SG10 Series Transformer Overload Protection Solution | Prevent Overheating and Damage, View Now

Rockwell
Rockwell
Field: Manufacturing
China

Operating Conditions in National Standard GB 6450-1986

Ambient temperature:

  • Maximum ambient temperature: +40°C

  • Daily average maximum temperature: +30°C

  • Annual average maximum temperature: +20°C

  • Minimum temperature: -30°C (outdoor); -5°C (indoor)

  • Horizontal axis: Product load;

  • Vertical axis: Average coil temperature rise in Kelvin (note: not in Celsius).

For Class H insulation products, the long-term temperature resistance of insulation materials is stipulated by the state as 180°C. However, the insulation materials used in CEEG’s SG (B) series transformer products include NOMEX paper (Class C, 220°C) and insulation coatings (Class H, 180°C or Class C, 220°C), which provide a large margin for product overload.

Examples

  • a. When the transformer operates at 70% load, its average coil temperature rise is 57K. If the ambient temperature is 25°C, the average temperature of the coil is calculated as:

  • T = Coil temperature rise + Ambient temperature = 57 + 25 = 82°C.

  • b. When the transformer operates at 120% load with an ambient temperature of 40°C, the average temperature of the coil is calculated as:

  • T = 133 + 40 = 173°C (which is lower than 200°C). The local hot spot temperature inside the coil is 185°C (173 × 1.07).

Note

SG (B) series transformers can achieve 120% load without fans; with fan cooling, they can handle short-term overloads of more than 50%. Although long-term overload operation is not recommended, this indicates that SG10 products have the capability to provide additional load in emergency situations, and also proves that the products have a sufficiently long service life under rated load conditions, reducing long-term investment costs.

Producing Class H (180°C) products using Class C (220°C) insulation materials is far superior to Japanese epoxy resin products (which are produced using Class F (155°C) materials and have no overload margin).

Sufficient overload capacity can withstand severe electric field interference and ensure stable power supply. This makes SG10 transformers highly reliable equipment, suitable for locations with unstable power supply, industries with high overload requirements, and industries with strict power stability requirements. Examples include the glass industry, iron and steel industry, automobile manufacturing, commercial buildings, microelectronics industry, cement industry, water treatment and pump stations, petrochemical industry, hospitals, and data centers.

Key Term Explanations

  • Class H/C/F insulation: Standard classifications for insulation materials in electrical equipment, defined by their maximum long-term allowable operating temperatures (Class H: 180°C, Class C: 220°C, Class F: 155°C), in line with international insulation classification norms.

  • Temperature rise in Kelvin (K): A unit of temperature difference where 1K = 1°C; using Kelvin for temperature rise avoids confusion with absolute temperature in Celsius, which is a common practice in electrical engineering.

  • NOMEX paper: A high-temperature resistant insulation paper (Class C) widely used in transformers, known for excellent thermal stability and dielectric properties.

Give a tip and encourage the author!
Recommended
How to Identify Internal Faults in a Transformer?
How to Identify Internal Faults in a Transformer?
Measure DC resistance: Use a bridge to measure the DC resistance of each high- and low-voltage winding. Check whether the resistance values among phases are balanced and consistent with the manufacturer’s original data. If phase resistance cannot be measured directly, line resistance may be measured instead. The DC resistance values can indicate whether the windings are intact, whether there are short circuits or open circuits, and whether the contact resistance of the tap changer is normal. If
Felix Spark
11/04/2025
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
The tap changer operating handle shall be equipped with a protective cover. The flange at the handle shall be well sealed with no oil leakage. Locking screws shall securely fasten both the handle and the drive mechanism, and the handle rotation shall be smooth without binding. The position indicator on the handle shall be clear, accurate, and consistent with the tap voltage regulation range of the winding. Limit stops shall be provided at both extreme positions. The insulating cylinder of the t
Leon
11/04/2025
How to Overhaul a Transformer Conservator (Oil Pillow)?
How to Overhaul a Transformer Conservator (Oil Pillow)?
Overhaul Items for Transformer Conservator:1. Ordinary-Type Conservator Remove the end covers on both sides of the conservator, clean rust and oil deposits from inner and outer surfaces, then apply insulating varnish to the inner wall and paint to the outer wall; Clean components such as the dirt collector, oil level gauge, and oil plug; Check that the connecting pipe between the explosion-proof device and the conservator is unobstructed; Replace all sealing gaskets to ensure good sealing with n
Felix Spark
11/04/2025
Why is it difficult to increase the voltage level?
Why is it difficult to increase the voltage level?
The solid-state transformer (SST), also known as a power electronic transformer (PET), uses voltage level as a key indicator of its technological maturity and application scenarios. Currently, SSTs have reached voltage levels of 10 kV and 35 kV on the medium-voltage distribution side, while on the high-voltage transmission side, they remain in the stage of laboratory research and prototype validation. The table below clearly illustrates the current status of voltage levels across different appli
Echo
11/03/2025