Why Does the Secondary Insulation of Outdoor Current Transformers Drop?

Felix Spark
07/05/2025

I'm Felix, a 15-Year Veteran in the CT Industry, Sharing What You Need to Watch Out For

Hi everyone, I'm Felix, and I've been working with current transformers (CTs) for over 15 years. Today, let’s talk about why the secondary insulation of outdoor CTs sometimes drops, and what you can do to prevent it.

Common Causes:
1. Moisture Ingress — Poor Sealing is the Biggest Problem!

Outdoor CTs are constantly exposed to wind and rain. If the sealing isn't tight enough, moisture can get inside and seriously damage insulation performance.

In coastal areas or humid environments, this problem gets worse — salt mist and dampness can cause mold, corrosion, or even short circuits.

Example: I once found water droplets inside a CT during a site inspection. It turned out the sealing ring had aged and allowed rainwater to slowly seep in.

2. Dust Buildup — Dirt Can Conduct Electricity Too!

Dust, salt particles, and other pollutants can stick to the surface or internal terminals of the CT. When combined with humidity, they form conductive paths that reduce insulation resistance.

Regular cleaning is key — especially in heavily polluted areas. Don’t wait until there’s a problem to wipe things down.

3. Material Aging — Everything Gets Old Eventually

No material lasts forever, especially when exposed to the elements.

UV exposure, extreme temperatures, and chemical corrosion all speed up aging. Over time, materials like silicone rubber or epoxy resin may crack, harden, or lose their insulating properties.

How to check for aging:

  • Look for cracks, discoloration, or brittleness.
  • Monitor if insulation values drop year after year.
  • Track historical test data for sudden changes.

4. Improper Installation — Problems Start Right After Setup

If installation is rushed or done carelessly, problems will follow.

Examples include:

  • Poor grounding;
  • Loose wiring;
  • Installing in places prone to water accumulation;
  • Forgetting or improperly installing waterproof seals.

These issues might not show up immediately, but over time they lead to contact failure, moisture ingress, or partial discharge — all bad news for insulation.

Real-life example: Once, I found unstable insulation readings due to a poorly installed waterproof seal. The technician had just loosely wrapped it instead of pressing it properly — which let rainwater in and caused an insulation breakdown.

5. Lack of Maintenance — Ignoring Care Is Like Slow Self-Damage

Many sites install CTs and forget them until something breaks. But like a car, CTs need regular maintenance.

This includes:

  • Cleaning terminals;
  • Checking seals;
  • Measuring insulation;
  • Replacing worn parts.

Ignoring these basic steps means small issues become big ones — and fixing them later costs more.

How to Detect and Prevent These Issues?

Here are some practical tips:

  • Measure insulation resistance regularly:Use a 2500V megohmmeter to check secondary-to-ground and primary-to-secondary insulation. Most manufacturers recommend values above 1000 MΩ.
  • Check the appearance:Look for cracks, rust, deformation, or signs of moisture. Any of these could signal deeper issues.
  • Improve environmental protection:In high-humidity or salty environments, consider adding space heaters or using CTs with higher IP ratings.
  • Schedule regular maintenance and cleaning:At least once a year, inspect and clean your CTs — replace old seals, tighten connections, and update worn components.

As someone with 15 years of experience in the CT industry, here's my takeaway:

“Insulation problems in outdoor CTs don’t happen suddenly — they build up over time.”

With proper installation, regular checks, and good maintenance habits, most issues can be caught early and avoided altogether.

If you're dealing with insulation drops, unusual data, or unsure how to proceed, feel free to reach out. I’m happy to share more real-world experiences and solutions.

May every CT run safely and reliably, protecting the power grid with precision!

— Felix

Felix Spark

Hey there! I'm an electrical engineer specializing in Failure and Maintenance. I've dedicated my career to ensuring the seamless operation of electrical systems. I excel at diagnosing complex electrical failures, from malfunctioning industrial motors to glitchy power distribution networks. Using state - of - the - art diagnostic tools and my in - depth knowledge, I pinpoint issues quickly. On this platform, I'm eager to share my insights, exchange ideas, and collaborate with fellow experts. Let's work together to enhance the reliability of electrical setups.

Vibration Testing and Fault Research of High - Voltage Shunt Reactors
Vibration Testing and Fault Research of High - Voltage Shunt Reactors
1 Vibration Monitoring and Fault Diagnosis Technology for High - Voltage Shunt Reactors1.1 Measuring Point Layout StrategyVibration characteristic parameters (frequency, power, energy) of high - voltage shunt reactors are fully recorded in operation logs. For vibration analysis, focus on resolving the complexity of electric field distribution at winding ends. Quantitatively evaluate field - strength distribution under operating/lightning overvoltage and voltage gradient characteristics of longit
Felix Spark
07/24/2025
Research on Online Diagnosis of Secondary Circuit Faults of Electronic Current Transformers
Research on Online Diagnosis of Secondary Circuit Faults of Electronic Current Transformers
1 Principle and Role of Electronic Current Transformers1.1 Working Principle of ECTAn Electronic Current Transformer (ECT) is a key device for managing safe power system operations, converting large currents into manageable small-current signals for measurement and control. Unlike traditional transformers (relying on direct magnetic field interaction between primary and secondary windings), ECTs use sensors (e.g., Hall effect sensors) to detect magnetic field changes from the primary winding. Th
Felix Spark
07/22/2025
What are the fault diagnosis and handling technologies for 35kV combined transformers?
What are the fault diagnosis and handling technologies for 35kV combined transformers?
For fault diagnosis and handling of 35kV combined transformers, the following technical means can be adopted:Insulation Fault DiagnosisUse equipment such as high-voltage test transformers, power frequency withstand voltage testers, and partial discharge detection systems to conduct a comprehensive assessment of the insulation performance of combined transformers. When the insulation resistance is found to be lower than 1000MΩ or the dielectric loss factor tanδ exceeds 0.5%, an applic
Felix Spark
07/21/2025
What are the common faults of low-voltage voltage transformers?
What are the common faults of low-voltage voltage transformers?
Open - Circuit Fault on the Secondary SideOpen - circuit in the secondary side is a typical fault of low - voltage voltage transformers, showing abnormal voltmeter readings (zero/fluctuation), faulty power meters, buzzing noises, and core overheating. When open - circuited, the secondary voltage spikes (no secondary current to balance the primary EMF), causing core saturation, flux distortion, and potential overheating/damage.Causes include loose terminals, poor contact, or human error. In low
Felix Spark
07/18/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!