How does silica gel play the role of hygroscopic agent in transformer ventilation system?

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

The Role of Silica Gel in Transformer Breathing Systems

Silica gel (Silica Gel) is a commonly used adsorbent with excellent hygroscopic properties, widely applied in power equipment for drying and moisture prevention. In transformer breathing systems, silica gel primarily functions to absorb moisture from the air entering the transformer tank, preventing water from entering the oil and insulation materials, thereby protecting the transformer's insulation performance.

1. Working Principle of Silica Gel

  • Adsorption Mechanism: Silica gel has a large number of micropores on its surface, which can adsorb water molecules from the air. As air passes through the transformer breather, the moisture is absorbed by the silica gel, allowing dry air to enter the tank.

  • Reversibility: The adsorption process of silica gel is reversible. When it becomes saturated with moisture, it can be regenerated by heating, releasing the absorbed water and restoring its hygroscopic capacity. This allows silica gel to be reused, extending its service life.

2. Application of Silica Gel in Transformer Breathing Systems

Breather: Transformers are typically equipped with a breather (also known as a desiccant breather) that connects the oil tank to the atmosphere. Inside the breather, silica gel filters the incoming air, ensuring that only dry air enters the tank. As the internal temperature of the transformer changes, the pressure inside the tank also fluctuates, causing gas exchange between the tank and the outside environment. The silica gel in the breather adsorbs moisture from the air, preventing wet air from entering the tank.

Sealing System: In some transformers, silica gel is also used as a desiccant in the sealing system to prevent moisture from entering the tank through poorly sealed areas.

Consequences of Inadequate Humidity Control

If humidity control in a transformer is inadequate, moisture can enter the tank and dissolve in the transformer oil or deposit on the insulation materials, leading to a series of issues that can severely affect the transformer's performance and lifespan. Below are the main consequences of inadequate humidity control:

1. Degradation of Insulation Performance

  • Impact on Insulation Materials: Moisture reduces the dielectric strength of both transformer oil and solid insulation materials (such as paper and fiber). As moisture content increases, the dielectric constant of the insulation materials rises, and the breakdown voltage decreases, making partial discharges or short circuits more likely.

  • Accelerated Aging: Moisture also accelerates the aging process of insulation materials, shortening the transformer's lifespan. In high-temperature conditions, moisture can combine with oxidation products in the oil to form acidic substances, further corroding the insulation materials.

2. Deterioration of Oil Quality

  • Excess Moisture in Oil: When moisture enters the transformer oil, it alters the physical and chemical properties of the oil. Moisture promotes oxidation reactions in the oil, generating acidic substances and precipitates, which reduce the oil's antioxidant capacity and cooling efficiency.

  • Impaired Heat Transfer: Moisture reduces the thermal conductivity of the oil, affecting the transformer's heat dissipation. This can lead to higher operating temperatures, accelerating the aging and damage of insulation materials.

3. Partial Discharge and Arc Faults

  • Partial Discharge: Moisture lowers the breakdown voltage of the oil, especially in high-voltage transformers, increasing the likelihood of partial discharge. Partial discharge not only damages insulation materials but can also lead to arc faults, causing sudden transformer shutdowns.

  • Arc Faults: Severe moisture ingress can result in arc faults, potentially leading to fires or explosions, posing significant safety risks to the power system.

4. Corrosion of Core and Windings

  • Corrosion of Metal Components: Moisture entering the transformer tank can come into contact with metal components such as the core and windings, causing corrosion. This effect is accelerated when the oil contains acidic substances, weakening the mechanical strength of the metal components and affecting the transformer's normal operation.

  • Winding Deformation: Moisture can cause the insulation layers of the windings to soften or swell, leading to winding deformation or short circuits. In severe cases, the windings may need to be replaced, increasing maintenance costs.

5. Impact on Transformer Reliability

  • Frequent Shutdowns: Due to degraded insulation performance, deteriorated oil quality, and other issues, the transformer may experience frequent faults, requiring shutdowns for maintenance, which can impact the stability and reliability of the power system.

  • Shortened Lifespan: Long-term inadequate humidity control can accelerate the aging of the transformer, shortening its lifespan and increasing the costs of maintenance and replacement.

Ensuring Effective Humidity Control

To ensure effective humidity control and avoid the above problems, the following measures are necessary:

  • Regular Inspection of Silica Gel Condition: Silica gel changes color (typically from blue to pink) when it absorbs moisture. It should be replaced or regenerated promptly when it becomes saturated to maintain its hygroscopic capacity.

  • Maintain Breather Ventilation: Ensure that the breather remains unobstructed, allowing air to pass through the silica gel for proper drying. Avoid blockages that could impede the flow of air.

  • Strengthen Sealing: Regularly inspect the transformer's sealing system to ensure that the tank is well-sealed, preventing moisture from entering through poorly sealed areas.

  • Monitor Moisture Content in Oil: Periodically sample and analyze the moisture content in the transformer oil to detect inadequate humidity control early and take corrective actions.

  • Install Dehumidification Equipment: For large transformers or those operating in humid environments, consider installing dehumidification equipment (such as dry air generators) to enhance humidity control.

Summary

Silica gel plays a crucial role in transformer breathing systems by effectively absorbing moisture from the air entering the tank, protecting the transformer's insulation performance and oil quality. If humidity control is inadequate, moisture can enter the tank, leading to a range of issues such as degraded insulation performance, deteriorated oil quality, partial discharge, metal component corrosion, and reduced transformer reliability and lifespan. Therefore, ensuring the good condition of silica gel and implementing effective humidity control measures are essential for maintaining the safe and stable operation of transformers.

Give a tip and encourage the author!
Recommended
How to Identify Internal Faults in a Transformer?
How to Identify Internal Faults in a Transformer?
Measure DC resistance: Use a bridge to measure the DC resistance of each high- and low-voltage winding. Check whether the resistance values among phases are balanced and consistent with the manufacturer’s original data. If phase resistance cannot be measured directly, line resistance may be measured instead. The DC resistance values can indicate whether the windings are intact, whether there are short circuits or open circuits, and whether the contact resistance of the tap changer is normal. If
Felix Spark
11/04/2025
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
The tap changer operating handle shall be equipped with a protective cover. The flange at the handle shall be well sealed with no oil leakage. Locking screws shall securely fasten both the handle and the drive mechanism, and the handle rotation shall be smooth without binding. The position indicator on the handle shall be clear, accurate, and consistent with the tap voltage regulation range of the winding. Limit stops shall be provided at both extreme positions. The insulating cylinder of the t
Leon
11/04/2025
How to Overhaul a Transformer Conservator (Oil Pillow)?
How to Overhaul a Transformer Conservator (Oil Pillow)?
Overhaul Items for Transformer Conservator:1. Ordinary-Type Conservator Remove the end covers on both sides of the conservator, clean rust and oil deposits from inner and outer surfaces, then apply insulating varnish to the inner wall and paint to the outer wall; Clean components such as the dirt collector, oil level gauge, and oil plug; Check that the connecting pipe between the explosion-proof device and the conservator is unobstructed; Replace all sealing gaskets to ensure good sealing with n
Felix Spark
11/04/2025
Why is it difficult to increase the voltage level?
Why is it difficult to increase the voltage level?
The solid-state transformer (SST), also known as a power electronic transformer (PET), uses voltage level as a key indicator of its technological maturity and application scenarios. Currently, SSTs have reached voltage levels of 10 kV and 35 kV on the medium-voltage distribution side, while on the high-voltage transmission side, they remain in the stage of laboratory research and prototype validation. The table below clearly illustrates the current status of voltage levels across different appli
Echo
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.