Essential Dry-Type Transformer Maintenance Steps

Noah
Noah
Field: Design & Maintenance
Australia

Routine Maintenance and Care of Dry-Type Power Transformers

Due to their flame-resistant and self-extinguishing properties, high mechanical strength, and ability to withstand large short-circuit currents, dry-type transformers are easy to operate and maintain. However, under poor ventilation conditions, their heat dissipation performance is inferior to that of oil-immersed transformers. Therefore, the key focus in the operation and maintenance of dry-type transformers is controlling the temperature rise during operation.

How should dry-type transformers be maintained and cared for?

  • Regular cleaning of the equipment. Dust accumulation must be removed promptly to ensure proper airflow and prevent insulation breakdown. Transformers should be thoroughly cleaned and dusted every six months, and the surrounding environment should remain dry and well-ventilated.

  • Enhance operation and maintenance of ventilation systems. Ensure cooling fans operate normally. For high-capacity transformers, turbo fans should be used to improve cooling efficiency.

  • Monitor temperature and humidity changes. Maintain a balanced temperature and humidity level, paying close attention to sudden changes in relative humidity readings. Ensure the temperature controller functions properly to prevent failures. Equip the transformer with built-in thermal resistors in a redundant configuration to enhance reliability and prevent transformer faults.

  • Inspect for moisture and condensation in cold, humid conditions. If operation is suddenly interrupted in cold and humid environments, check for abnormal moisture or frost formation. Any ice or frost on the surface must be removed to prevent insulation breakdown and ensure normal operation of the insulation windings. As long as the insulation resistance is not less than 2 MΩ per 1000 V, the transformer can operate normally. The heat generated during operation will restore the insulation resistance to normal levels. Under normal operating conditions, the transformer’s body temperature is higher than the ambient temperature, so insulation resistance typically does not decrease.

  • Inspect fasteners and connections for looseness. In addition to short circuits, prolonged operation may cause vibration-induced loosening of fasteners and connecting parts, potentially leading to overheating. Regular inspections, temperature monitoring (e.g., using temperature-sensitive wax), preventive testing, and tightening of loose components are essential to ensure safe and reliable operation.

Give a tip and encourage the author!
Recommended
What are the common faults encountered during the operation of power transformer longitudinal differential protection?
What are the common faults encountered during the operation of power transformer longitudinal differential protection?
Transformer Longitudinal Differential Protection: Common Issues and SolutionsTransformer longitudinal differential protection is the most complex among all component differential protections. Misoperations occasionally occur during operation. According to 1997 statistics from the North China Power Grid for transformers rated 220 kV and above, there were 18 incorrect operations in total, of which 5 were due to longitudinal differential protection—accounting for approximately one-third. Causes of
Felix Spark
11/05/2025
How to Identify Internal Faults in a Transformer?
How to Identify Internal Faults in a Transformer?
Measure DC resistance: Use a bridge to measure the DC resistance of each high- and low-voltage winding. Check whether the resistance values among phases are balanced and consistent with the manufacturer’s original data. If phase resistance cannot be measured directly, line resistance may be measured instead. The DC resistance values can indicate whether the windings are intact, whether there are short circuits or open circuits, and whether the contact resistance of the tap changer is normal. If
Felix Spark
11/04/2025
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
The tap changer operating handle shall be equipped with a protective cover. The flange at the handle shall be well sealed with no oil leakage. Locking screws shall securely fasten both the handle and the drive mechanism, and the handle rotation shall be smooth without binding. The position indicator on the handle shall be clear, accurate, and consistent with the tap voltage regulation range of the winding. Limit stops shall be provided at both extreme positions. The insulating cylinder of the t
Leon
11/04/2025
How to Overhaul a Transformer Conservator (Oil Pillow)?
How to Overhaul a Transformer Conservator (Oil Pillow)?
Overhaul Items for Transformer Conservator:1. Ordinary-Type Conservator Remove the end covers on both sides of the conservator, clean rust and oil deposits from inner and outer surfaces, then apply insulating varnish to the inner wall and paint to the outer wall; Clean components such as the dirt collector, oil level gauge, and oil plug; Check that the connecting pipe between the explosion-proof device and the conservator is unobstructed; Replace all sealing gaskets to ensure good sealing with n