Transformers Insulation Materials in Oil-Immersed & Dry Type T/F

Edwiin
Edwiin
Field: Power switch
China

Insulation Systems in Oil-Immersed Transformers

The most prevalent insulation for high-voltage windings in modern transformers consists of enamel-coated conductors with kraft paper interlayer insulation.Low-voltage busbars may employ bare conductors with paper insulation between layers.Notably, paper wrapping on busbar conductors is being gradually replaced by synthetic polymer coatings or synthetic fabric wraps.

The adoption of aluminum wires, busbars, and strip conductors with enamel coatings presents specific challenges for distribution transformer manufacturers: aluminum spontaneously forms an insulating oxide layer upon air exposure, which must be removed or mitigated at all electrical connection points.Additionally, electrical-grade aluminum conductors are relatively soft, prone to cold flow and differential expansion issues during mechanical clamping.Splicing methods for aluminum wires include soldering or crimping with specialized tools that penetrate enamel and oxide layers, while sealing out oxygen at contact areas.Aluminum busbars can be welded using TIG (tungsten inert gas) welding, or cold-welded/crimped to copper/aluminum connectors. Bolted connections to soft aluminum are feasible with proper joint cleaning.

Insulation Materials in Dry-Type Transformers

Dry-type transformer windings are typically sealed or coated with resin/varnish to protect against environmental factors causing degradation.Insulation media for primary/secondary windings are categorized as:

  • Cast coils: Formed via epoxy resin vacuum casting for superior corona resistance.

  • Vacuum-pressure encapsulated: Sealed under vacuum-pressure to enhance insulation integrity.

  • Vacuum-pressure impregnated (VPI): Insulation paint infiltrates windings under vacuum-pressure for uniform coverage.

  • Coated insulation: Surface coatings provide environmental protection for winding

Cast Coil

  • The winding is reinforced or placed in a mold and cast with resin under vacuum pressure.

  • Encasement in solid insulation minimizes noise levels. Vacuum-pressure resin casting eliminates voids that cause corona.

  • The solid insulation system ensures superior mechanical and short-circuit strength, while resisting moisture and contaminants.

Vacuum-Pressure Encapsulated

The winding is embedded in resin under vacuum pressure.Vacuum-pressure encapsulation eliminates corona-causing voids. The winding offers excellent mechanical/short-circuit strength and protection against moisture/contaminants.

Vacuum-Pressure Impregnated

The winding is permeated with varnish under vacuum pressure.Impregnation provides protection against moisture and contaminants.

Coated

The winding is dipped in varnish or resin. Coated windings offer moderate protection against moisture/contaminants for standard environments.

Give a tip and encourage the author!
Recommended
How to Identify Internal Faults in a Transformer?
How to Identify Internal Faults in a Transformer?
Measure DC resistance: Use a bridge to measure the DC resistance of each high- and low-voltage winding. Check whether the resistance values among phases are balanced and consistent with the manufacturer’s original data. If phase resistance cannot be measured directly, line resistance may be measured instead. The DC resistance values can indicate whether the windings are intact, whether there are short circuits or open circuits, and whether the contact resistance of the tap changer is normal. If
Felix Spark
11/04/2025
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
The tap changer operating handle shall be equipped with a protective cover. The flange at the handle shall be well sealed with no oil leakage. Locking screws shall securely fasten both the handle and the drive mechanism, and the handle rotation shall be smooth without binding. The position indicator on the handle shall be clear, accurate, and consistent with the tap voltage regulation range of the winding. Limit stops shall be provided at both extreme positions. The insulating cylinder of the t
Leon
11/04/2025
How to Overhaul a Transformer Conservator (Oil Pillow)?
How to Overhaul a Transformer Conservator (Oil Pillow)?
Overhaul Items for Transformer Conservator:1. Ordinary-Type Conservator Remove the end covers on both sides of the conservator, clean rust and oil deposits from inner and outer surfaces, then apply insulating varnish to the inner wall and paint to the outer wall; Clean components such as the dirt collector, oil level gauge, and oil plug; Check that the connecting pipe between the explosion-proof device and the conservator is unobstructed; Replace all sealing gaskets to ensure good sealing with n
Felix Spark
11/04/2025
Why is it difficult to increase the voltage level?
Why is it difficult to increase the voltage level?
The solid-state transformer (SST), also known as a power electronic transformer (PET), uses voltage level as a key indicator of its technological maturity and application scenarios. Currently, SSTs have reached voltage levels of 10 kV and 35 kV on the medium-voltage distribution side, while on the high-voltage transmission side, they remain in the stage of laboratory research and prototype validation. The table below clearly illustrates the current status of voltage levels across different appli
Echo
11/03/2025