Transformer Use and Installation: Ensuring Safe and Reliable Operation

Vziman
Vziman
Field: Manufacturing
China

Operating Conditions for Transformers

  • The installation site must be free from flooding, located at an altitude not exceeding 1,000 meters, and maintained in an ambient temperature not exceeding 40°C. Relative humidity may reach 100% within an operating temperature range of 40°C to -25°C (on-load tap changers and temperature controllers must be rated for -25°C).

  • The installation area should be clean, free from conductive dust and corrosive gases, and equipped with sufficient natural or mechanical ventilation.

  • When installing, maintain a minimum clearance of 300 mm between the transformer and walls or other obstacles. A 300 mm gap should also be provided between adjacent transformers. These distances may be reduced as necessary in space-constrained environments.

Product Packaging and Transportation

  • Transformers are available in open-type (without protective enclosure) and enclosed-type (with protective housing) configurations. They are typically transported by rail, sea, or road, and may be shipped either partially disassembled (e.g., on-load tap changers, temperature controllers, cooling units, and enclosures packed separately) or fully assembled within a shipping crate.

  • For crated units, lifting slings should be attached to the four bottom corners of the crate. When lifting from open packaging, use dedicated lifting equipment. A trial lift of 100–150 mm is recommended prior to full hoisting to verify stability and detect any abnormalities.

  • Avoid transport routes with inclines exceeding 15°. Position the transformer’s center of gravity along the vehicle’s vertical centerline to ensure even load distribution. Securely fasten the unit to the vehicle to prevent shifting or tipping, aligning the transformer’s long axis with the direction of travel.

Transformer Use and Installation.jpg

Pre-Installation Visual Inspection

  • After unpacking, remove protective covers and inspect the unit’s external condition. Pay close attention to the mechanical integrity of windings and core, the tightness of clamping structures, and the condition of connection bolts.

  • Re-tighten all fasteners and compression points on windings and core in sequence to ensure no looseness.

  • Clean the surface using dry compressed air or a clean, lint-free cloth to remove dust and debris.

  • If the transformer has been in storage for an extended period and shows signs of moisture or condensation, perform drying treatment until the winding insulation resistance meets acceptable standards.

Pre-Commissioning Checks

  • Measure the DC resistance of high- and low-voltage windings and verify results against factory test certificate values.

  • Inspect core grounding for reliability and ensure no foreign objects are creating unintended electrical paths.

  • Perform insulation resistance tests to confirm dielectric integrity.

Network Connection and Operation

  • Prior to full commissioning, operate the transformer under no-load conditions. After three energizing and de-energizing cycles, inspect and fine-tune the protection systems.

  • At the factory, the high-voltage tap changer is set to the rated position. If voltage adjustment is required during operation, it must be performed in accordance with the nameplate-specified rated tap voltage (off-circuit regulation) and only after the transformer has been completely de-energized.

Give a tip and encourage the author!
Recommended
How to Identify Internal Faults in a Transformer?
How to Identify Internal Faults in a Transformer?
Measure DC resistance: Use a bridge to measure the DC resistance of each high- and low-voltage winding. Check whether the resistance values among phases are balanced and consistent with the manufacturer’s original data. If phase resistance cannot be measured directly, line resistance may be measured instead. The DC resistance values can indicate whether the windings are intact, whether there are short circuits or open circuits, and whether the contact resistance of the tap changer is normal. If
Felix Spark
11/04/2025
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
The tap changer operating handle shall be equipped with a protective cover. The flange at the handle shall be well sealed with no oil leakage. Locking screws shall securely fasten both the handle and the drive mechanism, and the handle rotation shall be smooth without binding. The position indicator on the handle shall be clear, accurate, and consistent with the tap voltage regulation range of the winding. Limit stops shall be provided at both extreme positions. The insulating cylinder of the t
Leon
11/04/2025
How to Overhaul a Transformer Conservator (Oil Pillow)?
How to Overhaul a Transformer Conservator (Oil Pillow)?
Overhaul Items for Transformer Conservator:1. Ordinary-Type Conservator Remove the end covers on both sides of the conservator, clean rust and oil deposits from inner and outer surfaces, then apply insulating varnish to the inner wall and paint to the outer wall; Clean components such as the dirt collector, oil level gauge, and oil plug; Check that the connecting pipe between the explosion-proof device and the conservator is unobstructed; Replace all sealing gaskets to ensure good sealing with n
Felix Spark
11/04/2025
Why is it difficult to increase the voltage level?
Why is it difficult to increase the voltage level?
The solid-state transformer (SST), also known as a power electronic transformer (PET), uses voltage level as a key indicator of its technological maturity and application scenarios. Currently, SSTs have reached voltage levels of 10 kV and 35 kV on the medium-voltage distribution side, while on the high-voltage transmission side, they remain in the stage of laboratory research and prototype validation. The table below clearly illustrates the current status of voltage levels across different appli
Echo
11/03/2025