the difference between VA and VB, the transformer exhibits subtractive polarity.

Polarity Test Using a DC Source (Battery)

The AC voltage method described above can be impractical for determining the relative polarity of two-winding transformers. A more convenient approach uses a DC source (battery), a switch, and a DC permanent-magnet voltmeter. The connection diagram for this method—including the correct battery polarity—is shown in the figure below.
A switch is connected in series with the primary winding. When the switch is closed, the battery is connected to the primary winding, allowing current to flow through it. This generates flux linkage in both windings, inducing electromotive force (EMF) in both the primary and secondary windings.
The induced EMF in the primary winding has a positive polarity at the end connected to the battery's positive terminal. To determine the secondary winding's polarity:
  • If the DC voltmeter connected across the secondary winding shows a positive reading at the moment the switch is closed, the secondary terminal connected to the voltmeter's positive probe has the same polarity as the primary's positive terminal (i.e., the dotted terminals are correctly identified).
  • If the voltmeter deflects to the negative side, the secondary terminal connected to the voltmeter's positive probe has opposite polarity to the primary's positive terminal.
Edwiin

Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!

Example of Process Improvement for Enhancing Consistency of Small - Batch High - Temperature Special Transformers
Example of Process Improvement for Enhancing Consistency of Small - Batch High - Temperature Special Transformers
Given the lack of manufacturers for such transformers on the market, we design them in - house. We provide technical specs to partners, specifying materials like high - temp enameled wires.Electrical signals from downhole logging tools, transmitted via these transformers, impact formation - to - surface signal reliability. Thus, improving transformer consistency boosts signal uniformity, enhancing logging tool accuracy and our market competitiveness.Our common signal transformers are EI - type,
Vziman
07/28/2025
Analysis of the Process of Transformer Oil of Specialty Transformers Being Contaminated by Microorganisms and the Treatment Measures
Analysis of the Process of Transformer Oil of Specialty Transformers Being Contaminated by Microorganisms and the Treatment Measures
1 OverviewCases of transformer oil contaminated by microorganisms have been reported both domestically and internationally. Individual transformer manufacturers, user units, and research institutions have conducted specialized studies, but all focused on power transformers. This paper targets specialty transformers for specific applications (e.g., rectifier transformers for graphitization furnaces, submerged arc furnace transformers), exploring the process of microbial contamination of their tra
Rockwell
07/28/2025
Power Supply Design of the Group Testing Device for Special Transformers in Electrified Railways
Power Supply Design of the Group Testing Device for Special Transformers in Electrified Railways
1 Hardware Design of Tester Power SupplyThis device uses a standard small - signal generating device to generate small - current signals with the required frequency and phase angle. Then, through the amplifying circuit and phase - modulating circuit, the working power supply is generated.1.1 Power Frequency Sine Wave Small - Current Signal Generating DeviceThe sine wave generating circuit is mainly composed of the waveform generating chip MAX038 produced by MAXIM Corporation of the United States
Ron
07/28/2025
Analysis of Testing Methods for Turns Ratio and Connection Mode of Special Transformers
Analysis of Testing Methods for Turns Ratio and Connection Mode of Special Transformers
1 Error Analysis of Traditional Turn Ratio Testing MethodsThe QJ35 turn ratio bridge and other single-phase-phase-based testers all use the double-voltmeter principle. The QJ35, however, eliminates power supply fluctuation interference via bridge balance. For three-phase transformer ratio testing with a single power supply, corresponding terminals must be shorted and data converted, turning three-phase tests into independent single-phase measurements, with √3 Yd conversion based on connect
Felix Spark
07/28/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!