• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Dead Short: What is it? (vs Short Circuit vs Bolted Fault vs Ground Fault)

Electrical4u
Electrical4u
Field: Basic Electrical
0
China
what is a dead short

What is a Dead Short?

A dead short is an electrical circuit that results in current flowing along an unintended path with no resistance or impedance. This results in an excessive current flowing through the circuit, which can damage equipment or cause electrical shocks to those nearby.

A dead short is difficult to track and diagnose as the current builds rapidly and trips the breaker immediately.

It is mainly caused due to direct connection between positive and negative power wires or a direct connection between the positive wire and the ground.

Dead shorts are very dangerous because it causes a high amount of current to flow through the circuit.

Dead Short vs Short Circuit

To understand the difference between a dead short and a short circuit, let’s take an example. Consider a voltage difference between two points is 150 V.

If we measure the voltage between two points in normal conditions, it shows 150 V. But, if the voltage between two points is less than 150 V, it is called a short circuit.

Some voltage drop occurs during the short circuit, and some resistance appears between these two points.

If the measured voltage is 0 V, it is called dead short. It means there is zero resistance of a circuit.

The difference between the normal condition, short-circuit, and dead-short describes in the figure below.



normal condition short circuit condition dead short condition
Normal Condition, Short-circuit Condition, Dead Short Condition



Dead Short vs Bolted Fault

A bolted fault is defined as a fault with zero impedance. It produces extreme fault current in the system.

When all conductors are connected to the ground with a metallic conductor, the fault is known as a bolted fault.

The bolted fault (bolted short) is quite similar to the dead short. As in the dead short also, the resistance is zero.

Dead Short vs Ground Fault

The ground fault occurs in the power system when the hot wire (live wire) accidentally connected with the earth wire or grounded equipment frame.

In this condition, the frame of equipment energies with dangerous voltage. In the ground fault, there is some amount of ground resistance present. And the fault current depends on the ground resistance.

Therefore, the ground fault is different from the dead short.

Example of a Dead Short

To understand the dead short, let’s take an example. Consider a network having three resistors connected in series, as shown in the figure below.



example of dead short



In normal conditions, the current passes through the circuit are I ampere. And the total resistance of a circuit is REQ.

REQ=5+15+20

\[ R_{EQ} = 40 \Omega \]


According to ohm’s law;


\[ V = IR \]


\[ 40 = I (40) \]


\[ I = 1 A \]


Therefore, the current that passes through the circuit is 1 A in normal condition.

If we short battery terminals by a metallic wire or very low resistance (ideally zero resistance), the circuit looks like the figure below.



dead short



As points A and B are shorted with ideally zero resistance, it is known as dead short. And the current that passes through the resisters is zero.

All the current will flow through the shorted terminals. Because the current always follows a low resistance path.

Due to zero resistance, the current passes through terminals A and B is;


\[ V = IR\]


\[ I = \frac{V}{R} \]


\[ I = \frac{40}{0} \]


\[ I = \infy \]

From the calculation, infinite current will flow through the point A and B. But practically, there is some amount of current that will flow. And this current is very high compared to the standard current (1 A).

In a power system network, you can consider a part of a network instead of three resisters. The circuit will look like the figure below.



dead short in network



Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Solid insulation assistance combined with dry air insulation is a development direction for 24 kV ring main units. By balancing insulation performance and compactness, the use of solid auxiliary insulation allows passing insulation tests without significantly increasing phase-to-phase or phase-to-ground dimensions. Encapsulation of the pole can address the insulation of the vacuum interrupter and its connected conductors.For the 24 kV outgoing busbar, with the phase spacing maintained at 110 mm,
Dyson
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
What Is THD? How It Affects Power Quality & Equipment
What Is THD? How It Affects Power Quality & Equipment
In the field of electrical engineering, the stability and reliability of power systems are of paramount importance. With the advancement of power electronics technology, the widespread use of nonlinear loads has led to an increasingly serious problem of harmonic distortion in power systems.Definition of THDTotal Harmonic Distortion (THD) is defined as the ratio of the root mean square (RMS) value of all harmonic components to the RMS value of the fundamental component in a periodic signal. It is
Encyclopedia
11/01/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.