• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Polarity Test of a Transformer – Circuit Diagram and Working

Edwiin
Edwiin
Field: Power switch
China

Polarity in Two-Winding Transformers

In two-winding transformers, one terminal of a winding is always positive relative to the other at any instant. Transformer polarity refers to the relative direction of induced voltages between the high-voltage (HV) and low-voltage (LV) windings. In practical transformers, winding terminals are brought out as leads, and polarity defines how these leads are connected and labeled.

Significance of Transformer Polarity

Understanding polarity is critical for several operational and engineering tasks:

  • Instrument Transformer Connection (CTs and PTs):Proper polarity ensures accurate measurement of current and voltage in power systems.

  • Protective Relay Coordination:Correct polarity is essential for relays to detect faults and operate reliably.

  • Three-Phase Transformer Construction:Polarity determines how single-phase windings are interconnected to form three-phase configurations (e.g., delta or wye).

  • Parallel Operation of Transformers:Transformers in parallel must have identical polarity to avoid circulating currents and magnetic flux cancellation.

Terminal Markings and Polarity Identification

Instead of using traditional dot markings, it is often clearer to use H1/H2 for primary (HV) windings and X1/X2 for secondary (LV) windings to denote polarity:

  • H1 and H2: Markers for the primary winding terminals, indicating the start and end of the HV winding.

  • X1 and X2: Corresponding markers for the secondary winding terminals (LV side).

During polarity testing, these labels help identify:

  • The instantaneous voltage relationship between HV and LV windings (e.g., H1 and X1 are "in-phase" if polarity is additive).

  • Whether the transformer has additive (series-aiding) or subtractive (series-opposing) polarity, which impacts how windings are connected in circuits.

Key Consideration

Incorrect polarity can lead to:

  • Faulty measurements in instrument transformers.

  • Malfunctioning protective relays.

  • Excessive circulating currents or overheating in parallel-connected transformers.

By standardizing on clear terminal markings (H1/H2 and X1/X2), engineers and technicians can ensure proper transformer polarity, enhancing the safety, reliability, and efficiency of power systems.

Transformer Polarity
The dot convention (or dot notation) is a standard method used to denote the polarity of windings in a transformer.

Transformer Polarity and Dot Convention

In Figure A, two dots are placed on the same side of the primary and secondary windings. This indicates that the current entering the dotted terminal of the primary winding has the same direction as the current leaving the dotted terminal of the secondary winding. Consequently, the voltages at the dotted ends are in phase—if the voltage at the dotted point of the primary is positive, the voltage at the dotted point of the secondary will also be positive.

 

In Figure B, the dots are positioned on opposite sides of the windings, signifying that the windings are wound in opposite directions around the core. Here, the voltages at the dotted points are out of phase: a positive voltage at the primary’s dotted terminal corresponds to a negative voltage at the secondary’s dotted terminal.

Additive vs. Subtractive Polarity

Transformer polarity can be classified as additive or subtractive. To determine which type applies, connect one terminal of the primary winding to one terminal of the secondary winding and attach a voltmeter across the remaining terminals of both windings.

Additive Polarity

  • Voltmeter Reading: Measures the sum of the primary voltage VA and secondary voltage VB, denoted as VC.

  • Formula: VC = VA + VB.

  • Winding Configuration: The windings are oriented such that their magnetic fluxes oppose each other when currents flow into the dotted terminals.

The circuit diagram of additive polarity is shown in the figure below.

Subtractive Polarity

In subtractive polarity, the voltmeter measures the difference between the primary voltage and the secondary voltage. Denoted as VC, the voltmeter reading is expressed by the equation:

The circuit diagram of subtractive polarity is shown in the figure below.

 

 

Circuit Diagram of Polarity Test

The circuit diagram of the polarity test is shown in the figure below.

Polarity Testing of Transformers

The primary winding terminals are denoted as A1, A2, and the secondary winding terminals as a1, a2. As shown in the figure, a voltmeter VA is connected across the primary winding, VB across the secondary winding, and VC between the primary terminal A1 and secondary terminal a1.

An autotransformer is used to provide a variable AC supply to the primary winding. All voltmeter readings are recorded under this configuration:

  • If the voltmeter VC reads the sum of VA and VB, the transformer exhibits additive polarity.

  • If VC) reads the difference between VA and VB, the transformer exhibits subtractive polarity.

Polarity Test Using a DC Source (Battery)

The AC voltage method described above can be impractical for determining the relative polarity of two-winding transformers. A more convenient approach uses a DC source (battery), a switch, and a DC permanent-magnet voltmeter. The connection diagram for this method—including the correct battery polarity—is shown in the figure below.

A switch is connected in series with the primary winding. When the switch is closed, the battery is connected to the primary winding, allowing current to flow through it. This generates flux linkage in both windings, inducing electromotive force (EMF) in both the primary and secondary windings.

The induced EMF in the primary winding has a positive polarity at the end connected to the battery's positive terminal. To determine the secondary winding's polarity:

  • If the DC voltmeter connected across the secondary winding shows a positive reading at the moment the switch is closed, the secondary terminal connected to the voltmeter's positive probe has the same polarity as the primary's positive terminal (i.e., the dotted terminals are correctly identified).

  • If the voltmeter deflects to the negative side, the secondary terminal connected to the voltmeter's positive probe has opposite polarity to the primary's positive terminal.

Give a tip and encourage the author!
Recommended
Toroidal vs Square Transformers: Key Differences
Toroidal vs Square Transformers: Key Differences
What Is a Toroidal Transformer?A toroidal transformer is a major type of electronic transformer that has been widely used in household appliances and other electronic equipment with higher technical requirements. Its primary applications are as a power transformer and an isolation transformer. Abroad, toroidal transformers are already available in complete series and are extensively used in computers, medical equipment, telecommunications, instruments, and lighting applications.In China, toroida
Dyson
11/06/2025
What causes a transformer to be noisier under no-load conditions?
What causes a transformer to be noisier under no-load conditions?
When a transformer is operating under no-load conditions, it often produces louder noise than under full load. The primary reason is that, with no load on the secondary winding, the primary voltage tends to be slightly higher than nominal. For example, while the rated voltage is typically 10 kV, the actual no-load voltage may reach around 10.5 kV.This elevated voltage increases the magnetic flux density (B) in the core. According to the formula:B = 45 × Et / S(where Et is the designed volts-per-
Noah
11/05/2025
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
When installing an arc suppression coil, it is important to identify the conditions under which the coil should be taken out of service. The arc suppression coil should be disconnected under the following circumstances: When a transformer is being de-energized, the neutral-point disconnector must be opened first before performing any switching operations on the transformer. The energizing sequence is the reverse: the neutral-point disconnector should be closed only after the transformer is energ
Echo
11/05/2025
What fire prevention measures are available for power transformer failures?
What fire prevention measures are available for power transformer failures?
Failures in power transformers are commonly caused by severe overload operation, short circuits due to winding insulation degradation, aging of transformer oil, excessive contact resistance at connections or tap changers, failure of high- or low-voltage fuses to operate during external short circuits, core damage, internal arcing in oil, and lightning strikes.Since transformers are filled with insulating oil, fires can have severe consequences—ranging from oil spraying and ignition to, in extrem
Noah
11/05/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.